| 2007-08-22 16:22:53 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT |
| | . ------------------------------------- |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | ) NUMBER OF BEDROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | |
| | 4)THE RECEPTION AND RETAIL AREA SHALL MEET THE |
| | REQUIREMENTS OF FBC 11-7. SHOW IN DETAIL HOW THESE |
| | REQUIREMENTS WILL BE MET. |
| | |
| | 5)PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THE NEW |
| | IMPACT STEEL DOORS AND THE PRE-CAST LINTEL. FBC 106.3.3 |
| | THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR APPROVAL. |
| | NOTE: THE PRODUCT APPROVALS SHALL BE APPROVED BY THE |
| | DESIGNER OF RECORD. |
| | |
| | 6)SHEET A.3 THE LIFE SAFETY PLAN SHOWS THE TRAVEL |
| | PATH GOING THROUGH A WALL. THERE SEEMS TO BE AN ERROR |
| | WITH THIS DESIGN. |
| | |
| | 7)THE LIFE SAFETY PLAN SHALL INCLUDE THE FURNITURE |
| | LAY-OUT IN THE OFFICE AND RETAIL AREA ALONG WITH THE |
| | COMMON PATH OF EGRESS TRAVEL. THE COMMON PATH OF EGRESS |
| | TRAVEL SHALL BE 75 FEET IN UNSPRINKLERED BUILDINGS AND |
| | 100 FEET IN BUILDINGS WITH AUTOMATIC SPRINKLER SYSTEM. |
| | SEE FBC 1013 FOR MORE INFORMATION. |
| | |
| | 8)FBC 1013.4.1THE MINIMUM CLEAR AISLE WIDTH SHALL |
| | NOT BE LESS THAN 36 INCHES. |
| | |
| | 9)FBC 1210 TOILET ROOM FLOORS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE. WALLS WITHIN 2 FEET OF |
| | URINALS AND WATER CLOSETS SHALL HAVE SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE |
| | FLOOR. NOTE: PAINT ON DRYWALL IS NOT CONSIDER A ?HARD? |
| | SURFACE. |
| | |
| | 10) SHOW ON THE PLANS WHERE THE DRYWALL CEILING WILL |
| | BE INSTALLED. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |