Plan Review Notes
Plan Review Notes For Permit 07080080
Permit Number 07080080
Review Stop P
Sequence Number 2
Notes
Date Text
2008-02-23 08:53:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHTS 1 & 2 OF 2. NO INFORMATION CAN BE GLEANED FROM
 THE SEAL OF EITHER SHEET. FAC 61G15-23.001,
 61G15-23.002 & FS 471.025.PLEASE RESEAL THE PLANS SO
 THAT THE INFORMATION REQUIRED ON THE SEAL IS LEGIBLE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. SHTS T1.1, ALL ARCHITECTURAL & STRUCTURAL. THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), FOR CDS
 ARCHITECTURAL DESIGN IS REQUIRED IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 PLEASE INDICATE THE FIRM LICENSE NUMBER IN THE TITLE
 BLOCKS.
 ****RESPONSE NOTED, BUT THE CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK FOR CSD
 ARCHITECTURAL DESIGN AND ALSO FOR BOMFA ARCHITECTURAL
 INC. PLEASE COMPLY WITH THE FLORIDA ADMINISTRATIVE CODE
 AND FLORIDA STATUTES.
  
 3. OK
  
 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S
 A. OK
 B. OK
 ___FOR URINALS
 A. OK
 B. OK
 C. OK
 ___FOR LAVS
 A. 11-4.19.2 CLEARANCES
 ****RESPONSE NOTED, BUT THE CLEARANCE OF 29" IS NOT
 INDICATED. ALSO THE MEASUREMENT OF 2'8" IS NOT TO THE
 FLOOD RIM LEVEL OF THE SINK. PLEASE INDICATE THE HEIGHT
 OF THE SINK PER SECTION 11-4.19.2.
 B. OK
 C. OK
 D. OK
  
 5. SHT P-02 SUBMIT THE RISER DIAGRAMS, (SANITARY &
 WATER), IN ISOMETRIC FORM THAT REFLECT THE PIPING SHOWN
 ON THE FLOOR PLAN. SECTION
 106.3.5.1.3(3)(4)(6)(8)(10)(13). FOR THE SANITARY SHOW
 ALL PIPE SIZES, VENTS & TRAPS. FOR THE WATER SHOW ALL
 PIPE SIZES, VALVES & WATER HAMMER ARRESTORS.
 ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN WHERE THE SECOND WATER
 CLOSET CONNECTS TO THE BRANCH LINE. IT IS SHOWN
 CONNECTING BETWEEN THE FIRST FLOOR DRAIN AND THE URINAL
 ON THE FLOOR PLAN, BUT UPSTREAM OF THE URINAL ON THE
 RISER DIAGRAM. PLEASE CORRELATE.
  
 6. OK
 7. OK
 8. OK
  
 9. ALL PLUMBING SHEETS. THE ADDRESS OF RECORD ON THE
 FLORIDA STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS
 SHOWN ON THE ENGINEERS TITLE BLOCK. FAC
 61G15-23.002(2). PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCKS SO THAT THEY CORRELATE PRIOR TO
 RESUBMITTING FOR REVIEW. FS 471.025.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. THE FOLLOWING INFORMATION REQUIRED FOR THE SEPARATE
 GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT RESPONSE WAS FOR A DIFFERENT
 PERMIT, (05041760). ACCORDING TO THIS PLAN, THE GAS
 SYSTEM IS A SEPARATE SYSTEM WITH A SEPARATE METER. NO
 CORRESPONDING LENGHTS ARE INDICATED FOR THE PIPING FROM
 THE METER TO THE FIRST DROP IN THE SYSTEM, NOR IS THERE
 A CORRESPONDING LENGHT GIVEN FOR THE FIRST DROP AS WELL
 AS THE PIPING FROM THE POOL HEATER TO THE DROP TO THE
 POOL HEATER.
  
 B. OK
  
 C. TYPE OF GAS, (LP OR NATURAL).
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. OK
 E. N/A
 F. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT RESPONSE WAS FOR A DIFFERENT
 PERMIT, (05041760). NO MANUF. SHEETS SUBMITTED.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 ****NO RESPONSE, NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  