Plan Review Notes
Plan Review Notes For Permit 07080113
Permit Number 07080113
Review Stop P
Sequence Number 2
Notes
Date Text
2007-09-28 11:51:19DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & O6 REVISIONS, PLUMBING.
 ** FBC-2004 WITH 05 & 06 REVISIONS, CHAPTER 13.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 **NOTE: PREVIOUS PLUMBING PLAN REVIEW COMMENTS WERE
 ADDRESSED. THE FOLOWING ARE NEW COMMENTS THAT NEED TO
 BE ADDRESSED TO MEET CODE COMPLIANCE:
  
 1. THE INSTA-HOT UNITS ON SHEET E-1, ARE BEING
 INDICATED IN A DIFFERENT LOCATION ON SHEET P-1. PLEASE
 CORRELATE THE TWO SHEETS AND PLEASE ADJUST THE WATER
 DIAGRAM ON SHEET P-1 PLUMBING FLOOR PLAN IF NEEDED.
  
 2. SHEET P-1 PLAN KEY NOTES #3, INDICATES "INSTA-HOT
 WATER HEATER, EEMAX MODEL ESP 3208, 208V, 1 PHASE, 3KW,
 14.4AMPS. THE PLANS INDICATE TWO OF THESE INSTA-HOT
 WATER HEATERS BEING INSTALLED. THE FOLLOWING SUBMITTED
 ENERGY CALCULATIONS.
 METHOD C: PRESCRIPTIVE COMPLIANCE FOR COMMERCIAL
 BUILDING PROJECT SUMMARY:
 COMPLIANCE SUMMARY: WATER HEATING SYSTEMS (NONE
 ENTERED)
 SYSTEM REPORT COMPLIANCE: WATER HEATER COMPLIANCE (NONE
 ENTERED)
 INPUT DATA REPORT: SYSTEMS, WATER HEATERS (NONE
 ENTERED)
 NOTE: PER FBC-2004 W/06 REVISIONS SECTION 13-103.1.1.1
 COMMERCIAL APPLICATIONS AND SECTION 13-412.1.ABC.1
 WATER HEATER SIZING AND DESIGN CALCULATIONS ARE
 REQUIRED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy