2007-09-09 13:24:16REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO MECHANICAL PLANS WERE SUBMITTED WITH THIS
 PACKAGE. THE FOLLOWING INFORMATION AT A MINIMUM IS
 REQUIRED TO SHOW CODE COMPLIANCE:
 - MEANS AND RATE OF VENTILATION REQUIRED AND PROVIDED
 FOR TOILET ROOMS AND POOL EQUIPMENT ROOM. FBC,M 401.2
 AND 401.3
 - LOCATION OF ALL VENT OUTLETS FOR PLUMBING AND GAS,
 EXHAUST OUTLETS AND INTAKE OPENINGS. FBC,M 401.5
 - MEANS AND METHOD (INCLUDING CALCULATIONS) USED TO
 PROVIDE BOTH COMBUSTION AIR AND VENTILATION
 REQUIREMENTS ARE MET FOR THE GAS POOL HEATER/ POOL
 EQUIPMENT ROOM. FBC,FG 304.9 AND 304.10
 - PROTECTION FROM FUMES AND GASSES PER FBC,FG 304.12
  
 2. EXTERIOR WALL LOUVERS ARE LISTED AS PANEL WALLS
 UNDER FAC RULE 9B-72 AND AS SUCH ARE SUBJECT TO THE
 FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT
 APPROVALS FOR ALL LOUVERS AND THE "INTERCRIMP SCREENS
 BY TWP, INC." ALL OPENINGS INTO THE BUILDING SHALL ALSO
 MEET THE REQUIREMENTS OF FBC,M 401.6 (PROTECTION
 AGAINST LOCAL WEATHER CONDITIONS). FOR ADDITIONAL
 INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM
 PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 3. SHOW ON PLANS THE CORRECT ADDRESS OF THE PROPOSED
 WORK TO MATCH THAT SHOWN ON THE PERMIT APPLICATION. FAC
 61G1-16.004
  