Plan Review Notes
Plan Review Notes For Permit 07080113
Permit Number 07080113
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-26 10:57:02 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING
 CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC
 AS
 AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 PROVIDE A WRITTEN RESPONSE TO THESE COMMENTS.
  
 THIS COMMENT WAS FROM THE 8/22/07 REVIEW AND WAS NOT
 ADDRESSED:
  
 2} PER 13-103.1.1, THE PERSON PREPARING THE COMPLIANCE
 CERTIFICATION MUST SIGN AND SEAL SAME. THERE IS NO
 SEAL.
  
 THESE ARE COMMENTS GENERATED BY THE CHANGES ON THE
 PLAN, SHEET E-1
  
 1} THE RELOCATED PANELS LPA AND LPB ON THE PLAN MUST
 COMPLY WITH ARTICLE 230.70(A)(1), NO MORE THAN 8? OF
 UNPROTECTED CONDUCTORS AS DETERMINED BY THE AHJ, AND
 THEREFORE MAY REQUIRE DISCONNECTS OUTSIDE. ARTICLE
 110.26 WITH REGARDS TO THE PLACEMENT OF THE LIGHTING
 CONTROL PANEL WITH RESPECT TO LPA & LPB.
  
 NOTE: SHEET E-2 SHOWS A GUTTER CONNECTING A PANEL TO
 THE LIGHTING CONTROL PANEL, AND HAS A NOTE INDICATING
 MAKE UP WORK IN LINE VOLTAGE GUTTER. THE INTENTION OF
 THAT NOTE IS UNCLEAR BUT BE AWARE OF ARTICLE 230.7
 ?CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE
 CABLE?. INDICATE THE LOCATION OF THE GUTTER ON THE
 PLAN.
  
 2} LPB 9,11,13 FOR THE RTU HAS AN OCP OF 80 AMPS. THE
 MAXIMUM FUSE SIZE ON SHEET M1 IS LISTED AS 70 AMPS FOR
 THAT UNIT. PLEASE CORRELATE
  
 3} THE INSTA HOT UNITS ON SHEET E-1, ARE IN A DIFFERENT
 LOCATION THAN SHEET P.1, PLEASE CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 MAY BE REVIEWED. THEY WERE ON THE PLANS THE PREVIOUS
 REVIEW.