| 2007-09-16 21:40:53 | HAWTHORN HOTEL POOL HOUSE |
| | 301 LAMBERTON DR |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07080080 |
| | ADD: 301 LAMBERTON DR |
| | CONT: THE WEITZ CO. |
| | TEL: (561)719-0102 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) FBC 1802.2.1 QUESTIONABLE SOILS, WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 4) SHEET T1.1 THE MINIMUM BUILDING TYPE IS INDICATED AS |
| | TYPE III-B I BELIEVE THIS IS THE MINIMUM TYPE FOR THE |
| | HOTEL, PLEASE PROVIDE THE POOL HOUSE MINIMUM BUILDING |
| | TYPE SEE TABLE 503. |
| | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6, |
| | TABLE 601 & TABLE 503. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | |
| | 5)S1.2 INDICATES THIS IS A ENCLOSED BUILDING BUT |
| | THERE ARE SCREENS NOT WINDOWS IN THE BUILDING,A |
| | ALLOWING PRESSURES TO BUILD IN THE BUILDING, THE |
| | APPLICABLE INTERNAL PRESSURE COEFFICIENT WOULD NOT BE |
| | +-.18 FOR A PARTIALLY ENCLOSED BUILDING. |
| | |
| | 6)SHEET S1.1 FOUNDATION DETAIL INDICATES IN CERTAIN |
| | BLOCK CELLS THERE IS TO BE 4 # 5 BARS, IS THIS CORRECT? |
| | IF WHERE ARE THE REQUIRED HOOPS FOR A 4 BAR COLUMN? |
| | |
| | 7) PLEASE COORDINATE THE ARCHITECTURAL SHEETS AND |
| | STRUCTURAL, A3.3 INDICATES THE USE OF WOOD BEAMS OVER |
| | THE VARIOUS OPENINGS WHERE AS THE STRUCTURAL SHEETS |
| | INDICATE THE USE OF ANGLES AS LINTELS? PLEASE PROVIDE |
| | ADDITIONAL INFORMATION. |
| | |
| | 8) THE STRUCTURAL SHEETS DO NOT PROVIDE UPLIFT FORCES |
| | TO BE RESISTED NOR THE TYPE OF HARDWARE TO BE USED TO |
| | RESIST UPLIFT AND LATERAL LOADS. |
| | |
| | 9) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) TRUSS ANCHORS |
| | B)WALL LOUVERS |
| | C) PANEL WALL SYSTEMS- SCREENS |
| | |
| | 10)PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 11)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 12) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | ___ CONTRACTOR DID NOT PROVIDE THE MEANROOF |
| | HEIGHT. |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOFPITCH. |
| | _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE |
| | USED. |
| | _XX__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| | _2&3__ . |
| | _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, |
| | SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THATREQUIRED, AS |
| | DETERMINED BY THEBUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNEDAND SEALED BY |
| | A FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9, |
| | NO ENHANCEDFASTENING ALLOWED. |
| | |
| | 13)SHEET A2.1 INDICATES THE USE OF A DOWN SPOUT BUT |
| | NO SPLASH BLOCK.1503.6 PROTECTION AGAINST DECAY AND |
| | TERMITES. |
| | CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| | LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| | SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| | ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| | HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| | A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 14)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY |
| | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 15 ) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION |
| | MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS |
| | SERVING |
| | ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE |
| | DESIGN COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE |
| | THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE |
| | A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON |
| | COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER |
| | SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 16 ) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE |
| | CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO |
| | MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR |
| | PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO |
| | COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS |
| | EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT |
| | TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |