2007-08-27 12:47:26RESIDENTIALADDITION AND RENOVATION BUILDING REVIEW
 FIRST CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE ANDFBC
 2004 WITH 2006/2007 REVISIONS.
  
 1- OWES $15.86 FOR NEW ADDITION RADON FEES.
  
 2- NEED RECORDEDNOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDASTATUTE.
  
 3- PLANS NEED TO SPECIFY CONSTRUCTION TYPE AS REQUIRED
 BY SEC. 602.1 FBC 2004.
  
 4- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- PLANS TO SPECIFY ALL LOADS, INCLUDING THE ATTIC LIVE
 LOAD AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 6- EXTERIOR ELEVATIONS NEED TO SPECIFY ROOF PITCH. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- PROVIDE COMPLETE INTERIOR BEARING WALL SECTIONBY
 STAIRWAY OPENING THAT MATCHES PLANS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004. INFORMATION SUBMITTED DOESN'T
 MATCH PLANS.
  
 8- ENERGY CALCULATIONS ARE TAKING THE CEILING FANS
 CREDIT. THEREFORE,NEED TO SPECIFY ON PLANS CEILING
 FAN SIZES TO VERIFY COMPLIANCE WITH TABLE 13-607.1.A.1
 OF FBC 2004.
  
 9- TRUSS PACKAGE:
 A) ARCHITECT CAN'T SIGN AND SEAL THE TRUSS PLAN.
 ARCHITECT IS REQUIRED TO REVIEW AND APPROVE TRUSS
 PACKAGE, NOT TO SIGN AND SEAL IT.
  
 B) TRUSS ENGINEER NEEDS TO ADHERE TO SEC.
 61G15-23.002 OF FLORIDAADMINISTRATIVE CODEBY:
 * SIGNING AND SEALINGALL DRAWINGS WITH ORIGINAL
 SIGNATURE AND SEAL.
 ** PROVIDINGALL HIS INFORMATION IN ALL SHEETS.
  
 C) THIS IS A TWO STORY HOUSE.MEAN ROOF HEIGHT OF
 15'-0" SHOWN ON ENGINEERED TRUSSES IS INCORRECT. REVISE
 AS REQUIRED.
  
 10- SHEET 1 OF 6:
 A) SPECIFY TOTAL ROOF DEAD LOAD. LINE WAS LEFT
 BLANK.
  
 B) THIS IS NOT A LEVEL 2 ALTERATION. THIS IS AN
 ADDITION PLUS ALTERATION OF EXISTING HOUSE. SEE
 EXISTING BUILDING 2004 CODEFOR CORRECT SECTIONS TO BE
 REFERENCED AND REVISE INFORMATION AS REQUIRED.
  
 11- SHEET 3 OF 6:
 A) SPECIFY BUCK NAIL SIZE ON TYP. WINDOW AND SLIDING
 GLASS DOOR DETAIL. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) CLARIFY COLUMN SIZE SPECIFIED AT BOTHENDS OF
 DOOR LEADING TO THEUTILITY ROOM.DIMENSIONS SHOWN
 AND TYPE OF COLUMNS SHOWN DON'T MATCH. REVISE AS
 REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) * SIZE OF FOOTING SPECIFIED IN FOUNDATION PLAN
 DOESN'T MATCHSIZE SHOWN ON TYPICAL FOOTING
 ATTACHMENT. REVISE AS REQUIRED.
 ** ALSO,CLARIFY NUMBER OF #5 BARS TO BE USED.
 FOUNDATION PLAN INFORMATION AND DETAIL INFORMATION NEED
 TO MATCH.
 *** TYPICAL FOOTING ATTACHMENT DETAILS SHOWS 6" MIN.
 EMBEDMENT FOR #5 REBARS, WHILE SPECS ON SAME DETAIL
 CALL FOR 8". REVISE AS REQUIRED.
  
 D) SECOND FLOOR FRAMING PLAN AND TRUSS LAYOUT DON'T
 MATCH. REVISE AS REQUIRED AND SPECIFY ALL STRUCTURAL
 CONNECTORS AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 E) SPECIFY DEPTH OF FLOOR TRUSSES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 12- SHEET 4 OF 6:
 A) STAIRWAY BEARING WALL IS SHOWN INCORRECTLY.
 REVISE AS REQUIRED.
  
 B) CLARIFY IF WINDOW ON EXISTING BATHROOM WILL BE
 BLOCKED OR NOT. PLANSHOWS UNBLOCKED WINDOW.
  
 13- SHEET 5 OF 6:
 A) ROOF FRAMING PLAN AT ENTRY PORCH DOESN'T MATCH
 TRUSS LAYOUT.REVISE AS REQUIRED AND SPECIFY CORRECT
 TRUSS CONNECTOR ACCORDING TO THE STRUCTURE ATTACHMENT,
 CONCRETE BEAM OR WOOD BEAM. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) CONNECTORS MTS 16 AND MTSM 16 DON'T PROVIDE
 LATERAL SUPPORT. CLARIFY WHERE ARE THE LATERAL LOADS
 FOR MTSM CONNECTOR TAKEN FROM.SPECIFY CONNECTORS THAT
 PROVIDE LATERAL SUPPORT OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS SHOWING HOW SPECIFIEDCONNECTORS WILL RESIST
 THE LATERAL LOADS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 C) SPECIFY HOW IS THE GUARDRAIL ATTACHED TO COMPLY
 WITH SEC. 1607.7.1 FBC 2004.
  
 D) REVISE RAILING HEIGHT SHOWN ON STEP RAILING
 DETAIL. SEE SEC R311.5.6 FBC 2004 AND STAIR SECTION
 DETAIL AND REVISE AS REQUIRED.
  
 E) INFORMATION ON STAIR TREAD DETAIL AND STAIR
 SECTION TO MATCH. REVISE NUMBER OF STRINGERS, AND RISER
 HEIGHT.
  
 F)THERE ARE TWO DIFFERENT SIZE OF FLOOR TRUSSES
 SPECIFIED ON STAIR SECTION DETAIL. REVISE AS REQUIRED.
  
 G) STAIR PLAN DOESN'T MATCH FLOOR PLAN. REVISE AS
 REQUIRED. SEE LOCATION OF INTERIOR BEARING WALL..
 REVISE AS REQUIRED.
  
 H) FLOOR SHEATHING SPECS SHOWN ON STAIR SECTION
 DON'T MATCH SPECS SHOWN ON TYPICAL WALL SECTION. REVISE
 AS REQUIRED.
  
 I) STAIR HANDRAIL DETAIL DOESN'T MATCH STAIR
 SECTION. REVISE AS REQUIRED.
  
 13- SHEET 6 OF 6:
 A) REVISE ROOF SHEATHINGNAIL TYPE AND SPACING
 SPECS, INCLUDING ROOF ZONE 3 IN ALL WALL SECTIONS.SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIALAND REVISE
 AS REQUIRED.
  
 B) REVISE FOOTING SIZE IN ALL WALL SECTIONS TO MATCH
 FOUNDATION PLAN.
  
 C) REVISE SECOND FLOOR SHEATHINGSPECS TO MATCH IN
 ALL WALL SECTIONS AND STAIR SECTION DETAIL.
  
 D) REVISE ALL TRUSS CONNECTORS.COORDINATE WITH
 ITEM 13(B) ABOVE.
  
 E) PROVIDE COMPLETE STUD SIZE ON SECOND FLOOR WALL
 FRAMING SPECS ON WALL SECTION B-B.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 F) INTERIOR BEARING WALL DETAIL: WALL IS SUPPORTING
 THE SECOND FLOOR TRUSSES, NOT THE ROOF JOIST. REVISE AS
 REQUIRED.
  
 G) SPECIFICATIONS ON ENTRY PORCH SECTIONS ARE NOT
 LEGIBLE. REVISE AS REQUIRED. SAME THING APPLIES TO WALL
 SECTION C-C.
  
 H) WALL SECTION C-C:
 * REVISE TO MATCH TRUSSSECOND FLOOR LAYOUTAND
 SPECIFY ALL CONNECTORS. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF SYSTEM. CLEARLY SPECIFY FASTENING
 OPTION TO BE USED FROM PAGE 28 OF NOA 03-0501.02
 SUBMITTED.
 AND, PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 B) SIMPSON OR USP STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. SUBMIT ONLY THEFLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE CONNECTOR TO SAVE
 PAPER.
  
 C) 8" PRECAST LINTELS. NOA SUBMITTED IS FOR 4", 6' &
 12" PRECAST LINTELS, NOT 8" PRECAST LINTELS.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712