| 2007-09-04 15:47:27 | |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE THE ADDRESS WHICH HAS NOW BEEN |
| | ASSIGNED BY THE CITY OF WEST PALM BEACH AND AS APPLIED |
| | IS 301 LAMBERTON. |
| | PLEASE ADJUST TITLE BLOCKS FOR LOCATION. |
| | FAC 61G1-16.004, FAC 61G15-23.002 |
| | |
| | |
| | 2) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 3) NOTE: PLEASE KNOW AS THE PRIMARY BUILDING DOES NOT |
| | YET HAVE A CERTIFICATE OF OCCUPANCY AND THE DESIGNER OF |
| | RECORD FOR THE ARCHITECTURAL SHEETS IS NOW NEW, PLEASE |
| | BE SURE THESE PLANS WHICH DIRECTLY AFFECT THE PROJECT |
| | CONTAIN A *SHOP DRAWING* REVIEW STAMP. |
| | PLEASE KNOW THAT ANY CHANGES MADE DUE TO LOADS, ENERGY |
| | CALCULATIONS FOR OUTSIDE LIGHTING ETC WHICH IS FED FROM |
| | THE BASE BUILDING WILL REQUIRE PLANS FOR THE BASE |
| | BUILDING ALONG WITH ANY CALCULATIONS TO BE REVISED. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL |
| | SHEETS ARE MISSING THE REQUIRED INFORMATION FOR ONE OF |
| | THE DESIGN FIRMS AS LISTED PER FLORIDA ADMINISTRATIVE |
| | CODE 61G1-16.004 AND FLORIDA STATUTES 481.219. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHICH CONTAINS THIS INFORMATION ON TITLE BLOCKS. THIS |
| | COMMENT IS NOT FOR THE ELECTRICAL SHEETS. |
| | |
| | 5) NOTE: PLEASE SEE THE ELECTRICAL PLANS AS SUBMITTED |
| | NEED TO MEET FBC 13-415.2 |
| | PLEASE PROVIDE LIGHTING DENSITY INFORMATION. |
| | |
| | 6) NOTE: PLEASE SEE TWO ELECTRICAL RISERS AND PANEL |
| | SCHEDULES WERE SUBMITTED. |
| | IT IS UNCLEAR WHICH ONE IS TO BE REVIEWED FOR CODE |
| | COMPLIANCE. |
| | ONE RISER INDICATES A REQUESTED FOR A SEPARATE |
| | ELECTRICAL SERVICE FROM THE POWER COMPANY ONLY TO THIS |
| | BUILDING. THIS CONFLICTS WITH THE OTHER RISER WHICH |
| | INDICATES THE ELECTRICAL BEING FED FROM THE EXISTING |
| | BASED BUILDING SERVICE. |
| | PLEASE KNOW THAT GRANTING AN ADDITIONAL SERVICE FOR THE |
| | POOL HOUSE AS SHOWN IS NOT PERMITTED AS THERE WOULD BE |
| | ELECTRICAL SYSTEMS BEING CROSSED FROM TWO SEPARATE |
| | SERVICES. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 215.5,230.70, 230.71, 230.2, 310.16, 240.4 ETC. |
| | PLEASE COORDINATE. |
| | |
| | 7) NOTE: PLEASE SEE 422.13 IN THE 2005 NEC AS LOADS FOR |
| | ELECTRICAL WATER HEATERS ARE TO BE FIGURED AT 125% AS |
| | THESE ARE CONSIDERED CONTINUOUS LOADS. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |