| 2008-06-13 14:53:19 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | REVISION TO MECHANICAL PLAN. |
| | *** DENIED *** |
| | |
| | 1) THE COOLING LOAD CALCULATIONS WILL NEED TO BE |
| | REVISED AS THE ZONES BEING SERVICED BY EACH UNIT HAVE |
| | CHANGED, PER 2004 FBC 13-607.1.ABC.1. |
| | |
| | 2) THE FIRST FLOOR PLAN SHOWS A 12" DUCT COMING FROM |
| | THE SECOND FLOOR, BUT THE SECOND FLOOR PLAN SHOWS NO |
| | 12" DUCT GOING TO THE FIRST FLOOR, PLEASE CORRECT. |
| | |
| | 3) PLEASE LIST ALL A/C EQUIPMENT AS #1 OR #2 (AIR |
| | HANDLERS AND CONDENSERS). |
| | |
| | 3) THE 14X14 RETURN AIR TRANSFER GRILL IS TO SMALL FOR |
| | THE RETURN AIR TO PASS THROUGH FROM THE FIRST FLOOR AND |
| | THE MASTER SUITE, SEE 2004 FBC/R M1602.4. |
| | |
| | **2004 FBC/R M1602.4 BALANCED RETURN AIR. TRANSFER |
| | GRILLES SHALL USE 50 SQUARE INCHES (OF GRILLE AREA) TO |
| | 100 CFM (OF SUPPLY AIR) FOR SIZING THROUGH-THE-WALL |
| | TRANSFER GRILLES AND USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR |
| | BALANCE |
| | (A)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE |
| | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |