| 2008-02-23 08:53:04 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHTS 1 & 2 OF 2. NO INFORMATION CAN BE GLEANED FROM |
| | THE SEAL OF EITHER SHEET. FAC 61G15-23.001, |
| | 61G15-23.002 & FS 471.025.PLEASE RESEAL THE PLANS SO |
| | THAT THE INFORMATION REQUIRED ON THE SEAL IS LEGIBLE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 2. SHTS T1.1, ALL ARCHITECTURAL & STRUCTURAL. THE FIRM |
| | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), FOR CDS |
| | ARCHITECTURAL DESIGN IS REQUIRED IN THE TITLE BLOCK OF |
| | EACH SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055. |
| | PLEASE INDICATE THE FIRM LICENSE NUMBER IN THE TITLE |
| | BLOCKS. |
| | ****RESPONSE NOTED, BUT THE CERTIFICATE OF |
| | AUTHORIZATION IS REQUIRED IN THE TITLE BLOCK FOR CSD |
| | ARCHITECTURAL DESIGN AND ALSO FOR BOMFA ARCHITECTURAL |
| | INC. PLEASE COMPLY WITH THE FLORIDA ADMINISTRATIVE CODE |
| | AND FLORIDA STATUTES. |
| | |
| | 3. OK |
| | |
| | 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | ___FOR W/C'S |
| | A. OK |
| | B. OK |
| | ___FOR URINALS |
| | A. OK |
| | B. OK |
| | C. OK |
| | ___FOR LAVS |
| | A. 11-4.19.2 CLEARANCES |
| | ****RESPONSE NOTED, BUT THE CLEARANCE OF 29" IS NOT |
| | INDICATED. ALSO THE MEASUREMENT OF 2'8" IS NOT TO THE |
| | FLOOD RIM LEVEL OF THE SINK. PLEASE INDICATE THE HEIGHT |
| | OF THE SINK PER SECTION 11-4.19.2. |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | 5. SHT P-02 SUBMIT THE RISER DIAGRAMS, (SANITARY & |
| | WATER), IN ISOMETRIC FORM THAT REFLECT THE PIPING SHOWN |
| | ON THE FLOOR PLAN. SECTION |
| | 106.3.5.1.3(3)(4)(6)(8)(10)(13). FOR THE SANITARY SHOW |
| | ALL PIPE SIZES, VENTS & TRAPS. FOR THE WATER SHOW ALL |
| | PIPE SIZES, VALVES & WATER HAMMER ARRESTORS. |
| | ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN WHERE THE SECOND WATER |
| | CLOSET CONNECTS TO THE BRANCH LINE. IT IS SHOWN |
| | CONNECTING BETWEEN THE FIRST FLOOR DRAIN AND THE URINAL |
| | ON THE FLOOR PLAN, BUT UPSTREAM OF THE URINAL ON THE |
| | RISER DIAGRAM. PLEASE CORRELATE. |
| | |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. ALL PLUMBING SHEETS. THE ADDRESS OF RECORD ON THE |
| | FLORIDA STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS |
| | SHOWN ON THE ENGINEERS TITLE BLOCK. FAC |
| | 61G15-23.002(2). PLEASE UPDATE THE DBPR WEBSITE OR THE |
| | TITLE BLOCKS SO THAT THEY CORRELATE PRIOR TO |
| | RESUBMITTING FOR REVIEW. FS 471.025. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 10. THE FOLLOWING INFORMATION REQUIRED FOR THE SEPARATE |
| | GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT RESPONSE WAS FOR A DIFFERENT |
| | PERMIT, (05041760). ACCORDING TO THIS PLAN, THE GAS |
| | SYSTEM IS A SEPARATE SYSTEM WITH A SEPARATE METER. NO |
| | CORRESPONDING LENGHTS ARE INDICATED FOR THE PIPING FROM |
| | THE METER TO THE FIRST DROP IN THE SYSTEM, NOR IS THERE |
| | A CORRESPONDING LENGHT GIVEN FOR THE FIRST DROP AS WELL |
| | AS THE PIPING FROM THE POOL HEATER TO THE DROP TO THE |
| | POOL HEATER. |
| | |
| | B. OK |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | D. OK |
| | E. N/A |
| | F. OK |
| | G. OK |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT RESPONSE WAS FOR A DIFFERENT |
| | PERMIT, (05041760). NO MANUF. SHEETS SUBMITTED. |
| | |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |