2007-09-10 18:16:43REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PERMIT APPLICATION INDICATES AN ADDRESS ON HANK
 AARON DRIVE, BUT PLANS SHOW AN ADDRESS ON SAMANTHA
 LANE. ENERGY CALCULATIONS SHOW AN ADDRESS ON N.E. 3RD
 AVENUE. PLEASE SHOW CORRECT ADDRESS ON ALL 3 LOCATIONS.
 FBC 106.1.3
  
 2. M0.1: OUTSIDE AIR AND EXHAUST AIR CALCULATIONS,
 INCORRECT CODES AND REFERENCE STANDARDS ARE CITED.
 REFERENCE THE CORRECT STANDARDS WHICH ARE IN EFFECT AT
 TIME OF PERMIT APPLICATION SUCH AS FBC,M 2004 TABLE
 403.3 AND ASHRAE 62.1-2004. SEE FBC,M CH.15. ALSO, THE
 VENTILATION SYSTEMS SHALL BE DESIGNED BY EITHER FBC,M
 TABLE 403.3 OR ASHRAE 62.1-2004. SELECT AND DECLARE ONE
 METHOD OR THE OTHER TO BE USED AS ALLOWED BY FBC,M
 403.4.
  
 3. M0.2 PROVISIONS (A): IF THERE ARE CONFLICTS BETWEEN
 ANY OF THE LISTED CODES OR STANDARDS AND THE ONES
 CURRENTLY ADOPTED BY THE STATE OF FLORIDA, THE
 CURRENTLY ADOPTED CODE SHALL PREVAIL.
  
 4. M0.2 PROVISIONS (B): DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY DUCT OF ANY SYSTEM WITH A
 DESIGN CAPACITY EXCEEDING 2000 CFM, NOT JUST THOSE WITH
 COMMON PLENUMS. FBC,M 606.2.1
  
 5. M0.2 PROVISIONS (D): ALL THERMOSTATS WITHIN DWELLING
 UNITS SHALL BE AT A MAXIMUM HEIGHT OF 48" PROVIDED
 THERE IS AN UNOBSTRUCTED FORWARD APPROACH IN ACCORDANCE
 WITH FBC CH.11 PART B SECTION 5, REQUIREMENT 5.
  
 6. EXTERIOR WALL LOUVERS ARE CLASSIFIED AS PANEL WALLS
 PER FAC RULE 9B-72. AS SUCH, THEY ARE SUBJECT TO THE
 FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT
 APPROVALS FOR ALL WALL LOUVERS TO BE USED ON THIS
 PROJECT. FOR MORE INFORMATION ON THE FLORIDA PRODUCT
 APPROVAL SYSTEM PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 7. M2.1.1: PROVIDE C.O. DETECTION SYSTEM SUBMITTAL WITH
 INSTALLATION INSTRUCTIONS TO FACILITATE A THOROUGH
 REVIEW OF THE GARAGE VENTILATION SYSTEM. FBC 106.1.2
  
 8. M2.1.1: SHOW EF-8 TO BE PROTECTED FROM POTENTIAL
 VEHICLE IMPACT IN ACCORDANCE WITH FBC,M 304.5.
  
 9. M2.1.2: EF-8,9,10,11,12 ARE DISCHARGING ONTO A
 WALKWAY (ACCESSIBLE RAMP) WHICH IS PROHIBITED BY FBC,M
 401.5.2. ALSO, SEE FBC,M 401.7 AND 501.2.
  
 10. M2.1.2 AND THROUGHOUT: EQUIPMENT DESIGNATIONS ON
 FLOOR PLANS DO NOT MATCH DESIGNATIONS ON EQUIPMENT
 SCHEDULE (M6.1). EXAMPLES: UNIT IN MAIL ROOM IS MARKED
 HP-14 ON M2.2.1 BUT IS MARKED AHU-14 ON SCHEDULE.
 PLEASE COORDINATE FLOOR PLANS AND SCHEDULES. FBC
 106.1.3
  
 11. M2.1.2 AND M6.1: THERE IS NO INDICATION OF THE
 AMOUNT OF OUTDOOR AIR SUPPLIED TO HP-14, EITHER ON THE
 OUTSIDE AIR CALCULATIONS OR THE WATER SOURCE HEAT PUMP
 SCHEDULE. PROVIDE INFORMATION NEEDED TO DETERMIN THE
 REQUIRED OUTDOOR AIR QUANTITIES. ALSO, SEE COMMENT #2.
  
 12. M2.1.2: HP-14 (AND ALL UNITS WITH INDIVIDUAL O.A.
 INTAKES) OUTDOOR AIR INTAKE REQUIRES A VOLUME DAMPER
 PER FBC 13-409.1.ABC.1.1. ALSO, A MOTORIZED OR GRAVITY
 OPERATED DAMPER IS REQUIRED PER FBC 13-409.1.ABC.3.3.
  
 13. M2.2.1: SHOW EF-13 TO BE PROTECTED FROM POTENTIAL
 VEHICLE IMPACT PER FBC,M 304.5.
  
 14. M2.2.1: IF DRYER EXHAUST RISERS ARE OPEN AT THE
 BOTTOM WITH A GRILL, AS INDICATED ON PG M5.1, THE
 OPENINGS SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS
 IN ACCORDANCE WITH FBC,M 607.5.5.1.
  
 15. M2.2.1 AND M2.2.2: DRYER EXHAUST RISER DUCTS WHICH
 ARE OPEN AT THE BOTTOM ARE FUNCTIONING IN ONE OF THE
 TWO FOLLOWING PROHIBITED CONDITIONS:
 A) GARAGE EXHAUST; IN THIS CASE FBC,M 504.1 REQUIRES
 DRYER EXHAUST SYSTEMS TO BE INDEPENDENT OF ALL OTHER
 SYSTEMS.
 B) MAKE-UP AIR FOR DRYER FANS; IN THIS CASE FBC,M
 401.5.1 REQUIRES INTAKE OPENINGS AT LEAST 10' FROM
 ALLEYS, STREETS OR PARKING LOTS. ALSO, MAKE-UP OR
 TRANSFER AIR CAN NOT BE DRAWN FROM DISSIMILAR
 OCCUPANCIES PER FBC,M 403.2.1(1).
  
 16. M2.2.2: HP-13 IS SERVING THE MAINTENANCE OFFICE.
 WHAT IS THE SOURCE OF OUTDOOR AIR FOR THIS SPACE?
 MAKE-UP OR SUPPLY AIR IS ALSO REQUIRED FOR EF-1 IN THE
 TOILET ROOM. PROVIDE OUTDOOR AIR AS REQUIRED BY FBC,M
 403.3 AND TABLE 403.3. THE OFFICE SPACE SHALL BE
 MAINTAINED AT A POSITIVE PRESSURE WITH RESPECT TO THE
 GARAGE AREA PER FBC,M 404.3.
  
 17. M2.2.2: SHOW SIZE OF TOILET EXHAUST DUCT FOR EF-1
 IN MAINTENANCE OFFICE. FBC 106.3.5.1.4
  
 18. M2.3.1 THROUGH M2.6.2: SMOKE DAMPERS (AS WELL AS
 THE FIRE DAMPERS SHOWN ON PLAN) ARE REQUIRED IN ALL RTU
 DUCT PENETRATIONS OF CORRIDOR WALLS PER FBC,M 607.5.4.
  
 19. M2.3.1 AND ALL FLOORS: RISERS PAU-1 AND PAU-2 AS
 SHOWN ON FLOOR PLAN DOES NOT CORRESPOND WITH ANY RISERS
 ON THE RISER DETAILS ON PG M5.1. IS THIS SUPPOSED TO BE
 RISERS RTU-1 AND RTU-2? PLEASE COORDINATE FLOOR PLANS
 AND RISER PLANS.
  
 20: M2.3.1 AND ALL FLOORS: RISER PAU-1, FIRE AND SMOKE
 DAMPER IS REQUIRED AT ALL DUCT PENETRATIONS OF THE
 SHAFT PER FBC,M 607.5.5.1.
  
 21. M2.3.2: SUPPLY DROPS IN CORRIDOR ARE MISSING SIZE
 AND CFM DESIGNATIONS. PLEASE CORRECT AND RESUBMIT. FBC
 106.3.5.1.4
  
 22. M2.3.2 AND ALL FLOORS: RISER PAU-2, FIRE AND SMOKE
 DAMPER IS REQUIRED AT ALL DUCT PENETRATIONS OF THE
 SHAFT PER FBC,M 607.5.5.1.
  
 23. M2.3.2: MEN'S RESTROOM (337). FLOOR PLAN SHOWS 240
 CFM OF SUPPLY WITH 200 CFM OF EXHAUST. ALL AIR SUPPLIED
 TO SUCT SPACES SHALL BE EXHAUSTED, INCLUDING ANY AIR IN
 EXCESS OF THAT REQUIRED BY TABLE 403.3 IN ACCORDANCE
 WITH FBC,M 403.2.1(3).
  
 24. M2.3.2: RESIDENT STORAGE A/C CLOSET (313A), WHAT IS
 THE SOURCE OF R/A FOR HP-7? ROOM 313A COULD NOT BE
 FOUND ON DOOR SCHEDULE TO CHECK FOR GRILL OR LOUVERED
 DOOR. NOTE: 313A IS A PLENUM AND ALL MATERIALS USED
 SHALL BE APPROPRIATE FOR THAT APPLICATION. SEE FBC,M
 602.2.1 AND FBC,M 603.9. DOOR SHALL BE OF
 NON-COMBUSTIBLE MATERIALS OR MEET THE 25/50 RATING AS
 REQUIRED BY THIS CODE. THIS APPLIES TO ALL DOORS USED
 IN PLENUM CLOSETS IN ALL AREAS.
  
 25. M2.4.2: SHOW THE DESIGNATION FOR THE HP SERVING
 FITNESS ROOM 431. ALSO, SHOW SOURCE OF RETURN PER FBC,M
 601.4 AND MEANS OF SERVICE ACCESS PER FBC,M SEC.306.
  
 26. M2.4.2 PG A-106 SHOWS HP-7 IN RESIDENT STORAGE 411
 TO BE IN A CLOSET (411A). THIS DOES NOT MATCH M2.4.2
 FLOOR PLAN, WHICH SHOWS HP-7 IN A CAGE. COORDINATE
 PLANS, SHOWING COMPLIANCE WITH ALL PLENUM, SERVICE
 ACCESS AND R/A REQUIREMENTS AS STATED IN COMMENTS 24
 AND 25. NOTE: ROOM 411 IN ITS ENTIRETY WILL BE
 CONSIDERED A PLENUM UNLESS THE 8X6 O.A. DUCT TIES INTO
 A DUCTED RETURN.
  
 27. M2.5.2: RESIDENT CONFERENCE CENTER 533 DOES NOT
 APPEAR ON HEAT PUMP SCHEDULE OR OUTSIDE AIR SCHEDULE.
 PROVIDE MISSING INFORMATION ON FLOOR PLAN AND
 SCHEDULES. ALSO, SHOW THE SOURCE OF R/A AND MEANS OF
 SERVICE ACCESS.
  
 28. M2.5.2: FOR STORAGE ROOM 511, SEE COMMENT #26 AND
 SHOW COMPLIANCE WITH THE SAME. COORDINATE MECHANICAL
 FLOOR PLAN WITH PG A-106.
  
 29. M2.4.2 AND M2.5.2: NO SOURCE OF CONDENSER WATER FOR
 UNDESIGNATED HEAT PUMPS. SHOW SOURCE OF CONDENSER WATER
 AND LOCATION OF RISERS/PIPING ON FLOOR PLANS AND RISER
 DIAGRAMS. FBC 106.1.1 AND FBC 106.3.5.1.4.
  
 30. M2.6.2: HP-8 IN STORAGE 611 AND 711, COORDINATE
 MECHANICAL FLOOR PLANS WITH A-107. SEE A/C CLOSET. SHOW
 COMPLIANCE WITH REQUIREMENTS AS STATED IN COMMENT #26.
  
 31. M2.7.1: CONDENSER WATER LINE SIZES ON ROOF PLAN DO
 NOT MATCH THOSE ON RISERS AS SHOWN ON M5.2.1. EXAMPLE:
 RISER DIAGRAM SHOWS 3" LINES FEEDINGCWR-1 (2 1/2")
 AND CWR-2 (2"), BUT ROOF PLAN SHOWS A 4" LINE FEEDING
 BOTH RISERS WITH THE 4" LINES CONTINUING TO CWR-2.
 PLEASE COORDINATE DRAWINGS.
  
