Plan Review Notes
Plan Review Notes For Permit 07080080
Permit Number 07080080
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-04 15:47:27 
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE THE ADDRESS WHICH HAS NOW BEEN
 ASSIGNED BY THE CITY OF WEST PALM BEACH AND AS APPLIED
 IS 301 LAMBERTON.
 PLEASE ADJUST TITLE BLOCKS FOR LOCATION.
 FAC 61G1-16.004, FAC 61G15-23.002
  
  
 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 3) NOTE: PLEASE KNOW AS THE PRIMARY BUILDING DOES NOT
 YET HAVE A CERTIFICATE OF OCCUPANCY AND THE DESIGNER OF
 RECORD FOR THE ARCHITECTURAL SHEETS IS NOW NEW, PLEASE
 BE SURE THESE PLANS WHICH DIRECTLY AFFECT THE PROJECT
 CONTAIN A *SHOP DRAWING* REVIEW STAMP.
 PLEASE KNOW THAT ANY CHANGES MADE DUE TO LOADS, ENERGY
 CALCULATIONS FOR OUTSIDE LIGHTING ETC WHICH IS FED FROM
 THE BASE BUILDING WILL REQUIRE PLANS FOR THE BASE
 BUILDING ALONG WITH ANY CALCULATIONS TO BE REVISED.
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL
 SHEETS ARE MISSING THE REQUIRED INFORMATION FOR ONE OF
 THE DESIGN FIRMS AS LISTED PER FLORIDA ADMINISTRATIVE
 CODE 61G1-16.004 AND FLORIDA STATUTES 481.219.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHICH CONTAINS THIS INFORMATION ON TITLE BLOCKS. THIS
 COMMENT IS NOT FOR THE ELECTRICAL SHEETS.
  
 5) NOTE: PLEASE SEE THE ELECTRICAL PLANS AS SUBMITTED
 NEED TO MEET FBC 13-415.2
 PLEASE PROVIDE LIGHTING DENSITY INFORMATION.
  
 6) NOTE: PLEASE SEE TWO ELECTRICAL RISERS AND PANEL
 SCHEDULES WERE SUBMITTED.
 IT IS UNCLEAR WHICH ONE IS TO BE REVIEWED FOR CODE
 COMPLIANCE.
 ONE RISER INDICATES A REQUESTED FOR A SEPARATE
 ELECTRICAL SERVICE FROM THE POWER COMPANY ONLY TO THIS
 BUILDING. THIS CONFLICTS WITH THE OTHER RISER WHICH
 INDICATES THE ELECTRICAL BEING FED FROM THE EXISTING
 BASED BUILDING SERVICE.
 PLEASE KNOW THAT GRANTING AN ADDITIONAL SERVICE FOR THE
 POOL HOUSE AS SHOWN IS NOT PERMITTED AS THERE WOULD BE
 ELECTRICAL SYSTEMS BEING CROSSED FROM TWO SEPARATE
 SERVICES.
 FBC 106.1.2, 106.3.5.1.2
 NEC 215.5,230.70, 230.71, 230.2, 310.16, 240.4 ETC.
 PLEASE COORDINATE.
  
 7) NOTE: PLEASE SEE 422.13 IN THE 2005 NEC AS LOADS FOR
 ELECTRICAL WATER HEATERS ARE TO BE FIGURED AT 125% AS
 THESE ARE CONSIDERED CONTINUOUS LOADS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]