Plan Review Notes
Plan Review Notes For Permit 07080080
Permit Number 07080080
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-20 15:46:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. SHTS 1 & 2 OF 2. NO INFORMATION CAN BE GLEANED FROM
 THE SEAL OF EITHER SHEET. FAC 61G15-23.001,
 61G15-23.002 & FS 471.025.PLEASE RESEAL THE PLANS SO
 THAT THE INFORMATION REQUIRED ON THE SEAL IS LEGIBLE.
  
 2. SHTS T1.1, ALL ARCHITECTURAL & STRUCTURAL. THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), FOR CDS
 ARCHITECTURAL DESIGN IS REQUIRED IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 PLEASE INDICATE THE FIRM LICENSE NUMBER IN THE TITLE
 BLOCKS.
  
 3. SHT A1.1 MENS TOILET ROOM. IF TOILET STALLS ARE
 PROVIDED, THEN AT LEAST ONE SHALL BE A STANDARD TOILET
 STALL COMPLYING WITH SECTION 11-4.17.3EXCEPTION NEW
 CONSTRUCTION(1)(2). A LAV IS REQUIRED IN THE STALL.
 (SEE FIG. 11-30E). PLEASE SHOW THE REQUIRED LAV IN THE
 STALL.
  
 4. SHT A3.4 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR
 W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR URINALS
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ___FOR LAVS
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 5. SHT P-02 SUBMIT THE RISER DIAGRAMS, (SANITARY &
 WATER), IN ISOMETRIC FORM THAT REFLECT THE PIPING SHOWN
 ON THE FLOOR PLAN. SECTION
 106.3.5.1.3(3)(4)(6)(8)(10)(13). FOR THE SANITARY SHOW
 ALL PIPE SIZES, VENTS & TRAPS. FOR THE WATER SHOW ALL
 PIPE SIZES, VALVES & WATER HAMMER ARRESTORS.
  
 6. SHT P-02 THE EXTERIOR SHOWER DRAIN IS NOT APPROVED.
 PLEASE DELETE FROM RISER AND FLOOR PLAN. ARTICLE III
 SECTION 90-125(5).
  
 7. SHT P-02 ELECTRIC WATER HEATER DETAIL. THE EMERGENCY
 PAN DRAIN SHALL EXTEND FULL SIZE AND TERMINATE OVER A
 SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR FLOOR DRAIN
 OR EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE
 NOT LESS THAN 6" AND NOT MORE THAN 24" ABOVE THE
 ADJACENT GROUND SURFACE. SECTION 504.7.2. THE DETAIL
 SHOWS THE PAN DRAIN SPILLING OVER THE FLOOR. PLEASE
 CORRECT THE TERMINATION POINT TO COMPLY.
  
 8. SHT P-02 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING. SECTION 608.13.2. PLEASE SHOW
 THE BACKFLOW ON THE WATER SERVICE.NOTE: THE POOL
 PLANS SHOW A HOSE BIBB WITH A VACUUM BREAKER AS WELL AS
 AN AIR GAP FOR THE MAKE-UP WATER AT THE COLLECTOR TANK.
 THE RPZV BACKFLOW SHOWN FOR THE MAKE-UP WATER WILL NOT
 BE NECESSARY AND CAN BE DELETED.
  
 9. ALL PLUMBING SHEETS. THE ADDRESS OF RECORD ON THE
 FLORIDA STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS
 SHOWN ON THE ENGINEERS TITLE BLOCK. FAC
 61G15-23.002(2). PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCKS SO THAT THEY CORRELATE PRIOR TO
 RESUBMITTING FOR REVIEW. FS 471.025.
  
 10. THE FOLLOWING INFORMATION REQUIRED FOR THE SEPARATE
 GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: SHT P-03 INDICATES 7" WC FOR SUPPLY PRESSURE. IF
 NATURAL GAS FLORIDA PUBLIC
 UTILITIES ONLY SUPPLIES 12" TO 14" WC OR
 2PSI. PLEASE CLAIRFY WITH GAS PROVIDER
 PRIOR TO RESUBMITTING FOR CORRECT
 DELIVERY PRESSURE.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]