| 2007-08-29 12:29:53 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | |
| | 1.)COMPLETE THE INSTALLATION SCHEDULE.TWO SETS |
| | REQUIRED.ONLY ONE INCOMPLETE SCHEDULE SUBMITTED. |
| | |
| | 2.)SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE |
| | WITH ANCHOR SCHEDULE, IN THIS CASE A THROUGH L.EDGE |
| | DISTANCE WAS NOT SPECIFIED; PRIOR TO SUBMITTAL PLEASE |
| | MAKE NOTE OF THE BOX ON SHEET 14 WHICH REQUIRES A |
| | FACTOR FOR EDGE DISTANCE LESS THAN 3 1/2". |
| | |
| | 3.)SPANS SHOULD BE BLADE LENGTH.THE SPANS YOU HAVE |
| | SPECIFIED ARE MUCH LARGER THAN OPENING SIZE AND |
| | ANCHORING IS NOT COMPLIANT FOR HIGHLIGHTED CONNECTION |
| | TYPES.YOU'VE HIGHLIGHTED 5', BUT 108" IS GREATER THAN |
| | 5'. |
| | |
| | 4.)POSITIVE DESIGN PRESSURES ARE TOO LOW.YOU ARE |
| | USING POSITIVE PRESSURES FROM PARTIALLY ENCLOSED |
| | CONDITION, BUT THIS BUILDING IS A FULLY ENCLOSED |
| | BUILDING.NEGATIVE PRESSURES FOR A PARTIALLY ENCLOSED |
| | BUILDING ARE MORE STRINGENT THAN ENCLOSED, SO USE OF |
| | NEGATIVE PRESSURES FOR PARTIALLY ENCLOSED CONDITIONS ON |
| | A FULLY ENCLOSED BUILDING IS ACCEPTABLE (EXCEEDS CODE |
| | COMPLIANCE). |
| | |