| 2007-08-09 15:29:59 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PER 220.52(B) LAUNDRY CIRCUIT LOAD A LOAD OF NOT |
| | LESS THAN 1500 VOLT-AMPERES SHALL BE INCLUDED FOR EACH |
| | 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED AS REQUIRED BY |
| | 210.11(C)(2). THIS LOAD SHALL BE PERMITTED TO BE |
| | INCLUDED WITH THE GENERAL LIGHTING LOAD AND SUBJECTED |
| | TO THE DEMAND FACTORS PROVIDED IN TABLE 220.42. |
| | |
| | 2} 220.54 ELECTRIC CLOTHES DRYERS ? DWELLING UNIT(S) |
| | THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES DRYERS IN A |
| | DWELLING UNIT(S) SHALL BE EITHER 5000 WATTS |
| | (VOLT-AMPERES) OR THE NAMEPLATE RATING, WHICHEVER IS |
| | LARGER, FOR EACH DRYER SERVED. |
| | |
| | 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| | 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR |
| | DEFICIENCIES. |
| | |
| | 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |