| 2007-09-09 13:24:16 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. NO MECHANICAL PLANS WERE SUBMITTED WITH THIS |
| | PACKAGE. THE FOLLOWING INFORMATION AT A MINIMUM IS |
| | REQUIRED TO SHOW CODE COMPLIANCE: |
| | - MEANS AND RATE OF VENTILATION REQUIRED AND PROVIDED |
| | FOR TOILET ROOMS AND POOL EQUIPMENT ROOM. FBC,M 401.2 |
| | AND 401.3 |
| | - LOCATION OF ALL VENT OUTLETS FOR PLUMBING AND GAS, |
| | EXHAUST OUTLETS AND INTAKE OPENINGS. FBC,M 401.5 |
| | - MEANS AND METHOD (INCLUDING CALCULATIONS) USED TO |
| | PROVIDE BOTH COMBUSTION AIR AND VENTILATION |
| | REQUIREMENTS ARE MET FOR THE GAS POOL HEATER/ POOL |
| | EQUIPMENT ROOM. FBC,FG 304.9 AND 304.10 |
| | - PROTECTION FROM FUMES AND GASSES PER FBC,FG 304.12 |
| | |
| | 2. EXTERIOR WALL LOUVERS ARE LISTED AS PANEL WALLS |
| | UNDER FAC RULE 9B-72 AND AS SUCH ARE SUBJECT TO THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT |
| | APPROVALS FOR ALL LOUVERS AND THE "INTERCRIMP SCREENS |
| | BY TWP, INC." ALL OPENINGS INTO THE BUILDING SHALL ALSO |
| | MEET THE REQUIREMENTS OF FBC,M 401.6 (PROTECTION |
| | AGAINST LOCAL WEATHER CONDITIONS). FOR ADDITIONAL |
| | INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM |
| | PLEASE VISIT: WWW.FLORIDABUILDING.ORG |
| | |
| | 3. SHOW ON PLANS THE CORRECT ADDRESS OF THE PROPOSED |
| | WORK TO MATCH THAT SHOWN ON THE PERMIT APPLICATION. FAC |
| | 61G1-16.004 |
| | |