| Date |
Text |
| 2007-09-20 15:46:58 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. SHTS 1 & 2 OF 2. NO INFORMATION CAN BE GLEANED FROM |
| | THE SEAL OF EITHER SHEET. FAC 61G15-23.001, |
| | 61G15-23.002 & FS 471.025.PLEASE RESEAL THE PLANS SO |
| | THAT THE INFORMATION REQUIRED ON THE SEAL IS LEGIBLE. |
| | |
| | 2. SHTS T1.1, ALL ARCHITECTURAL & STRUCTURAL. THE FIRM |
| | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), FOR CDS |
| | ARCHITECTURAL DESIGN IS REQUIRED IN THE TITLE BLOCK OF |
| | EACH SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055. |
| | PLEASE INDICATE THE FIRM LICENSE NUMBER IN THE TITLE |
| | BLOCKS. |
| | |
| | 3. SHT A1.1 MENS TOILET ROOM. IF TOILET STALLS ARE |
| | PROVIDED, THEN AT LEAST ONE SHALL BE A STANDARD TOILET |
| | STALL COMPLYING WITH SECTION 11-4.17.3EXCEPTION NEW |
| | CONSTRUCTION(1)(2). A LAV IS REQUIRED IN THE STALL. |
| | (SEE FIG. 11-30E). PLEASE SHOW THE REQUIRED LAV IN THE |
| | STALL. |
| | |
| | 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR |
| | W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | ___FOR URINALS |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | ___FOR LAVS |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | |
| | 5. SHT P-02 SUBMIT THE RISER DIAGRAMS, (SANITARY & |
| | WATER), IN ISOMETRIC FORM THAT REFLECT THE PIPING SHOWN |
| | ON THE FLOOR PLAN. SECTION |
| | 106.3.5.1.3(3)(4)(6)(8)(10)(13). FOR THE SANITARY SHOW |
| | ALL PIPE SIZES, VENTS & TRAPS. FOR THE WATER SHOW ALL |
| | PIPE SIZES, VALVES & WATER HAMMER ARRESTORS. |
| | |
| | 6. SHT P-02 THE EXTERIOR SHOWER DRAIN IS NOT APPROVED. |
| | PLEASE DELETE FROM RISER AND FLOOR PLAN. ARTICLE III |
| | SECTION 90-125(5). |
| | |
| | 7. SHT P-02 ELECTRIC WATER HEATER DETAIL. THE EMERGENCY |
| | PAN DRAIN SHALL EXTEND FULL SIZE AND TERMINATE OVER A |
| | SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR DRAIN |
| | OR EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE |
| | NOT LESS THAN 6" AND NOT MORE THAN 24" ABOVE THE |
| | ADJACENT GROUND SURFACE. SECTION 504.7.2. THE DETAIL |
| | SHOWS THE PAN DRAIN SPILLING OVER THE FLOOR. PLEASE |
| | CORRECT THE TERMINATION POINT TO COMPLY. |
| | |
| | 8. SHT P-02 AN RPZV BACKFLOW IS REQUIRED ON THE WATER |
| | SERVICE TO THE BUILDING. SECTION 608.13.2. PLEASE SHOW |
| | THE BACKFLOW ON THE WATER SERVICE.NOTE: THE POOL |
| | PLANS SHOW A HOSE BIBB WITH A VACUUM BREAKER AS WELL AS |
| | AN AIR GAP FOR THE MAKE-UP WATER AT THE COLLECTOR TANK. |
| | THE RPZV BACKFLOW SHOWN FOR THE MAKE-UP WATER WILL NOT |
| | BE NECESSARY AND CAN BE DELETED. |
| | |
| | 9. ALL PLUMBING SHEETS. THE ADDRESS OF RECORD ON THE |
| | FLORIDA STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS |
| | SHOWN ON THE ENGINEERS TITLE BLOCK. FAC |
| | 61G15-23.002(2). PLEASE UPDATE THE DBPR WEBSITE OR THE |
| | TITLE BLOCKS SO THAT THEY CORRELATE PRIOR TO |
| | RESUBMITTING FOR REVIEW. FS 471.025. |
| | |
| | 10. THE FOLLOWING INFORMATION REQUIRED FOR THE SEPARATE |
| | GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | NOTE: SHT P-03 INDICATES 7" WC FOR SUPPLY PRESSURE. IF |
| | NATURAL GAS FLORIDA PUBLIC |
| | UTILITIES ONLY SUPPLIES 12" TO 14" WC OR |
| | 2PSI. PLEASE CLAIRFY WITH GAS PROVIDER |
| | PRIOR TO RESUBMITTING FOR CORRECT |
| | DELIVERY PRESSURE. |
| | |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |