2007-09-12 12:08:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)SEE SHEET 5 OF THE PRODUCT APPROVAL.A .86 FACTOR
 FOR 3" EDGE DISTANCE REQUIRED.
  
 2ND REVIEW - THIS MEANS THAT YOU NEED TO APPLY THE
 FACTOR OF .86 TO THE ANCHOR SPACING ON THE TABLE.YOU
 CANNOT USE THE ANCHOR SPACING ON THE TABLE WITH A 3"
 EDGE DISTANCE (ONLY 3 1/2").
  
  