Plan Review Notes For Permit 07080113
Permit Number 07080113
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-22 09:55:28THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PAGE #2 OF THE ENERGY GAUGE INPUT DATA REPORT,
 DOES NOT INDICATE THE CORRECT NUMBER OF FIXTURES AS
 SHOWN ON THE PLAN. CHAPTER 13.
  
 2} PER 13-103.1.1, THE PERSON PREPARING THE COMPLIANCE
 CERTIFICATION MUST SIGN AND SEAL SAME. THERE IS NO
 SEAL.
  
 3} 13-400.0.C.4 RENOVATED BUILDINGS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR
 COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE
 ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR
 THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED.
  
 NOTE: THE RELAY PANEL ON SHEET E-2 IS INDICATING AN
 OPERATING VOLTAGE OF 120/277, THE SERVICE VOLTAGE IS
 LISTED AT 120/208. SEE INSTA HOT MANUFACTURERS RATINGS
 PRIOR TO INSTALLATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718