Plan Review Notes
Plan Review Notes For Permit 07080080
Permit Number 07080080
Review Stop B
Sequence Number 3
Notes
Date Text
2008-04-24 14:31:34BUILDING PLAN REVIEW #3
 PERMIT: 07080080
 ADD: 301 LAMBERTON DR.
 CONT: THE WEITZ CO.
 TEL: (561)719-0102
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD4-16-08
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 **NOTED**
 2) THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **3RDREVIEW.**
 3)1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6. THIS IS A QUESTIONABLE
 SOIL AREA SO PLEASE PROVIDE THE SOIL REPORT.
  
 4) OK
 5)OK
 6)OK
 7)OK
 8)OK
 9)OK
 10)OK
 11)OK
  
 3RDREVIEW
 12)THE ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOWING ITEMS.
 ____1)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
 ____ 2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
 _XX_ 3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE
 OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
 _XX_4)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
 _XX_5)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
 XX6) THE SYSTEM PROVIDED INDICATES LIMITATION #9, NO
 ENHANCED FASTENING IS ALLOWED.
  
 13)OK
  
 3RDREVIEW
 14)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15)OK
 16)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 (561) 805-6676
 [email protected]
  