2007-08-29 12:29:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)COMPLETE THE INSTALLATION SCHEDULE.TWO SETS
 REQUIRED.ONLY ONE INCOMPLETE SCHEDULE SUBMITTED.
  
 2.)SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH ANCHOR SCHEDULE, IN THIS CASE A THROUGH L.EDGE
 DISTANCE WAS NOT SPECIFIED; PRIOR TO SUBMITTAL PLEASE
 MAKE NOTE OF THE BOX ON SHEET 14 WHICH REQUIRES A
 FACTOR FOR EDGE DISTANCE LESS THAN 3 1/2".
  
 3.)SPANS SHOULD BE BLADE LENGTH.THE SPANS YOU HAVE
 SPECIFIED ARE MUCH LARGER THAN OPENING SIZE AND
 ANCHORING IS NOT COMPLIANT FOR HIGHLIGHTED CONNECTION
 TYPES.YOU'VE HIGHLIGHTED 5', BUT 108" IS GREATER THAN
 5'.
  
 4.)POSITIVE DESIGN PRESSURES ARE TOO LOW.YOU ARE
 USING POSITIVE PRESSURES FROM PARTIALLY ENCLOSED
 CONDITION, BUT THIS BUILDING IS A FULLY ENCLOSED
 BUILDING.NEGATIVE PRESSURES FOR A PARTIALLY ENCLOSED
 BUILDING ARE MORE STRINGENT THAN ENCLOSED, SO USE OF
 NEGATIVE PRESSURES FOR PARTIALLY ENCLOSED CONDITIONS ON
 A FULLY ENCLOSED BUILDING IS ACCEPTABLE (EXCEEDS CODE
 COMPLIANCE).
  