| Plan Review Notes For Permit 07080132 |
| Permit Number |
07080132 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-08-08 17:56:35 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | FROM PREVIOUS LIST, NOT ADDRESSED: | | | | | | _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED | | | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER | | | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE | | | LIMITATIONS.THE ASSEMBLY YOU SELECTED IS FOR | | | INSULATED DECK, YOU STATED THAT YOU ARE INSTALLING A | | | TORCH DOWN (NO INSULATION). | | | | | | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED | | | FASTENING FOR CORNER AND PERIMETER ZONES.YOU HAVE | | | SUBMITTED A LETTER BUT BE ADVISED THAT WE DISCUSSED 4" | | | SPACING AND YOU HAVE WRITTEN 12".COMPLIANCE WITH | | | RAS117 CANNOT BE DETERMINED UNTIL YOU SELECT AN | | | ASSEMBLY AND INDICATE WHICH FASTENER YOU ARE USING. | | | | | | _XX_ 7.)ADDRESSED BY DECLARING EXPOSURE C. | | | |
|