Plan Review Notes
Plan Review Notes For Permit 07080080
Permit Number 07080080
Review Stop G
Sequence Number 3
Notes
Date Text
2008-12-23 08:53:31DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEWS:
  
 1. SHT P-03 GAS RISER DIAGRAM DOES NOT REFLECT THE
 PIPING SHOWN ON THE SITE PLAN. THE PIPING ON THE SITE
 PLAN IS INDICATED AS OFFSETTING TO THE NORTH EAST,
 TURNING TO THE SOUTH EAST, AND THEN TURNING TO THE
 NORTH EAST TO THE POOL BUILDING. -- ALSO THE PIPING
 SCALES OUT TO ABOUT 200 FEET FROM THE METER WITH 40
 FEET INSIDE THE BUILDING FOR A TOTAL DEVELOPED LENGTH
 OF ABOUT 240 FEET. PLANS AND RISER DIAGRAM INDICATE 160
 FEET TO THE BUILDING AND A TOTAL DEVELOPED LENGTH OF
 200 FEET. PLEASE CORRELATE AND CLARIFY. TABLE 402.4(3).
 ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED EXCEPT
 FOR THE DEVELOPED LENGTH.
  
 2. THE PLANS INDICATE THAT THE PIPING WILL ALL BE
 SCHEDULE 40 BLACK IRON PIPE. PER SECTIONS 404.8 &
 404.8.2 PIPES SHALL BE PROTECTED AND THE PROTECTIVE
 COATINGS AND WRAPPING SHALL BE FACTORY INSTALLED.
 ****RESPONSE NOTED, BUT PLANS SHALL INDICATE THE
 REQUIRED PROTECTION FOR THE SCHEDULE 40 BLACK IRON PIPE
 AND THE REQUIRED PROTECTION REQUIRED FOR THE WARDFLEX
 PIPING AS WELL AS THE EDH NUMBER OF THE WARDFLEX
 PIPING.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 THE FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. INFORMATIONAL: 3/4" PIPE WILL BE SUFFICIENT ON THE
 2PSI SYSTEM UP TO 500 FT FOR THE SCHEDULE 40 PIPE, AND
 UP TO 600 FT FOR PE PIPE UNDERGROUND. TABLES 402.4.3 &
 402.4(20).
  
 5. TO EXPEDITE THE PERMIT, A SUGGESTION WOULD BE TO
 REMOVE THE GAS PLANS FROM THIS SET OF PLANS FOR THE
 POOL BUILDING AND REFERENCE THE BLD-COM PERMIT FOR THE
 6 STORY BUILDING AS THERE ARE GAS PLANS FOR THE POOL
 HEATER ON THOSE PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved