| Date |
Text |
| 2008-12-23 08:53:31 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEWS: |
| | |
| | 1. SHT P-03 GAS RISER DIAGRAM DOES NOT REFLECT THE |
| | PIPING SHOWN ON THE SITE PLAN. THE PIPING ON THE SITE |
| | PLAN IS INDICATED AS OFFSETTING TO THE NORTH EAST, |
| | TURNING TO THE SOUTH EAST, AND THEN TURNING TO THE |
| | NORTH EAST TO THE POOL BUILDING. -- ALSO THE PIPING |
| | SCALES OUT TO ABOUT 200 FEET FROM THE METER WITH 40 |
| | FEET INSIDE THE BUILDING FOR A TOTAL DEVELOPED LENGTH |
| | OF ABOUT 240 FEET. PLANS AND RISER DIAGRAM INDICATE 160 |
| | FEET TO THE BUILDING AND A TOTAL DEVELOPED LENGTH OF |
| | 200 FEET. PLEASE CORRELATE AND CLARIFY. TABLE 402.4(3). |
| | ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED EXCEPT |
| | FOR THE DEVELOPED LENGTH. |
| | |
| | 2. THE PLANS INDICATE THAT THE PIPING WILL ALL BE |
| | SCHEDULE 40 BLACK IRON PIPE. PER SECTIONS 404.8 & |
| | 404.8.2 PIPES SHALL BE PROTECTED AND THE PROTECTIVE |
| | COATINGS AND WRAPPING SHALL BE FACTORY INSTALLED. |
| | ****RESPONSE NOTED, BUT PLANS SHALL INDICATE THE |
| | REQUIRED PROTECTION FOR THE SCHEDULE 40 BLACK IRON PIPE |
| | AND THE REQUIRED PROTECTION REQUIRED FOR THE WARDFLEX |
| | PIPING AS WELL AS THE EDH NUMBER OF THE WARDFLEX |
| | PIPING. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | THE FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 4. INFORMATIONAL: 3/4" PIPE WILL BE SUFFICIENT ON THE |
| | 2PSI SYSTEM UP TO 500 FT FOR THE SCHEDULE 40 PIPE, AND |
| | UP TO 600 FT FOR PE PIPE UNDERGROUND. TABLES 402.4.3 & |
| | 402.4(20). |
| | |
| | 5. TO EXPEDITE THE PERMIT, A SUGGESTION WOULD BE TO |
| | REMOVE THE GAS PLANS FROM THIS SET OF PLANS FOR THE |
| | POOL BUILDING AND REFERENCE THE BLD-COM PERMIT FOR THE |
| | 6 STORY BUILDING AS THERE ARE GAS PLANS FOR THE POOL |
| | HEATER ON THOSE PLANS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |