Plan Review Notes
Plan Review Notes For Permit 07080192
Permit Number 07080192
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-10 11:49:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE PRODUCT APPROVAL ANCHOR CHARTS; IN THIS CASE,
 WILL BE WALL MOUNT 1 THROUGH 4, CEILING MOUNT 5, FLOOR
 MOUNT 6 THORUGH 8, ETC.SEE PP 10-11 OF THE PRODUCT
 APPROVAL.
  
 2.)YOU HAVE CIRCLED WALL MOUNT 1 AND FLOOR MOUNT 7
 ANCHOR SPACING.NOTE THAT THESE CONNECTION TYPES
 REQUIRE A CONCRETE SUBSTRATE, BUT YOUR INSTALLATION
 SCHEDULE STATES THAT THE OPENINGS HAVE A BLOCK
 SUBSTRATE.
  
 3.)INFORMATION CIRCLED ON THE PRODUCT APPROVAL SHOULD
 CORRELATE WITH THE INSTALLATION SCHEDULE.YOU'VE
 CIRCLED 6", 7", 5.5" SPACINGS, BUT HAVE WRITTEN 9" ON
 THE INSTALLATION SCHEDULE.
  
 4.)A 2" EDGE DISTANCE REQUIRES A FACTOR OF .5, SEE
 SHEET 11.NOTE THE MINIMUM ANCHOR SPACING OF 3" FOR
 TAPCONS.OPENING 4, 2" EDGE DISTANCE, IF USING FLOOR
 MOUNT 7, 75PSF, REQUIRES A SPACING OF 5.5 WITH .5
 FACTOR WHICH EQUALS A SPACING OF 2.75.THIS DOES NOT
 MEET THE MINIMUM ANCHOR SPACING REQUIREMENT.
  