| Date |
Text |
| 2007-09-28 11:51:19 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & O6 REVISIONS, PLUMBING. |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, CHAPTER 13. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | **NOTE: PREVIOUS PLUMBING PLAN REVIEW COMMENTS WERE |
| | ADDRESSED. THE FOLOWING ARE NEW COMMENTS THAT NEED TO |
| | BE ADDRESSED TO MEET CODE COMPLIANCE: |
| | |
| | 1. THE INSTA-HOT UNITS ON SHEET E-1, ARE BEING |
| | INDICATED IN A DIFFERENT LOCATION ON SHEET P-1. PLEASE |
| | CORRELATE THE TWO SHEETS AND PLEASE ADJUST THE WATER |
| | DIAGRAM ON SHEET P-1 PLUMBING FLOOR PLAN IF NEEDED. |
| | |
| | 2. SHEET P-1 PLAN KEY NOTES #3, INDICATES "INSTA-HOT |
| | WATER HEATER, EEMAX MODEL ESP 3208, 208V, 1 PHASE, 3KW, |
| | 14.4AMPS. THE PLANS INDICATE TWO OF THESE INSTA-HOT |
| | WATER HEATERS BEING INSTALLED. THE FOLLOWING SUBMITTED |
| | ENERGY CALCULATIONS. |
| | METHOD C: PRESCRIPTIVE COMPLIANCE FOR COMMERCIAL |
| | BUILDING PROJECT SUMMARY: |
| | COMPLIANCE SUMMARY: WATER HEATING SYSTEMS (NONE |
| | ENTERED) |
| | SYSTEM REPORT COMPLIANCE: WATER HEATER COMPLIANCE (NONE |
| | ENTERED) |
| | INPUT DATA REPORT: SYSTEMS, WATER HEATERS (NONE |
| | ENTERED) |
| | NOTE: PER FBC-2004 W/06 REVISIONS SECTION 13-103.1.1.1 |
| | COMMERCIAL APPLICATIONS AND SECTION 13-412.1.ABC.1 |
| | WATER HEATER SIZING AND DESIGN CALCULATIONS ARE |
| | REQUIRED. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |