Notes
Date Text
2007-08-08 17:56:35****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST, NOT ADDRESSED:
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.THE ASSEMBLY YOU SELECTED IS FOR
 INSULATED DECK, YOU STATED THAT YOU ARE INSTALLING A
 TORCH DOWN (NO INSULATION).
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.YOU HAVE
 SUBMITTED A LETTER BUT BE ADVISED THAT WE DISCUSSED 4"
 SPACING AND YOU HAVE WRITTEN 12".COMPLIANCE WITH
 RAS117 CANNOT BE DETERMINED UNTIL YOU SELECT AN
 ASSEMBLY AND INDICATE WHICH FASTENER YOU ARE USING.
  
 _XX_ 7.)ADDRESSED BY DECLARING EXPOSURE C.
  