 32. M2.7.2: CONDENSER WATER LINE SIZES ON ROOF PLAN DO
 NOT MATCH THOSE ON RISER DIAGRAMS AS SHOWN ON M5.2.1
 AND M2.5.2. EXAMPLE: CWR-10 ON ROOF PLAN SHOWS 2 1/2"
 LINES BUT RISER DIAGRAM SHOWS 2" LINES. PLEASE
 COORDINATE DRAWINGS.
  
 33. M 2.7.2: TX-21 RISER TERMINATES IN OR UNDER THE
 ELEVATOR MACHINE ROOM. MECHANICAL EXHAUST SHALL BE
 DISCHARGED TO THE OUTDOORS PER FBC,M 501.2.
  
 34. M2.7.22: AC BOILER, THIS DOES NOT APPEAR ON ANY
 MECHANICAL EQUIPMENT SCHEDULES OR IN PLUMBING PLANS
 OTHER THAN THE GAS ISOMENTRIC DIAGRAM. SHOW THE TOTAL
 BTU/H OF ALL GAS APPLIANCES IN THE BOILER ROOM (SEE
 COMMENT #58 REGARDING SIZE OF BOILER), SIZE AND
 LOCATION OF VENTING, AMOUNT OF COMBUSTION AIR REQUIRED,
 METHOD USED TO CALCULATE COMBUSTION AIR (FBC,FG 304.6)
 AND FREE AREA ASSOCIATED WITH ALL LOUVERS AND GRILLS
 USED FOR COMBUSTION AIR (FBC,FG 304.10).
  
 35. M2.7.1 AND 2.7.2: VERIFY THAT OARTU'S HAVE
 SUFFICIENT CLEARANCE FOR SERVICE AND VENTILATION
 RELATED TO POTENTIAL OBSTRUCTIONS SUCH AS MANSARD ROOF
 STRUCTURES AND MECHANICAL SCREEN WALLS. FBC,M 306.1
  
 36. M4.1 - 4.3: SEVERAL EXHAUST DUCTS ARE MISSING
 SIZES. PLEASE CORRECT.
  
 37. M4.1: UNIT C3A, SHOW CFM AND GRILL SIZE FOR SUPPLY
 DROP IN MASTER BATHROOM.
  
 38. M4.1 - 4.3: SOME SUPPLY FLEX DROPS ARE MISSING
 INFORMATION SUCH AS DUCT SIZE, CFM AND GRILL SIZE.
 PLEASE PROVIDE ALL MISSING INFORMATION ON APARTMENT
 FLOOR PLANS. IF A SUPPLY DROP CFM FALLS OUTSIDE THE CFM
 RANGE OF THE FLEX DUCT SCHEDULE AS SHOWN ON M6.1,
 EITHER REVISE THE SCHEDULE TO SHOW THE SIZE TO BE USED
 OR SHOW ALL DUCT SIZES ON FLOOR PLANS. SHOWING ALL FLEX
 DUCT SIZES ON FLOOR PLANS WOULD BE BENEFICIAL DURING
 THE INSPECTION PROCESS.
  
 39. M4.1 - 4.3: SEVERAL BRANCH AND TRANSFER RECTANGULAR
 DUCTS ARE MISSING SIZES FOR SUPPLY AND RETURN. PLEASE
 PROVIDE ALL MISSING INFORMATION. FBC 106.1.1 AND FBC
 106.3.5.1.4
  
 40. M4.1 - 4.3: SOME R/A TRANSFER DUCTS, ESPECIALLY IN
 THE MASTER SUITES ARE NOT DESIGNED TO MEET THE BALANCED
 RETURN EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS AND
 JUMPERS ARE NOT DESIGNED TO MEET THESE EXCEPTIONS, A
 FIELD TEST WILL BE REQUIRED AAT FINAL INSPECTION TO
 VERIFY PRESSURE DIFFERENTIALS ACROSS CLOSED BEDROOM
 DOORS DO NOT EXCEED 0.01" W.C. IN ACCORDANCE WITH THIS
 SECTION.
  
 41. M4.1, 4.2, 5.1: BATH AND DRYER EXHAUST DUCTS WHICH
 ENTER A SHAFT AND UTILIZE A SUBDUCT SYSTEM ARE EXEMPT
 FROM FIRE DAMPERS UNDER THE EXCEPTIONS LISTED IN FBC,M
 607.5.5.1. HOWEVER, THEY ARE NOT EXEMPT FROM SMOKE
 DAMPERS WHICH ARE REQUIRED BY THIS SECTION. NOTE: SMOKE
 DAMPERS SHALL NOT BE INSTALLED IN CLOTHES DRYER EXHAUST
 DUCTS PER FBC,M 504.2. ALSO, AN INLINE BACKDRAFT DAMPER
 IS ALSO PROHIBITED UNDER THIS SECTION. SEE ALSO
 COMMENTS # 14 AND 15.
  
 42. M4.1, 4.2, 5.1: BATH EXHAUST SUBDUCT SYSTEM
 REQUIRES A CONTINUOUS AIRFLOW UPWARD TO THE OUTSIDE IF
 THE FIRE DAMPER EXCEPTION IS TO BE CLAIMED UNDER FBC,M
 607.5.5.1 (1.1). THIS WOULD REQUIRE A FAN ON THE ROOF
 ABOVE THE SUBDUCT SYSTEM WHICH WOUDL RUN CONTINUOUSLY,
 EVEN UNDER EMERGENCY CONDITIONS.
  
 43. M4.1: NO DRYER EXHAUST DUCT IS SHOWN IN UNIT C2.
 SHOW MEANS OF DRYER EXHAUST PER FBC,M 504.6.2. ALSO, SE
 COMMENT #41.
  
 44. M4.1 AND 4.2: MECHANICAL FLOOR PLANS SHOW RETURNS
 DUCTED TO A/C CLOSETS WHICH ARE BEING USED AS PLENUMS
 (WITH SOLID DOORS). FLOOR PLAN ON A-803 SHOWS A/C
 CLOSETS WITH 7'8" CEILINGS, WHICH WOULD NOT ALLOW FOR
 THE DUCTED RETURN TO GET BACK TO THE A/C UNIT, AND
 BIFOLD DOORS. IS THE R/A TO BE DUCTED TO THE CLOSET OR
 THROUGH BIFOLD LOVER DOORS? MECHANICAL AND
 ARCHITECTURAL PLANS ARE IN CONFLICT. PLEASE CLARIFY.
 NOTE: SEE COMMENT #24 REGARDING A/C CLOSET DOORS.
  
 45. M4.3: TH1 PLAN SHOWS A 12X8 SUPPLY RISER DUCT IN
 THE MIDDLE OF A WALL. PLEASE CLARIFY.
  
 46. M4.3: TH1 FLOOR PLAN SHOWS A/C UNIT IN THE SAME
 LOCATION WHERE PG A-801 SHOWS THE CLOTHES DRYER. DRYER
 EXHAUST DUCT IS SHOWN AT THE AHU CLOSET. COORDINATE
 DRAWINGS AND FLOOR PLANS TO SHOW CODE COMPLIANCE.
  
 47. M4.3: TH2, NONE OF THE SUPPLY OR RETURN DUCT IS
 ACTUALLY ROUTED TO THE A/C CLOSET OR THE A/C UNIT.
 PLEASE CORRECT.
  
 48. M4.4: IF LOWER AND UPPER LOBBY AREAS ARE DEEMED TO
 BE AN ATRIUM RATHER THAN A MEZZANINE DURING BUILDING
 PLAN REVIEW, SMOKE CONTROL SHALL BE REQUIRED PER FBC
 SEC. 404.
  
 49. M4.4: UPPER FLOOR PLAN SHOWS SUPPLY RISER DUCT SIZE
 AS 14X10, BUT LOWER FLOOR PLAN SHOWS THE SAME DUCT AS
 14X12. PLEASE COORDINATE. ALSO, MECHANICAL FLOOR PLAN
 SHOWS THE SUPPLY RISER GOING DOWN THROUGH THE CORNER OF
 A CONCRETE BLOCK WALL TO THE FIRST FLOOR. THE FLOOR
 PLAN OR A-301 SHOWS A CHASE IN THE A/C CLOSET (PROBABLY
 FOR A/C DUCT) AND THE DOOR TO THE A/C CLOSET IS SHOWN
 WHERE THE RETURN WALL GRILL IS LOCATED. PLEASE
 COORDINATE PLANS. IS THERE ANY FIRE OR SMOKE BARRIER
 PROTECTION REQUIRED IN THIS AREA?
  
 50. M4.4: WHAT IS THE PURPOSE OF THE ACCESS PANELS IN
 THE 2-HOUR RATED ENCLOSURES? IF THIS IS THE LOCATION OF
 SUPPLY FANS, PLEASE SHOW THE FANS ON THE PLANS. FBC
 106.1.1 AND FBC 106.3.5.1.4
  
 51. M4.4: EF-1 IN TOILET ROOM 124 SHALL BE INTERLOCKED
 TO RUN WITH HP-6 TO ENSURE ALL AIR SUPPLIED TO THAT
 SPACE IS EXHAUSTED IN ACCORDANCE WITH FBC,M 403.2.1(3).
 PROVISIONS SHALL ALSO BE MADE TO ASSURE THAT BOTH THE
 HP AND THE EF ARE RUNNING WHENEVER THE SPACE IS
 OCCUPIED IN ACCORDANCE WITH FBC,M 401.3 (UNLESS BOTH
 ARE SET TO RUN CONTINUOUS).
  
 52. M5.1: PLAN SHOWS ROOF CURBS FOR RTU 1 AND 2 USED
 FOR SUPPLY DUCT. IF SO, CURBS SHALL BE LINED WITH MIN.
 R-8, UL-181 APPROVED DUCT MATERIAL IN ACCORDANCE WITH
 FBC TABLE 13-410.1.ABC.2.2 AND FBC,M 604.13. IF THIS IS
 A LISTED SYSTEM, PROVIDE SUBMITTAL.
  
 53. M5.1: ALL DUCT PENETRATIONS OF SHAFT FOR RTU 1 AND
 2 SHALL BE PROTECTED BY FIRE AND SMOKE DAMPERS PER
 FBC,M 607.5.5.1. SEE COMMENTS 20 AND 22.
  
 54. M5.1: TOILET EXHAUST RISER PENETRATIONS REQUIRE
 SMOKE DAMPERS AND ROOFTOP EXHAUST FANS TO RUN
 CONTINUOUS UNDER ALL CONDITIONS PER FBC,M 607.5.5.1.
 SEE COMMENT #42.
  
 55. M5.1: DRYER EXHAUST RISERS ARE NOT EXEMPT FROM
 SMOKE DAMPER REQUIREMENTS. SEE COMMENT #41.
  
 56. M5.2: COORDINATE PIPE SIZES WITH THOSE SHOWN ON
 ROOF PLAN. ALSO, SHOW ALL PIPE SIZES, INCLUDING
 BRANCHES FOR HP'S 5,6,13,14.
  
 57. M5.3: COORDINATE PIPE SIZES WITH THOSE SHOWN ON
 ROOF PLAN. ALSO, SHOW ALL PIPE SIZES, INCLUDING
 BRANCHES FOR HP'S 10,11,12.
  
 58. M5.3: DIAGRAM ON THIS PAGE SHOWS AC BOILER TO BE
 600,000 BTU/H BUT PLUMBING PLAN SHOWS THE BOILER AT
 200,000 BTU/H. PLEASE CLARIFY. PROVIDE SUBMITTAL FOR
 THE BOILER AND ALL EQUIPMENT SHOWN ON THIS PAGE. FBC
 106.1.2.
  
 59. M6.1: EF-3, 4 POOL TOILET AND POOL EQUIPMENT ROOMS
 COULD NOT BE LOCATED ON MECHANICAL PLANS. PROVIDE
 MISSING INFORMATION. FBC 106.1.1
  
 60. M6.1: SHOW LOCATION OF EF-7 AND FIRE PUMP ROOM ON
 PLANS. ELECTRICAL PLAN INDICATES FIRE PUMPS ARE DIESEL
 OPERATED. PROVIDE INFORMATION ON FUEL STORAGE MEANS,
 LOCATION AND QUANTITIES AS WELL AS LOCATION AND DETAILS
 OF ALL FUEL DELIVERY AND REFUELING LINES. PROVIDE
 SUBMITTALS FOR ALL LISTED EQUIPMENT USED FOR FUEL
 STORAGE AND DELIVERY. STATIONARY COMBUSTION ENGINES
 SHALL COMPLY WITH NFPA 37-02 AND FUEL STORAGE SHALL
 COMPLY WITH NFPA 30-00.
  
