| | BUILDING PLAN REVIEW |
| | PERMIT: 07080113 |
| | ADD: 412 CLEMATIS ST. |
| | CONT: REDECOR, INC. |
| | TEL: (561)222-0223 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 3RD 11/1/07 |
| | ACTION: DENIED |
| | |
| | 1)OK |
| | 2) OK |
| | 4)OK |
| | |
| | 5)PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE NEW |
| | IMPACT STEEL DOORS AND THE PRE-CAST LINTEL. FBC |
| | 106.3.3. THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR APPROVAL. |
| | NOTE: THE PRODUCT APPROVALS SHALL BE APPROVED BY THE |
| | DESIGNER OF RECORD. |
| | **NOTED** |
| | HOWEVER, THE NOA REPORT IS MISSING FOR THE STEEL CRAFT |
| | DOOR. IN THE PACKAGE THERE ARE MANY DIFFERENT TYPES OF |
| | DOORS WITH THE NOA NUMBER. CHOOSE THE DOOR WHICH WILL |
| | BE INSTALLED AT THE PROJECT AND SUBMIT THE NOA REPORT. |
| | THE PRODUCT APPROVAL FOR THE ROLL-UP DOOR IS NOT |
| | INCLUDED IN THE PACKAGE. |
| | **NEEW** TWO COMPLETE SETS OF PRODUCT APPROVAL SHALL BE |
| | SUBMITTED FOR EACH PRODUCT. ONLY ONE SET FOR EACH |
| | PRODUCT WAS SUBMITTED. THE ROLL-UP EXTERIOR DOOR HAS A |
| | MAXIMUM DESIGN PRESSURE OF 30PSF WHICH IS BELOW THE |
| | DESIGN PRESSURES INDICATED ON SHEET S.1. SEE TABLE |
| | 1609.2.1(5) A 10X 10 GARAGE DOOR THE NEGATIVE PRESSURE |
| | IS -30.8. PROVIDE SIGNED, SEALED AND DATED CALCULATIONS |
| | SHOWING THAT THE ROLL-UP DOOR SUBMITTED WILL MEET THE |
| | PRESSURES INDICATED ON SHEET S.1 OR PROVIDE A DIFFERENT |
| | PRODUCT WHICH WILL MEET THE PRESSURES STATED ON THE |
| | PLANS, ( SHEET S.1). HI-LIGHT EACH ITEM ON THE PRODUCT |
| | APPROVAL FOR THE INSTALLATION OF THE PRODUCT. |
| | |
| | 6)OK |
| | 7)OK |
| | 8)OK |
| | 9)OK |
| | 10) OK |
| | |