| 2007-09-26 10:57:02 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING |
| | CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC |
| | AS |
| | AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | PROVIDE A WRITTEN RESPONSE TO THESE COMMENTS. |
| | |
| | THIS COMMENT WAS FROM THE 8/22/07 REVIEW AND WAS NOT |
| | ADDRESSED: |
| | |
| | 2} PER 13-103.1.1, THE PERSON PREPARING THE COMPLIANCE |
| | CERTIFICATION MUST SIGN AND SEAL SAME. THERE IS NO |
| | SEAL. |
| | |
| | THESE ARE COMMENTS GENERATED BY THE CHANGES ON THE |
| | PLAN, SHEET E-1 |
| | |
| | 1} THE RELOCATED PANELS LPA AND LPB ON THE PLAN MUST |
| | COMPLY WITH ARTICLE 230.70(A)(1), NO MORE THAN 8? OF |
| | UNPROTECTED CONDUCTORS AS DETERMINED BY THE AHJ, AND |
| | THEREFORE MAY REQUIRE DISCONNECTS OUTSIDE. ARTICLE |
| | 110.26 WITH REGARDS TO THE PLACEMENT OF THE LIGHTING |
| | CONTROL PANEL WITH RESPECT TO LPA & LPB. |
| | |
| | NOTE: SHEET E-2 SHOWS A GUTTER CONNECTING A PANEL TO |
| | THE LIGHTING CONTROL PANEL, AND HAS A NOTE INDICATING |
| | MAKE UP WORK IN LINE VOLTAGE GUTTER. THE INTENTION OF |
| | THAT NOTE IS UNCLEAR BUT BE AWARE OF ARTICLE 230.7 |
| | ?CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE |
| | INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE |
| | CABLE?. INDICATE THE LOCATION OF THE GUTTER ON THE |
| | PLAN. |
| | |
| | 2} LPB 9,11,13 FOR THE RTU HAS AN OCP OF 80 AMPS. THE |
| | MAXIMUM FUSE SIZE ON SHEET M1 IS LISTED AS 70 AMPS FOR |
| | THAT UNIT. PLEASE CORRELATE |
| | |
| | 3} THE INSTA HOT UNITS ON SHEET E-1, ARE IN A DIFFERENT |
| | LOCATION THAN SHEET P.1, PLEASE CORRELATE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | MAY BE REVIEWED. THEY WERE ON THE PLANS THE PREVIOUS |
| | REVIEW. |