Plan Review Notes
Plan Review Notes For Permit 07080073
Permit Number 07080073
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-17 18:51:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. FAC 61G1-16.004(6) & FS 481.2055.
 PLEASE SHOW PRINTED NAME IN TITLE BLOCK OF EACH SHEET.
  
 2. SHT A-002 BUILDING #4 DATA. THE BUILDING CODE
 EDITION IS SHOWN AS 2001 FBC. THE CODE IN EFFECT IS THE
 FBC-2004. PLEASE CORRECT CODE REFERENCE.
  
 3. SHT A-200 BUILDING #4 DATA. ONE INTENDED USE
 ACCESSORY OCCUPANCY IS INDICATED AS MERCANTILE RETAIL
 AREA. PLEASE INDICATE THE LOCATION OF THE RETAIL AREA.
 SECTION 106.1.1.
  
 4. SHT A-003 DETAIL E. THE CLEAR FLOOR SPACE FOR THE
 LAV IS NOT SHOWN. PLEASE SHOW CLEAR FLOOR SPACE AS
 INDICATED ON PAGE 7.47. ALSO SHTS A-801, A-801A,
 A-801B, A-801C, A-801D, A-801E, A-802, A-802B & A-802C
 SHALL COMPLY WITH THE FHA-08 DESIGN MANUAL FOR THE
 PRIMARY ENTRY LEVEL. PLEASE INDICATED ON THE PLANS AND
 SHOW COMPLIANCE WITH REQUIREMENTS 1 THRU 7. SEE PAGE 7
 OF THE FHA DESIGN MANUAL.
  
 5. SHT A-0003A DETAILS A & B. THE WATER CLOSET CAN NOT
 BE IN THE CLEAR FLOOR SPACE REQUIRED FOR THE LAV,
 (DETAIL A), OR SHOWER, (DETAIL B). PLEASE SHOW
 COMPLIANCE WITH THE CLEAR FLOOR SPACE REQUIREMENTS.
  
 6. SHT A-104 ROOF DRAIN CALCULATIONS. NO MENTION OF THE
 CONTRIBUTION FROM THE ROOF AREA ABOVE DRAINING ONTO THE
 ROOF AREAS. SECTION 1106.3. PLEASE SHOW THE UPPER ROOF
 CONTRIBUTION IN THE CALCULATIONS FOR THE ROOF/DECK
 DRAINS.
  
 7. SHT A-104 ROOF DRAIN CALCULATIONS. AREA "C" SCALES
 OUT TO BE ROUGHLY 15FT SHORTER THAN AREAS "D & E", BUT
 SHOWS MORE TOTAL AREA. PLEASE CLARIFY. SECTION 106.1.1.
 IS THERE MORE VERTICAL SF OR UPPER ROOF AREA?
  
 8. SHT A-104 AREAS "D & E" SCALE OUT TO BE
 APPROXIMATELY THE SAME LENGTH, BUT AREA "E" IS
 INDICATED AS ABOUT TWICE THE AREA. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 9. SHT A-104. AREA "F" SHOWS NO CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS. PLEASE SHOW
 CALCULATIONS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SQUARE FOOTAGE OF THE ROOF AREA,
 WITH 1/2 THE AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AS WELL AS THE AREA FROM THE UPPER ROOF THAT
 DRAINS ONTO THE ROOF FROM ABOVE.
  
 10. SHT A-104 CALCULATIONS ARE REQUIRED FOR THE OUTDOOR
 LIVING PATIO & DECK DRAINS. SHOW THE SQUARE FOOTAGE OF
 THE DECK AREA AND SHOW 1/2 AREA OF ALL VERTICAL WALLS
 AND INDICATE THE SQUARE FOOT AREA OF THE ROOFS THAT
 DRAIN ONTO THE DECK AREA FROM ABOVE. SECTIONS 1106 &
 1107 AND ALL SUBSECTIONS.
  
 11. SHT A-104 SHOW THE LOCATIONS FOR ALL SECONDARY
 DRAINAGE ON THE DECK. INDICATE ALL AREAS THAT DRAIN OFF
 THE SIDE OF THE BUILDING IF ANY. SECTIONS 106.1.2 &
 1107.
  
 12. SHT A-104 THE LOCATIONS OF THE DECK DRAINS IN THE
 OUTDOOR LIVING PATIO & DECK DRAINS ARE APPROXIMATELY
 6FT FROM THE SLIDING GLASS DOOR, BUT THE DISTANCE TO
 THE AREA WHERE THE OVERFLOW LEAVES THEPATIO AREA IS
 APPROXIMATELY 11FT. IS THERE ANY CONCERN THAT THE STORM
 WATER WILL ENTER THE UNIT BEFORE THE STORM WATER
 REACHES THE OVERFLOW AREA? PLEASE CLARIFY. SECTION
 106.1.2. (MORE INFORMATION REQUIRED). SECTION 1503.4.3
  
 13. SHT A-104 THERE ARE ABOUT FIVE PLANTER DRAINS THAT
 RECIEVE THE WATER OF THE VERTICAL WALL FROM THE ROOF
 AREA. WHEN INDICATING THE SQUARE FOOTAGE BEING DRAINED
 BY THESE PLANTER DRAINS, PLEASE SHOW 1/2 THE AREA OF
 THE VERTICAL WALLS INCLUDED IN THE TOTAL SQUARE
 FOOTAGE. SECTION 1106.4.
  
 14. SHT A-108 THE ROOF DRAINS DO NOT APPEAR TO BE
 LOCATED AT THE LOW POINT OF THE ROOF. THE LOW AREA FOR
 AREA"G" APPEARS TO BE IN THE ELEVATOR MACHINE ROOM.
 NO SLOPE INDICATION IS SHOWN FOR AREA "F" PLEASE
 CLARIFY. SECTION 106.1.1. ELEVATIONS SHALL BE SUBMITTED
 FOR ALL AREAS OF THE ROOF TO VERIFY IF THE ROOF DRAINS
 ARE IN THE LOWEST POINT OF THE ROOF.
  
 15. SHTS A-205 & A-206 SHOW THE SECONDARY DRAINS FOR
 ALL AREAS PER SECTION 1107.
  
 16. SHT A-206 SHOW COMPLIANCE FOR THE TOILET ROOMS.
 (337 & 338).
 ____W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ____URINAL
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 ____LAVS
 A.11-4.19.3 CLEAR FLOOR SPACE
 ____TOILET ROOMS
 A. 11-4.22.3 SHOW THE 5' TURNING AREA IN THE TOILET
 ROOM, ITS NOT REQUIRED IN STALL
  
 17. SHT A-907 FINISH SCHEDULE INDICATES PAINT ON GWB
 FOR THE ADCP TOILET ROOM, MEN'S TOILET ROOM & WOMEN'S
 TOILET ROOM. SECTION 1210.2 REQUIRES THE WALL WITHIN
 2FT OF WATER CLOSETS OR URINALS TO HAVE A "SMOOTH,
 HARD, NONABSORBENT" SURFACE. PAINTED GWB DOES NOT MEET
 THE "HARD" REQUIREMENT OF THE CODE SECTION. PLEASE SHOW
 COMPLIANCE.
  
 18. ALL CIVIL SHEETS ARE NOT SIGNED, SEALED OR DATED AS
 REQUIRED PER SECTION 106.1 AND FAC 61G15-23.002(2) & FS
 472.025. PLEASE SIGN, SEAL AND DATE ALL SHEETS.
  
 19. SHTS CS-1 & A-001A. THE PRINTED NAME OF THE PERSON
 SIGNING & SEALING THE DOCUMENT IS REQUIRED ON EACH
 SHEET. FAC 61G1-16.003, 61G1-16.004(6) & FS 481.2055.
  
 20. ALL CIVIL SHEETS SHALL BE SIGNED, SEALED &DATED
 PRIOR TO PLANS BEING ISSUED. THE DATE THE SEAL AND
 SIGNATURE ARE AFFIXED TO THE DOCUMENTS SHALL BE ENTERED
 ON THE PLANS, SPECIFICATIONS, REPORTS, OR OTHER
 DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER. FAC 61G15-23.002(1)(2) & FS
 471.025.
  
 21. SHT P0.1 PLUMBING LEGEND. ALL WATER LINES ARE SOLID
 LINES WITH NO DIFFERENCES. PLEASE CLARIFY. SECTION
 106.1.1.--PLUMBING SHEET INDEX DOES NOT INDICATE A
 6TH FLOOR. PLEASE CLARIFY.--SHTS P5.2.1, P5.2.2 &
 P5.3.1 WERE NOT SUBMITTED IN ONE SET OF PLANS.
  
 22. SHT P2.1.1 SHOWS SANITARY RISER #1 IN A SOLID WALL
 AND RISERS #5 & #8 IN COLUMNS. PER SECTION 1906.3
 CONDUITS AND PIPES EMBEDDED IN CONCRETE. CONDUITS,
 PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL TO
 CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, SECTION
 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE WITH
 APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. PLEASE
 SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE
 REQUIRED. SECTION 305.
  
 23. SHT P2.1.2 SHOWS SANITARY RISERS #13 & #14 IN A
 SOLID WALL AND RISERS #21 & #25 & #26 IN COLUMNS. PER
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES
 MAY BE REQUIRED. SECTION 305.
  
 24. SHT P2.1.3 A CLEANOUT IS REQUIRED IN THE BUILDING
 STORM DRAIN TO SDR'S 1 & 2 AND AT THE JUNCTION OF THE
 STORM SEWER AT SDR 3. SECTION 1101.8.
  
 25. SHT P2.1.4 A CLEANOUT IS REQUIRED AT THE JUNCTION
 OF THE STORM SEWER AT SDR 4. SECTION 1101.8.
  
 26. SHT P2.1.5 TWO KEY NOTES #3 SHOWN. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 27. SHT P2.1.5 IDENTIFY ALL STRUCTURES. (CB-1, CB-2
 ETC). SECTION 106.1.2.
  
 28. SHT P2.1.5 CONDENSATE RISER #1&2 AND SANT. RISER #1
 ARE SHOWN IN A SOLID WALL. PER SECTION 1906.3 CONDUITS
 AND PIPES EMBEDDED IN CONCRETE. CONDUITS, PIPES AND
 SLEEVES OF ANY MATERIAL NOT HARMFUL TO CONCRETE AND
 WITHIN THE LIMITATIONS OF ACI 318, SECTION 6.3, ARE
 PERMITTED TO BE EMBEDDED IN CONCRETE WITH APPROVAL OF
 THE REGISTERED DESIGN PROFESSIONAL. PLEASE SUBMIT
 APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE REQUIRED.
 SECTION 305.
  
 29. SHT P2.1.5 A CLEANOUT IS REQUIRED NEAR THE JUNCTION
 OF THE BUILDING STORM DRAIN AND THE BUILDING STORM
 SEWER. SECTION 1101.8.
  
 30. SHT P2.1.6 KEY NOTES #1 & #3 NOT FOUND. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 31. SHT P2.2.1 CONDENSATE RISER #1&2 AND SANT. RISER #1
 ARE SHOWN IN A SOLID WALL. PER SECTION 1906.3 CONDUITS
 AND PIPES EMBEDDED IN CONCRETE. CONDUITS, PIPES AND
 SLEEVES OF ANY MATERIAL NOT HARMFUL TO CONCRETE AND
 WITHIN THE LIMITATIONS OF ACI 318, SECTION 6.3, ARE
 PERMITTED TO BE EMBEDDED IN CONCRETE WITH APPROVAL OF
 THE REGISTERED DESIGN PROFESSIONAL. PLEASE SUBMIT
 APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE REQUIRED.
 SECTION 305.
  
 32. SHT P2.2.1 SANITARY RISER #8 IS SHOWN IN A COLUMN.
 PER SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN
 CONCRETE. CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL
 NOT HARMFUL TO CONCRETE AND WITHIN THE LIMITATIONS OF
 ACI 318, SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN
 CONCRETE WITH APPROVAL OF THE REGISTERED DESIGN
 PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 33. SHT P2.2.2 THE MATCH LINE DOES NOT REFLECT THE
 PREVIOUS WEST SECTION MATCH LINES. PLEASE CORRLEATE
 MATCH LINES TO AVOID CONFUSION. SECTION 106.1.1.
  
 34. SHT P2.2.2 SANITARY RISERS #8, #21, #22 & #26 ARE
 SHOWN IN COLUMNS. PER SECTION 1906.3 CONDUITS AND PIPES
 EMBEDDED IN CONCRETE. CONDUITS, PIPES AND SLEEVES OF
 ANY MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 35. SHT P2.2.2 SHOWS SANITARY RISERS #13 & #14 IN A
 SOLID WALL AND RISERS #21 & #25 & #26 IN COLUMNS. PER
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES
 MAY BE REQUIRED. SECTION 305.
  
 36. SHT P2.2.2 SHOWS A MINI SUTDOR VENT. A RELEIF VENT
 IS REQUIRED PER SECTION 917.3.2. PLEASE SHOW ON THE
 FLOOR PLAN AND THE RISER DIAGRAM.
  
 37. SHT P2.3.1A RELIEF VENT IS REQUIRED FOR THE AIR
 ADMITTENCE VALVE AT THE PAVILLION SINK. SECTION
 917.3.2. PLEASE SHOW ON THE FLOOR PLAN AND THE RISER
 DIAGRAM.
  
 38. SHT P2.3.1 SANITARY RISER #6 SHOWS A BRANCH LINE
 RUNNING THRU A COLUMN. PER SECTION 1906.3 CONDUITS AND
 PIPES EMBEDDED IN CONCRETE. CONDUITS, PIPES AND SLEEVES
 OF ANY MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 39. SHT P2.3.1 SANT. RISER #1 DESIGNATOR IS NOT
 LEGIBLE. SECTION 106.1.1.
  
 40. SHT P2.3.1 CONDENSATE RISER #1&2 AND SANT. RISER #1
 ARE SHOWN IN A SOLID WALL. PER SECTION 1906.3 CONDUITS
 AND PIPES EMBEDDED IN CONCRETE. CONDUITS, PIPES AND
 SLEEVES OF ANY MATERIAL NOT HARMFUL TO CONCRETE AND
 WITHIN THE LIMITATIONS OF ACI 318, SECTION 6.3, ARE
 PERMITTED TO BE EMBEDDED IN CONCRETE WITH APPROVAL OF
 THE REGISTERED DESIGN PROFESSIONAL. PLEASE SUBMIT
 APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE REQUIRED.
 SECTION 305.
  
 41. SHT P2.3.1 SHOW THE LOCATION OF CONDENSATE RISER
 1/2. SECTION 106.1.2.
  
 42. SHT P2.3.1 SANITARY RISER #9 BRANCH LINE RUNNING
 THRU A COLUMN. PER SECTION 1906.3 CONDUITS AND PIPES
 EMBEDDED IN CONCRETE. CONDUITS, PIPES AND SLEEVES OF
 ANY MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 43. SHT P2.3.1. SANITARY RISER #6 BRANCH LINE RUNNING
 THRU A COLUMN. PER SECTION 1906.3 CONDUITS AND PIPES
 EMBEDDED IN CONCRETE. CONDUITS, PIPES AND SLEEVES OF
 ANY MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 44. SHT P2.3.2 THE TITLE BLOCK READS DRAINAGE PLAN 2ND
 FLOOR, BUT THE PAGE TITLE INDICATEDS 3RD FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 45. SHT P2.3.2 SDR 10 & ODR SDR 10 ARE SHOWN IN A
 COLUMN. PER SECTION 1906.3 CONDUITS AND PIPES EMBEDDED
 IN CONCRETE. CONDUITS, PIPES AND SLEEVES OF ANY
 MATERIAL NOT HARMFUL TO CONCRETE AND WITHIN THE
 LIMITATIONS OF ACI 318, SECTION 6.3, ARE PERMITTED TO
 BE EMBEDDED IN CONCRETE WITH APPROVAL OF THE REGISTERED
 DESIGN PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 46. SHT P2.3.2SANITARY RISERS 16, 19, 20 & 25 SHOW
 BRANCH LINES RUNNING THRU COLUMNS. PER SECTION 1906.3
 CONDUITS AND PIPES EMBEDDED IN CONCRETE. CONDUITS,
 PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL TO
 CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, SECTION
 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE WITH
 APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. PLEASE
 SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES MAY BE
 REQUIRED. SECTION 305.
  
 47. SHT P2.3.2 REQUIRED SECONDARY DRAINS/SCUPPERS ARE
 NOT SHOWN. SECTION 1107. PLEASE SHOW THE LOCATION OF
 REQUIRED SECONDARY DRAINS OR OVERFLOW SCUPPERS AND
 INDICATE THE SQUARE FOOTAGE BEING DRAINED BY EACH
 DRAIN/SCUPPER.
  
 48. SHT P2.3.1E FOUR PLANTERS HAVE VERTICAL
 CONTRIBUTION NOT INDICATED IN THE CALCULATIONS. PLEASE
 SHOW ALL SQUARE FOOTAGE DRAINED BY THE PLANTER DRAINS.
 TABLE 1106.3.
  
 49. SHT P2.3.1E THE DISTANCE FROM THE DECK DRAINS IN
 THE PATIO TO THE SLIDING GLASS DOORS TO EACH UNIT US
 ABOUT 1/2 THE DISTANCE TO THE OVERFLOW LINE OUT OF THE
 PATIO AREA. IS THERE ANY CONCERN THAT THE STORM WATER
 WILL ENTER THE UNIT BEFORE OVERFLOWING OFF THE PATIO IF
 THERE IS A BLOCKAGE IN THE MAIN DECK DRAIN? PLEASE
 CLARIFY. SECTION 106.1.2.
  
 50. SHT P2.3.2E REQUIRED SECONDARY DRAINS/SCUPPERS ARE
 NOT SHOWN. SECTION 1107. PLEASE SHOW THE LOCATION OF
 REQUIRED SECONDARY DRAINS OR OVERFLOW SCUPPERS AND
 INDICATE THE SQUARE FOOTAGE BEING DRAINED BY EACH
 DRAIN/SCUPPER.
  
 51. SHT P2.4.1 SHOW THE RISER NUMBER FOR THE SANITARY
 RISERS AT THE SHOWER, LAV, W/C PORTION OF THE MASTER
 BATH, C-2 UNIT (414), & THE TUB, W/C, LAV BATH C-2 UNIT
 (415). SECTION 106.1.2.
  
 52. SHT P2.4.1 WEST SECTION DRAINAGE PLAN? (SAME AS SHT
 P2.4.2). PLEASE CLARIFY. SECTION 106.1.1.
  
 53. SHT P2.4.2 SHT TITLE STATES 4TH - 6TH FLOORS, BUT
 5TH FLOOR & 6TH - 7TH FLOORS SUBMITTED ALSO. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 54. SHT P2.4.2 SHOW THE PIPING FOR TWO RISERS #8.
 SECTION 106.1.2.
  
 55. SHT P2.4.2 INDICATE THE RISER NUMBER FOR THE MOP
 SINK SANITARY. SECTION 106.1.2
  
 56. SHT P2.4.2 SANITARY RISER #13 IS SHOWN IN A SOLID
 WALL. PER SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN
 CONCRETE. CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL
 NOT HARMFUL TO CONCRETE AND WITHIN THE LIMITATIONS OF
 ACI 318, SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN
 CONCRETE WITH APPROVAL OF THE REGISTERED DESIGN
 PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SLEEVES MAY BE REQUIRED. SECTION 305.
  
 57. SHT P2.4.2 SANITARY RISER NUMBERS 16,19 & 20 ARE
 NOT SHOWN IN THE SAME LOCATION ON THE FLOOR BELOW,
 (P2.3.2), AT THE TUB BATHS. ARE THE RISERS OFFSET? IF
 SO SHOW ON THE FLOOR PLAN AND THE RISER DIAGRAMS.
 SECTION 106.1.1.
  
 58. SHT P2.4.2 SHOW THE RISER NUMBER FOR THE
 LAV/JACUZZI RISER IN THE C-2E UNIT, (425). SECTION
 106.1.1.
  
 59. SHT P2.4.2 RISER DIAGRAM 23 IS NOT INDICATED FOR
 EACH RISER, (3). PLEASE INDICATE ALL RISER NUMBERS.
 SECTION 106.1.2.
  
 60. SHT P2.5.1 SANITARY RISER NUMBER IS NOT INDICATED
 FOR THE W/M STACK BY STAIR #3. PLEASE IDENTIFY. SECTION
 106.1.2.
  
 61. SHT P2.5.2 SANITARY RISERS 10 & 13, CONDENSATE
 RISER 11, AND RISER 9 WITH PLAN NOTE NUMBER 3 ARE
 EITHER IN A SOLID WALL OR PASSING THRU A COLUMN. PER
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES
 MAY BE REQUIRED. SECTION 305.
  
 62. SHT P2.5.2 INDICATE THE RISER NUMBER FOR THE MOP
 SINK. SECTION 105.1.2.
  
 63. SHTS P2.5.1 & P2.5.2 INDICATED TYPICAL 5TH FLOOR.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 64. SHT P2.6.2 SANITARY RISERS 10 & 13, CONDENSATE
 RISER 11, AND RISER 9 WITH PLAN NOTE NUMBER 3 ARE
 EITHER IN A SOLID WALL OR PASSING THRU A COLUMN. PER
 SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SLEEVES
 MAY BE REQUIRED. SECTION 305.
  
 65. SHT P2.6.2 INDICATE THE RISER NUMBER FOR THE MOP
 SINK. SECTION 105.1.2.
  
 66. SHT P2.7.1 ROOF DRAINS DO NOT APPEAR TO BE LOCATED
 AT THE LOW POINT OF THE ROOF. PLEASE SUBMIT ELEVATIONS
 AT DIFFERENT AREAS OF THE ROOF SHOWING THE LOW POINTS
 AND THE HIGH POINTS OF THE ROOF TO VERIFY PROPER
 DRAINAGE TO THE ROOF DRAINS. SECTION 106.1.2. THE
 PRIMARY AND SECONDARY ROOF DRAINS APPEAR TO BE IN LINE,
 BUT NOT NEXT TO EACH OTHER BEFORE OFFSETTING IN
 DIFFERENT DIRECTIONS. THE FLOORS BELOW SHOW THE PRIMARY
 AND SECONDARY RISERS NEXT TO EACH OTHER ON EACH FLOOR
 PLAN. PLEASE CORRELATE THE ROOF DRAIN AND OFFSETS WITH
 THE FLOOR PLANS BELOW. SECTION 106.1.1.
  
 67. SHT P2.7.2 ROOF DRAINS DO NOT APPEAR TO BE LOCATED
 AT THE LOW POINT OF THE ROOF. PLEASE SUBMIT ELEVATIONS
 AT DIFFERENT AREAS OF THE ROOF SHOWING THE LOW POINTS
 AND THE HIGH POINTS OF THE ROOF TO VERIFY PROPER
 DRAINAGE TO THE ROOF DRAINS. SECTION 106.1.2. THE
 PRIMARY AND SECONDARY ROOF DRAINS APPEAR TO BE IN LINE,
 BUT NOT NEXT TO EACH OTHER BEFORE OFFSETTING IN
 DIFFERENT DIRECTIONS. THE FLOORS BELOW SHOW THE PRIMARY
 AND SECONDARY RISERS NEXT TO EACH OTHER ON EACH FLOOR
 PLAN. PLEASE CORRELATE THE ROOF DRAIN AND OFFSETS WITH
 THE FLOOR PLANS BELOW. SECTION 106.1.1.
  
 68. SHT P2.7.2 THE DRAINS FOR CCC-1, CCC-2, & CCC-3 THE
 MAXIMUM DISTANCE FROM THE TRAP TO THE VENT IS 12. ALL
 THREE EXCEED THIS LIMIT. TABLE 906.1.
  
 69. SHT P2.7.2 SHOW THE VENT THRU ROOF LOCATION FOR ALL
 SANITARY RISER DIAGRAMS AND FOR THE CONDENSATE VENT
 THRU THE ROOF. SECTION 106.1.2.
  
 70. SHT P2.7.2 ONE ROOF AREA "?" SHOWS NO SLOPE TO
 DRAIN. PLEASE INDICATE SLOPE TO ROOF DRAIN. SECTION
 106.1.2.
  
 71. SHT P2.7.2 ONE ROOF AREA "?" ROOF DRAIN AND OD NOT
 LABELED. PLEASE INDICATE WHICH IS THE ROOF DRAIN AND
 WHICH IS THE OD. SECTION 106.1.1.
  
 72. SHT P2.7.2 PLAN NOTES (3) &(4). MORE INFORMATION IS
 REQUIRED. WHAT DRAINS FROM CCC-1, CCC-2 & CCC-3. IF THE
 DRAINAGE IS CONDENSATE, THEN IT SHALL NOT DRAIN INTO
 THE SANITARY SYSTEM. ARTICLE III SECTION 90-125(5)--
 PLEASE INDICATE WHAT DRAINS FROM THE UNITS AND IF IT
 SHALL INDEED DRAIN INTO THE SANITARY SYSTEM, THEN
 SUBMIT A DETAIL SHOWING HOW STORM WATER WILL NOT DRAIN
 INTO THE FUNNEL DRAIN. SECTION 106.1.2.
  
 73. SHT P3.1.2 IDENTIFY THE GAS PIPING TO REFLECT THE
 PIPING LEGEND ON SHT P0.1.
  
 74. SHT P3.1.2 INDICATE THE MATERIAL USED FOR THE 3"
 UNDERGROUND WATER SERVICE TO THE PUMP ROOM. MATERIAL
 SHALL COMPLY WITH TABLE 605.3 AND SECTION 605.3.
  
 75. SHT P3.2.1 SHOWS THE HOT & COLD WATER LINES THRU A
 COLUMN. SLEEVES MAY BE REQUIRED, AND PER SECTION 1906.3
 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED.
  
 76. SHT P3.2.1 IDENTYFY ALL PIPING SYSTEMS, HOT, COLD &
 GAS LINES. UNABLE TO VERIFY CODE COMPLIANCE UNTIL ALL
 LINES ARE IDENTIFIED. SECTION 106.1.2.
  
 77 SHT P3.2.1 HAS A NOTE THAT STATES "SEE RETAIL WATER
 SUPPL RISER ON SHT P7.1". SHT P7.1 NOT SUBMITTED, NOR
 IS IT INDICATED ON THE PLUMBING SHEET INDEX SHT P0.1.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 78. SHT P3.2.2 IDENTYFY ALL PIPING SYSTEMS, HOT, COLD &
 GAS LINES. UNABLE TO VERIFY CODE COMPLIANCE UNTIL ALL
 LINES ARE IDENTIFIED. SECTION 106.1.2.
  
 79. SHT P3.2.2 WATER RISER 13 IS SHOWN THRU A COLUMN.
 PER SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN
 CONCRETE. CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL
 NOT HARMFUL TO CONCRETE AND WITHIN THE LIMITATIONS OF
 ACI 318, SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN
 CONCRETE WITH APPROVAL OF THE REGISTERED DESIGN
 PROFESSIONAL. PLEASE SUBMIT APPROVAL FROM DESIGN
 ENGINEER. SECTION 305.3 SLEEVES MAY BE REQUIRED.
  
 80. SHT P3.2.2 WATER RISER 23 DOES NOT SHOW A
 CONNECTION TO THE WATER MAIN. SECTION 106.1.2. PLEASE
 INDICATE WHERE THE RISER CONNECTS TO THE WATER MAIN.
  
 81. SHT P3.3.1 TWO SHEETS WITH THE SAME NUMBER AND SAME
 INFORMATION SUBMITTED.DELETE ONE. SECTION 106.1.1.
  
 82.SHT P3.3.2 SHOWS RISER 11 IN A COLUMN. PER SECTION
 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED. ALSO THE RISER STARTED
 OUT WITH 3 SLEEVES FOR COLD WATER, GAS & HOT WATER.
  
 83. SHT P3.4.2 SHOWS RISER 11 IN A COLUMN. PER SECTION
 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED. ALSO THE RISER STARTED
 OUT WITH 3 SLEEVES FOR COLD WATER, GAS & HOT WATER.
  
 84. SHT P3.5.2 SHOWS RISER 11 IN A COLUMN. PER SECTION
 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED. ALSO THE RISER STARTED
 OUT WITH 3 SLEEVES FOR COLD WATER, GAS & HOT WATER.
  
 85. SHT P3.6.2 SHOWS RISER 11 IN A COLUMN. PER SECTION
 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE.
 CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL
 TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318,
 SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE
 WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL.
 PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION
 305.3 SLEEVES MAY BE REQUIRED. ALSO THE RISER STARTED
 OUT WITH 3 SLEEVES FOR COLD WATER, GAS & HOT WATER.
  
 86. SHT P3.6.2 OFFSET FOR RISER 23 NOT SHOWN ON THE
 FLOOR PLAN. SECTION 106.1.2.
  
 87. SHT P3.7.2 RISER 11 STARTED OUT WITH 3 SLEEVES FOR
 COLD WATER, GAS & HOT WATER, BUT NOW SHOWS 2. CLARIFY &
 CORRELATE. SECTION 106.1.1.
  
 88. SHT 3.7.2 NOTE INDICATES HOT WATER "UP TO" WATER
 HEATERS, BUT FROM THE HOT RISER DIAGRAM, IT APPEARS
 THAT IT SHOULD READ HOT WATER "DOWN FROM" THE WATER
 HEATERS. PLEASE CLARIFY. SECTION 106.1.1.
  
 89. SHT P3.8.1 THE WATER SUPPLY ROOF PLAN EAST SECTION
 SHOWS NO WATER. PLEASE CLARIFY. SECTION 106.1.1. PLEASE
 INDICATE WHERE THE WATER IS LOCATED.
  
 90. SHT P3.8.2 PRV SET AT 7"W.C. SUBMIT THE TABLE FOR
 THE GAS PRESSURE AT 7" W.C. AS THE MINIMUM PRESSURE
 TABLE IN FBC-2004 FUEL GAS IS .5PSI.
  
 91. SHT P3.8.2 IDENTIFY WHAT THE GAS LINE THAT CONNECTS
 TO THE RISER AND IS ROUTED TO THE AREA BY THE
 CIRCULATION PUMP FOR THE RECIRCULATION OF HOT WATER.
 WHERE IS THE HVAC SYSTEM W/H (200KBTUH MAX) AS THE GAS
 APPLIANCE IS NOT SHOWN ON THE FLOOR PLAN. SECTION
 106.1.2.
  
 92. SHT P3.8.2 NOTE STATES, "GAS, CW AND RECIRC. PIPING
 DOWN", WHEN IT IS ACTUALLY FEEDING UP TO THE ROOF.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 93. SHT P4.1.1 WATER SUPPLY PLANS FOR UNITS C1, C1A &
 CAB. WATER HAMMER ARRESTORS ARE REQUIRED FOR BOTH THE
 HOT & COLD WATER AT THE WASH MACHINE. SECTION 604.9.
  
 94. SHT P4.1.6 WATER SUPPLY PLANS FOR UNITS TH2, & TH2A
 THE WATER HAMMER ARRESTORS ARE REQUIRED AT THE WASH
 MACHINES BY SECTIONS 604.9.
  
 95. SHT P4.1.7WATER SUPPLY PLANS FOR UNITS TH2B, &
 TH2C THE WATER HAMMER ARRESTORS ARE REQUIRED AT THE
 WASH MACHINES BY SECTIONS 604.9.--ALSO SHOW THE
 PIPING TO THE W/C 2ND FLOOR OF TH2B & THE W/C IN TH2C
 IS NOT LOCATED WHERE THE WATER LINE IS SHOWN. PLEASE
 CLARIFY. IF THE FLOOR PLAN IS DIFFERENT, THAN THE WATER
 RISER DIAGRAM CAN NOT BE TYPICAL AND A SEPARATE
 ISOMETRIC RISER DIAGRAM IS REQUIRED.SECTIONS 106.1.1
 & 106.3.5.1.3.
  
 96. SHT P5.1.1 THE SANITARY RISER ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN AT THE BASE OF SANITARY RISERS
 11 & 25. PLEASE CORRELATE. SECTION 106.1.1.
  
 97. SHT P5.1.1 SANITARY RISER 27 DOES NOT REFLECT THE
 FLOOR PLAN AT THE 2ND FLOOR TOILET ROOM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 98. SHT P5.1.1 EXPLAIN THE HORIZONTAL BRANCH LINE FROM
 SANITARY RISER 17 TO SANITARY RISER 13. SECTION
 106.1.1.
  
 99. SHT P5.1.1 THE VENTING DOES NOT REFLECT THE FLOOR
 PLAN BY RISERS 17 & 20. PLEASE CORRELATE. SECTION
 106.1.1.
  
 100. SHT P5.1.1 THE WASH MACHINE PIPING AND W/M BOX
 LOCATION DOES NOT REFLECT THE FLOOR PLAN BY SANITARY
 RISERS 17 & 22. PLEASE CORRELATE. SECTION 106.1.1.
  
 101. SHT P5.1.1 THE OFFSET SHOWN ON THE FLOOR PLAN AT
 THE TOP OF THE RISER TO THE 2ND FLOOR FIXTURES IN UNIT
 TH2B IS NOT REFLECTED ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 102. SHT P5.1.1 EXPLAIN THE BRANCH LINE & CLEANOUT PAST
 RISER 26 ON THE RISER DIAGRAM.THIS IS NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 103. SHT P5.1.2 THE SANITARY DRAINAGE ISOMETRIC DOES
 NOT REFLECT THE FLOOR PLAN AT THE VENTING, WASH MACHINE
 BOX & OFFSET ON THE SECOND FLOOR FOR TH2. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 104. SHT P5.1.2 THE BUILDING DRAIN CLEANOUT IS MISSING
 UPSTREAM OF TH2 AS INDICATED ON THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 105. SHT P5.1.2 THE UNIT TH1D THE LAUNDRY BOX AND
 OFFSET AT THE TOP OF THE RISER TO THE 2ND FLOOR DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 106. SHT P5.1.2THE CLEANOUT UPSTREAM OF UNIT TH1D IS
 NOT SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 107. SHT P5.1.2THE RISER UPSTREAM OF UNIT TH1D DOES
 NOT REFLECT THE FLOOR PLAN. THE OFFSET IS NOT SHOWN &
 NO SANT PLUMBING FOR THE POOL ELECTRICAL ROOM FLOOR
 DRAIN. PLEASE CORRELATE. SECTION 106.1.
  
 108. SHT P5.1.2THE BUILDING SANT. DRAIN JUNCTION BY
 THE 6" 160 DFU & 6" 495 DFU DOES NOT REFLECT YTHE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.
  
 109. SHT P5.1.2 THE CLEANOUT IS MISSING UPSTREAM OF
 RISER JUST UPSTREAM OF UNITS TH1D AND IS SHOWN
 DOWNSTREAM OF SANT. RISER 5 ON THE FLOOR PLAN BUT
 UPSTREAM OF SANT. RISER 5 ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.
  
 110. SHT P5.1.2 DOES NOT REFLECT THE FLOOR PLAN AT THE
 WASH MACHINE BOX AND AT THE TOP OF THE RISER TO THE 2ND
 FLOOR. PLEASE CORRELATE. SECTION 106.1.
  
 111. SHT P5.1.2 SANITARY RISER 8 BRANCH LINE DOES NOT
 REFLECT THE FLOOR PLAN AS IT DOES NOT INDICATE THE
 LOCATION IN RESPECT TO RISERS 6 & 7. PLEASE CORRELATE.
 SECTION 106.1.
  
 112. SHT P5.1.3 SANITARY RISERS 12 & 13 VENT SHALL
 CONNECT TO THE DRAINAGE STACK. SECTION 903.4
  
 113. SHT P5.1.3 SANITARY RISER 4 DOES NOT REFLECT THE
 FLOOR PLAN WHERE THE LAV STACK CONNECTS TO THE DRAIN
 LINE, (PRIOR TO MASTER BATH), AND AT THE LAV IN THE TUB
 BATH AS WELL AS AT THE BASE OF THE RISER TO LAV AT THE
 3RD FLOOR. PLEASE CORRELATE. SECTION 106.1.
  
 114. SHT P5.1.3 SANITARY RISER 6 DOES NOT REFLECT THE
 FLOOR PLAN FOR THE 3RD FLOOR TUB BATHAT THE LAV.
 PLEASE CORRELATE. SECTION 106.1.
  
 115. SHT P5.1.3 SANITARY RISER 8 DOES NOT REFLECT THE
 FLOOR PLAN WHERE THE WASH MACHINE BRANCH LINES CONNECT
 TO THE BUILDING DRAIN LINE AND ONLY ONE BRANCH LINE IS
 SHOWN WHERE THERE ARE TWO BRANCH LINES ON THE FLOOR
 PLAN. ALSO WHERE THE DOUBLE LAV BRANCH LINE CONNECTS TO
 BLDG DRAIN. PLEASE CORRELATE. SECTION 106.1.
  
 116. SHT ??? SHEET BETWEEN P5.1.3 & P5.1.5 IS MISSING
 THE TITLE BLOCK INFORMATION AND PAGE NUMBER. PLEASE
 CLARIFY AND MAKE SURE THE TITLE BLOCK AND SHEET NUMBER
 ARE INDICATED. (SHOWN AS P5.1.4 ON SECOND SET OF
 PLANS).
  
 117. SHT P5.1.4SANITARY RISER 9, MINIMUM 3" REQUIRED
 TO THE WASH MACHINE. SECTION 406.3.--CLEANOUT PAST
 THE WATER CLOSET IS NOT SHOWN ON THE FLOOR PLAN.--
 THE VENT SHALL CONNECT TO THE DRAINAGE STACK AT THE TUB
 BATH RISER. SECTION 903.4.--THE FLOOR DRAIN FOR THE
 WATER HEATER ROOM IS SHOWN ON THE 5TH, 6TH & 7TH FLOORS
 ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.
  
 118. SHT P5.1.4 SANITARY RISER 13 DOES NOT REFLECT THE
 FLOOR PLAN ON THE SECOND FLOOR. PLEASE CORRELATE.
 SECTION 106.1.
  
 119. SHT P5.1.4 SANITARY RISER 15 DOES NOT REFLECT THE
 OFFSET SHOWN ON FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.
  
 120. SHT P5.1.4 SANITARY RISER 16/20 DOES NOT REFLECT
 THE FLOOR PLAN AT EITHER WASH MACHINE BRANCH LINES &
 WHERE THE LAV FOR THE TUB BATH CONNECTS TO THE STACK.
 ALSO THE DRAIN LINE FOR THE CCC UNITS DOES NOT REFLECT
 THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.
  
 121 SHT P5.1.4 SANITARY RISER 17 DOES NOT REFLECT THE
 FLOOR PLAN AT OFFSETS PRIOR TO STACK AND STACK FOR
 JACUZZ I/LAV IS NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.
  
 122. SHT P5.1.5 RISER DIAGRAM #18 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF BOTH WASH MACHINES RISERS.
 THE FLOOR PLAN SHOWS THE LAUNDRY BOX BETWEEN THE
 RISERS. PLEASE CLARIFY. SECTION 106.1.1. PLEASE MAKE
 SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR
 PLAN.
  
 123. SHT P5.1.5 RISER DIAGRAM #19 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF THE WASH MACHINE RISERS FOR
 THE OFFSETS AND THE LAUNDRY BOX SHOWN BETWEEN THE
 RISERS. NOR DOES IT REFLECT THE FLOOR PLAN WHERE THE
 BRANCH CONNECTION FOR THE JACUZZI TUB/LAV TO DRAIN LINE
 AS WELL AS THE LAV ARM IN THE SHOWER BATH. SECTION
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN.
  
 124. SHT P5.1.5 RISER DIAGRAM #21 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BRANCH LINE TO THE
 KITCHEN/LAV/JACUZZI & AT THE WASH MACHINE RISERS WHERE
 THEY CONNECT TO THE DRAIN LINE. SECTION 106.1.1. PLEASE
 MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE
 FLOOR PLAN.
  
 125. SHT P5.1.5 RISER DIAGRAM #25 DOES NOT REFLECT THE
 FLOOR PLAN AT THE BASE OF THE WASH MACHINE STACK, OFF
 SET NOT SHOWN AND JACUZZI TUB IS NOT LEFT OF STACK.
 SECTION 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM
 REFLECTS THE PIPING ON THE FLOOR PLAN.
  
 126. SHT P5.1.5 RISER DIAGRAM #26 DOES NOT REFLECT THE
 FLOOR PLAN AT THE WASH MACHINE STACK BASE, (LAUNDRY BOX
 SHOWN BETWEEN THE W/M STACKS), AND AT THE LAV ARM IN
 THE TUB BATH ALL FLOORS.--A DRY HORIZONTAL VENT IS
 SHOWN UPSTREAM OF THE W/C AT THE BASE OF THE W/C STACK.
 SECTION 106.1.1. DRY HORIZONTAL VENTS ARE NOT APPROVED.
 PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING
 ON THE FLOOR PLAN AND MEETS CODE REQUIREMENTS. SECTION
 905.3.
  
 127. SHT P6.1.1 RISER DOES NOT REFLECT THE FLOOR PLAN.
 SHOW ALL OFFSETS, CONNECTIONS TO MAINS ETC TO REFLECT
 THE FLOOR PLAN.--2 COLD LINES FROM PUMP ROOM AND
 AROUND THE 2ND FLOOR SHOWN ON THE FLOOR PLAN ARE NOT ON
 THE RISER DIAGRAM. THERE IS NO SUPPLY TO THE MOP SINK
 RISER, NOR IS THERE SUPPLY TO THE TOILET ROOM. ALL "TH"
 UNITS SHOW CONNECTING TO A SECOND WATER MAIN. WATER
 PIPING TO WATER HEATER ON THE 3RD FLOOR AND RELATED
 PIPING DOES NOT REFLECT THE FLOOR PLAN. PIPING AT THE
 BASE OF SOME RISERS DOES NOT REFLECT THE FLOOR PLAN.
 ALSO THE COLD WATER ISO FOR THE POOL SUPPLY LINE DOES
 NOT REFLECT THE FLOOR PLAN.PLEASE MAKE SURE THE RISER
 DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN. --RPZV
 BACKFLOW SHALL BE LOCATED AS CLOSE TO THE METER AS
 POSSIBLE ON PRIVATE PROPERTY. PLEASE CORRELATE. SECTION
 106.1.
  
 128. SHT P6.1.2 RISER DOES NOT REFLECT THE FLOOR PLAN
 WHERE SOME RISERS OR DROPS CONNECT TO THE MAIN, AT
 OFFSETS AND AT THE TOP OF RISER 23.--CHECK VALVES
 ARE NOT REQUIRED AT THE BASE OF THE DROPS. (HOW CAN
 RISERS BE DRAINED IF REQUIRED FOR SERVICE)?SECTION
 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN. THE MOP SINK& TOILET
 ROOM PIPING IS NOT SHOWN. "TH" UNITS DO NOT CONNECT TO
 THE MAIN AS SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.
  
 129. SHT P6.1.5 A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - INDICATE ALL CUT SECTIONS DOWNSTREAM
 OF THE REGULATOR FOR THE GAS WATER HEATERS. FINAL DROP
 LENGTH NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. - SIZE OF PIPE
 SHOWS 1-1/4" REDUCING TO 1" THEN BACK TO 1-1/4". PLEASE
 CLARIFY.--ALSO SHOW THE MATERIAL TYPE OF THE
 VENTING FROM THE REGULATORS. (MATERIAL SHALL BE NON
 COMBUSTABLE).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - ALSO SHOW THE TOTAL
 DISTANCE FROM THE REGULATOR TO THE MOST REMOTE OUTLET
 DOWNSTREAM OF THE REGULATOR FOR THE GAS WATER HEATERS.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLEASE SUBMIT AN
 APPROVED TABLE FOR 7"W.C. OR INDICATE 1/2PSI DOWNSTREAM
 OF THE REGULATOR. FBC-2004 FUEL GAS HAS NO 7" W.C.
 TABLES TO VERIFY PIPE SIZES.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. INDICATE MODEL NUMBER FOR EACH REGULATOR.
 --A UNION IS REQUIRED NEXT TO THE REGULATOR NOT AT
 THE END OF A RUN. (SEE GAS WATER HEATERS & HVAC SYSTEM
 REGULATORS).
  
 130. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAM FOR UNITS
 C1, C1A & C1B REQUIRE A WATER HAMMER ARRESTOR FOR THE
 DISH WASHER & FOR BOTH THE HOT & COLD AT THE WASH
 MACHINE. SECTION 604.9.
  
 131. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAMS FOR
 UNITS C2, C2C, C2F & C2D REQUIRE A WATER HAMMER
 ARRESTOR FOR THE DISH WASHER. 604.9.
  
 132. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAM FOR UNITS
 C3 REQUIRES A WATER HAMMER ARRESTOR FOR THE DISH WASHER
 & THE ICE MAKER. 604.9.
  
 133. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAM FOR UNITS
 C5A REQUIRES A WATER HAMMER ARRESTOR FOR THE ICE MAKER.
 604.9.
  
 134. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAMS FOR
 UNITS TH1, TH1A, TH1B, TH1C, TH1D & TH1E REQUIRE A
 WATER HAMMER ARRESTOR FOR THE ICE MAKER PER SECTION
 604.9 AND DO NOT REFLECT THE FLOOR PLAN WHERE THE
 JACUZZI CONNECTS TO THE WATER MAIN LINES. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 135. SHT P6.1.4 ISOMETRIC WATER RISER DIAGRAMS FOR
 UNITS TH2, TH2A, TH2B & TH2C REQUIRE THE WATER HAMMER
 ARRESTORS TO BE LOCATED AT THE WASH MACHINE. SECTION
 604.9.
  
 136. SHT P6.1.4 SUBMIT A FLOOR PLAN FOR THE 3RD FLOOR
 RESTROOMS THAT SHOWS THE WATER PIPING IN PLAN VIEW THAT
 WILL REFLECT THE RISER DIAGRAM. IDENTIFY THE HOT AND
 COLD WATER LINES. SECTION 106.3.5.1.3.
  
 137.SHT P5.2.1 ALL OFFSETS AT THE ROOF LEVEL DO NOT
 REFLECT THE OFFSETS SHOWN ON THE ROOF PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 138. SHT P5.2.1 RISER SDR2 DECK DRAIN, (FD-4), THE TRAP
 AND TRAP PRIMER IS NOT REQUIRED ON THE STORM DRAINAGE.
 PLEASE DELETE.
  
 139. SHT P5.2.1 SDR 5 OFFSETS AT THE ROOF,MINIMUM 5"
 PIPE REQUIRED OR MINIMUM SLOPE 2%.PLEASE SHOW ON THE
 PLANS. TABLE 1106.3.
  
 140. SHT P5.2.1 SDR'S 6, 7, 8, 9, 10, 11, 13 & 14
 OFFSETS AT THE ROOF, MINIMUM 5" PIPE REQUIRED OR
 MINIMUM 4% SLOPE. PLEASE SHOW ON THE PLANS. TABLE
 1106.3.
  
 141. SHT P5.2.1 SDR 12 OFFSET AT THE ROOF, MINIMUM 5"
 PIPE REQUIRED OR MINIMUM 2% SLOPE. PLEASE SHOW ON THE
 PLANS. TABLE 1106.3.
  
 142. SHT P5.2.1 SDR 15 OFFSET AT THE ROOF, MINIMUM 6"
 PIPE REQUIRED OR MINIMUM 4% SLOPE. PLEASE SHOW ON THE
 PLANS. TABLE 1106.3.
  
 142. SHT P5.2.1 SDR'S 10 & 15 FD-4 IS NOT SHOWN ABOVE
 THE THIRD FLOOR BT ON THE 2ND FLOOR ON THE FLOOR PLAN.
 THE RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 143. SHT P5.2.1 THE GCO IS SHOWN UPSTREAM OF SDR 13 ON
 THE FLOOR PLAN BUT IS SHOWN DOWNSTREAM ON THE RISER
 DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.
  
 144. SHT P5.2.2 SHOW ALL PIPE SIZES PER TABLE 1106.3.
  
 145. SHT P5.2.2 CLEANOUTS REQUIRED BY SECTION 1101.8
 SHALL BE SHOWN TO REFLECT THE FLOOR PLAN. (SOME ARE
 MISSING). PLEASE CORRELATE. SECTION 106.1.1.
  
 146. SHT P5.2.2 RECHECK THE ADDITION ON DDR 1 & DDR 7
 AND CORRECT ALL SQUARE FOOTAGE FOR THOSE RISERS AND ALL
 PIPING DOWNSTREAM. TABLE 1106.3.
  
 147. SHT P5.2.2MINIMUM 5" PIPE REQUIRED FOR DD
 2,500SF ON RISERS DDR-2 & DDR-3. TABLE 1106.3.
  
 148. SHT P5.2.2 MINIMUM 5" PIPE REQUIRED FOR 1750SF,
 (4" SHOWN), ON RISER DDR-5. TABLE 1106.3.
  
 149. SHT P5.2.2 ALL PIPING DOWNSTREAM OF THE LAST CATCH
 BASIN SHALL SLOPE IN A UNIFORM SLOPE OF 1/4"/FT. PLEASE
 SHOW ON THE PLANS. SECTION 704.1.
  
 150. SHT P9.1.1 ROOF TOP EQUIPMENT. CONDENSATION
 CONNECTION DETAIL INDICATES A LINE TO DISCHARGE THAT
 RUNS BELOW THE ROOF & CONNECTS TO NEAREST CATCH BASIN,
 BUT SHT P2.7.2 SHOWS RTU-2 DISCHARGING TO NEAREST ROOF
 DRAIN. PLEASE CORRELATE DETAIL AND ROOF PLAN. SECTION
 106.1.1.
  
 151. THERE IS A MOP SINK INDICATED IN ROOM 339 THAT HAS
 NO WATER PIPING SHOWN. PLEASE CLARIFY. SECTION
 106.1.1.
  
 152. ALL LANDSCAPE PLANS THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF ALL SHEETS. THE SEAL FOR EACH SHEET IS
 NOT APPROVED AS IT IS REQUIRED TO BE APPROX. 2" IN
 DIAMETER. FAC 61G1-16.002, 61G1-16.004(2) & FS
 481.305.
  
 153. SHTS IR-1 THRU IR-12 THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF ALL SHEETS. THE SEAL FOR EACH SHEET IS
 NOT APPROVED AS IT IS REQUIRED TO BE APPROX. 2" IN
 DIAMETER.--SUBMIT ONLY THE IRRIGATION SHEETS FOR
 BUILDING 5 IN THE PLANS FOR BUILDING 5.--INDICATE
 THE WATER SOURCE FOR THE IRRIGATION AND SHOW RPZV
 BACKFLOW LOCATION. SHOW THE CONTROLLER LOCATION AND THE
 RAIN SENSOR LOCATION ON THE PLANS. FAC 61G1-16.002,
 61G1-16.004(2) & FS 481.305.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  