| 2007-08-28 16:16:30 | *****DENIED***** | | | THIS MERCANTILE OCCUPANCY SHALL BE SUBCLASSIFIED AS | | | CLASS B (AGGREGATE GROSS AREA MORE THAN 3,000 SQUARE | | | BUT NOT MORE THAN 30,000 SQUARE FEET AND OCCUPYING NOT | | | MORE THAN THREE STORIES. | | | | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 4. THE TRAVEL DISTANCE TO AN EXIT SHALL BE MEASURED ON | | | THE FLOOR OR WALKING SURFACE AS PER NFPA 7.6.1, NOT AS | | | INDICATED ON SHEET A.3 | | | | | | 5.PROVIDE A FURNITURE PLAN WHICH SHALL PROVIDE THE | | | REVIEWER(S) WITH DETAILS SUCH AISLE CLEARANCE, TRAVEL | | | DISTANCE TO NEAREST EXIT, COMMON PATHS OF TRAVEL, | | | OBSTRUCTIONS TO EXITS, ETC. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|