| Plan Review Notes For Permit 07080080 |
| Permit Number |
07080080 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-02-21 12:27:35 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE REVIEWED: | | | | | | 1.OK | | | | | | 2.OK | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | | COMMENT TO AN APPROPIATE PLAN SHEET | | | | | | 4.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR | | | HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY | | | OR VICINITY THEREOF (INCLUDING STREETS, FIRE LANES). | | | ADD COMMENT TO AN APPROPIATE PLAN SHEET | | | | | | 5.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C.COULD NOT | | | LOCATE COMMENT ON SHEET A1.1 AS PER YOUR RESPONSE | | | LETTER | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|