| 2007-08-23 16:20:22 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| | LOCATIONS. |
| | NOTE: NOT ALL WASTE AND TRAPS ARE SIZED ON SHEET 4, |
| | SANITARY ISOMETRIC RISER DIAGRAM. PLEASE CORRECT THIS |
| | ON THE RESUBMITTAL. |
| | |
| | 2. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DOES NOT |
| | REFLECT THE FLOOR PLAN PER FBC-2004 CHAPTER 1, THE CITY |
| | OF WEST PALM BEACH AMENDMENTS SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE |
| | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| | AS DETERMINED BY THE |
| | BUILDING OFFICIAL. PLEASE CORRECT THE FOLLOWING. |
| | |
| | A} THE RELOCATED DOUBLE BOWL KITCHEN SINK IS MISSING |
| | FROM THE SANITARY ISOMETRIC PLUMBING RISER DIAGRAM. |
| | PLEASE CORRECT THIS AND RESUBMIT. |
| | |
| | B} THE RECONFIGURED EXISTING 1ST FLOOR BATH IS MISSING |
| | FROM THE SANITARY ISOMETRIC PLUMBING RISER DIAGRAM. |
| | PLEASE CORRECT THIS AND RESUBMIT. |
| | |
| | C} THERE ARE TWO WASHING MACHINES INDICATED ON THE |
| | SANITARY ISOMETRIC PLUMBING RISER DIAGRAM BUT ONLY ONE |
| | (WASHING MACHINE) IS BEING INDICATED ON THE FLOOR PLAN. |
| | PLEASE CLARIFY AND CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | D} THE 2ND FLOOR MASTER BATH. |
| | |
| | 3. SHEET 4, SANITARY ISOMETRIC RISER DIAGRAM THE |
| | RELOCATED WASHING MACHINE MUST DISCHARGE DOWNSTREAM OF |
| | THE WET VENTED BATHROOM PER FBC-2004, PLUMBING, SECTION |
| | 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | NOTE: ALSO THE FOLLOWING IS REQUIRED FOR THE WASHING |
| | MACHINE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE THE WASHING MACHINE |
| | STANDPIPE. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 |
| | INCH. |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT |
| | 4 FEET ABOVE FINNISH FLOOR (4' A.F.F.) |
| | |
| | 4. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM |
| | THE INDICATED PLUMBING TIED INTO THE 2ND FLOOR PLUMBING |
| | STACK ON THE !ST FLOOR IS WRONG PER FBC-2004 PLUMBING, |
| | SECTION 908.3 CONNECTION AT DIFFERENT |
| | LEVELS. WHERE THE FIXTURE DRAINS CONNECT |
| | AT DIFFERENT LEVELS, THE VENT SHALL |
| | CONNECT AS A VERTICAL EXTENTION OF THE |
| | VERTICLE DRAIN. THE VERTICAL DRAIN PIPE CONNECCTING THE |
| | TWO FIXTURE DRAINS SHALL |
| | BE CONSIDERED THE VENT FOR THE LOWER |
| | FIXTURE DRAIN, AND SHALL BE SIZED IN |
| | ACCORDANCE WITH TABLE 908.3. THE UPPER |
| | FIXTURE SHALL NOT BE A WATER CLOSET. |
| | |
| | 5. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM |
| | A VENT IS REQUIRED FOR THE 2ND FLOORMASTER BATH |
| | SHOWER AND TUB PER TABLE 906.1 BECAUSE THE 2 INCH TRAPS |
| | ARE MORE THAN 6 FEET FROM THE VENT. |
| | |
| | 6. SHEET 4, SANITARY ISOMETRIC PLUMBING RISER DIAGRAM |
| | A TWO-WAY CLEANOUT IS REQUIRED PER FBC-2004 PLUMBING |
| | SECTION 708.3.5 BUILDING DRAIN AND BUILDING SEWER |
| | JUNCTION. THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE |
| | JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED, PLEASE |
| | INCLUDE A TRANSMITTAL LETTER INDICATING HOW EACH ITEM |
| | WAS ADDRESSED AND PROVIDE ONE COPY OF ALL OLD/VOIDED |
| | SHEETS FOR REFERENCE ONLY. |
| | |
| | **NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK |
| | ON THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR |
| | REFERENCE FOR RESUBMITTAL AND PLEASE REFERENCE THE |
| | SANITARY PLUMBING ISOMETRIC RISER DIAGRAM THAT REFLECTS |
| | THE FLOOR PLAN AND IS CODE COMPLIANT ATTACHED TO THESE |
| | COMMENTS FOR THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |