Plan Review Notes
Plan Review Notes For Permit 07080141
Permit Number 07080141
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-04 19:34:25** DENIED**
  
 1) NOTE: PLEASE SEE THE INCORRECT ELECTRICAL CODE IS
 BEING REFLECTED ON PLANS.
 PLEASE KNOW ANY PERMIT APPLICATIONS APPLIED FOR AFTER
 DECEMBER 8TH, 2006 PLACES PROJECTS UNDER THE 2005 NEC/
 NFPA-70
  
 2) NOTE: PLEASE SUBMIT INFORMATION ON ANY EXTERIOR
 LIGHTING BEING REPAIRED OR REPLACED DU TO DAMAGE AS
 NOTED.
 PLANS MENTIONS THE NEC IS PART OF THE SCOPE ON PLANS
 HOWEVER NO INFORMATION WAS LOCATED.
 FBC 106.3.5.1.2.
  
 PLEASE KNOW THAT ANY NEW LIGHTING INSTALLED OUTSIDE
 WOULD BE REQUIRED TO COMPLY WITH FBC 13-415.2.ABC.1.3
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]