| 2007-09-10 11:49:05 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.)SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE |
| | WITH THE PRODUCT APPROVAL ANCHOR CHARTS; IN THIS CASE, |
| | WILL BE WALL MOUNT 1 THROUGH 4, CEILING MOUNT 5, FLOOR |
| | MOUNT 6 THORUGH 8, ETC.SEE PP 10-11 OF THE PRODUCT |
| | APPROVAL. |
| | |
| | 2.)YOU HAVE CIRCLED WALL MOUNT 1 AND FLOOR MOUNT 7 |
| | ANCHOR SPACING.NOTE THAT THESE CONNECTION TYPES |
| | REQUIRE A CONCRETE SUBSTRATE, BUT YOUR INSTALLATION |
| | SCHEDULE STATES THAT THE OPENINGS HAVE A BLOCK |
| | SUBSTRATE. |
| | |
| | 3.)INFORMATION CIRCLED ON THE PRODUCT APPROVAL SHOULD |
| | CORRELATE WITH THE INSTALLATION SCHEDULE.YOU'VE |
| | CIRCLED 6", 7", 5.5" SPACINGS, BUT HAVE WRITTEN 9" ON |
| | THE INSTALLATION SCHEDULE. |
| | |
| | 4.)A 2" EDGE DISTANCE REQUIRES A FACTOR OF .5, SEE |
| | SHEET 11.NOTE THE MINIMUM ANCHOR SPACING OF 3" FOR |
| | TAPCONS.OPENING 4, 2" EDGE DISTANCE, IF USING FLOOR |
| | MOUNT 7, 75PSF, REQUIRES A SPACING OF 5.5 WITH .5 |
| | FACTOR WHICH EQUALS A SPACING OF 2.75.THIS DOES NOT |
| | MEET THE MINIMUM ANCHOR SPACING REQUIREMENT. |
| | |