| Plan Review Notes For Permit 07080145 |
| Permit Number |
07080145 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-03-28 18:15:29 | BUILDING REVISION CHECKLIST: | | | | | | 1- NEW FOOTING REVISION ALSO SHOWS A NEW CONCRETE BLOCK | | | WALL BECAUSE EXISTING WALL WAS A WOOD FRAMED STRUCTURE. | | | NEED TO REVISE CONNECTORS THAT CORRESPOND TO NEW | | | CONCRETE BLOCK WALL.. REVISE SECOND FLOOR FRAMING PLAN | | | AND CONNECTORS THAT REFLECT REVISED CONDITIONS.NEED | | | TO SPECIFY WOOD TO MASONRY CONNECTORS THAT REFLECT NEW | | | PROPOSED WALL.SEE CATALOG FOR PROPER CONNECTORS TO | | | BE SPECIFIED.SPECIFY ALL CONNECTORS TO VERIFY | | | COMPLIANCE WITHSEC. R601.2 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | | | | 2- SPECIFY BEAM SIZE AND REINFORCEMENT AT OPENING AREA | | | THAT CONNECTS EXISTING HOUSE WITH PROPOSED ADDITION. | | | SEE COMMENTS ON PLANS SUBMITTED. | | | | | | 2) SHEETSREVISED ARE THREE, NOT ONE. OWES $20.00 | | | REVISION FEES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|