 61. M6.1: RTU-1 ON FLOOR PLANS CALLS FOR A TOTAL OF
 6920 CFM. EQUIPMENT SCHEDULE SHOWS 8500 CFM. WHICH IS
 CORRECT? RTU-2, TOO MUCH INFORMATION IS MISSING TO
 DETERMINE TOTAL CFM ON FLOOR PLANS.
  
 62. M6.1: HEAT PUMPS, NOTE INDICATES HONEYWELL "T-87"
 THERMOSTAT. THIS TYPE OF THERMOSTAT IS NOT PROGRAMMABLE
 AS CALLED FOR ON PG M0.2 AUTOMATIC TEMPERATURE CONTROLS
 NOTE (A). THERMOSTATS SHALL COMPLY WITH FBC
 13-407.1.ABC.2.4.1.
  
 63. M6.1: WATER SOURCE HEAT PUMPS SHALL HAVE
 TWO-POSITION AUTOMATIC VALVES INTERLOCKED TO SHUT OFF
 WATER FLOW WHEN THE COMPRESSOR IS OFF IN ACCORDANCE
 WITH FBC 13-411.1.ABC.1.4.
  
 64. M7.1: ROOFTOP CLEARANCE SCHEDULE, THE INCORRECT
 CODE YEAR AND CODE SECTION ARE REFERENCED. THE CORRECT
 YEAR/SECTION ARE AS FOLLOWS: FBC 2004 TABLE 1509.7.
  
 65. M7.1: INSULATED DUCT THRU ROOF DETAIL, THIS DETAIL
 DOES NOT MAKE SENSE AS THE NOTES POINT TO STRUCTURAL
 STEEL COMPONENTS WHERE NONE EXIST. THE DETAIL ALSO
 INDICATES PENETRATION OF AN EXISTING ROOF DECK. THIS IS
 NEW CONSTRUCTION. NOTHING IS EXISTING. ALSO, IF
 FLASHING AND DUCT ARE TO BE WELDED, PLEASE PROVIDE
 ADDDITIONAL INFO, SUCH AS METHOD OF WELDING AND
 REQUIRED THICKNESS OF SHEET METAL FOR EACH.
  
 66. M7.1: CLOSED CIRCUIT COOLER DETAIL, WHERE VIBRATION
 ISOLATION IS EMPLOYED, AN APPROVED MEANS OF
 SUPPLEMENTAL RESTRAINT SHALL BE USED TO ACCOMPLISH
 SUPPORT AND RESTRAINT IN ACCORDANCE WITH FBC,M 301.10.
 ALSO, SHOW COMPLIANCE WITH FBC,M 301.13 FOR WIND
 RESISTANCE.
  
 67. M7.1: HEAT PUMP DETAIL, THERE IS ANOTHER DETAIL FOR
 THIS SAME INSTALLATION ON M7.3, BUT THE DETAILS DO NOT
 MATCH. PLEASE CHOOSE ONE METHOD AND REMOVE THE OTHER
 FROM PLANS TO AVOID CONFLICT. FBC 106.1.1.
  
 68. M7.2: DUCT SUPPORT DETAIL, THERE IS ANOTHER DETAIL
 FOR THIS SAME INSTALLATION ON M7.3, BUT THE DETAILS DO
 NOT MATCH. PLEASE CHOOSE ONE METHOD AND REMOVE THE
 OTHER FROM PLANS TO AVOID CONFLICT. FBC 106.1.1. NOTE:
 COMPLIANCE WITH FBC,M 301.13 AND FBC TABLE 1509.7 IS
 REQUIRED.
  
 69. M7.3: SHOW HOW AIR SEPARATOR AND EXPANSION TANK ARE
 TO BE SECURED TO STRUCTURE IN A MANNER THAT MEETS WIND
 LOAD REQUIREMENTS OF FBC,M 301.13 AND FBC CH.16.
  
 70. M7.2 AND 7.3: FIRE DAMPERS, SMOKE DAMPERS AND
 COMBINATION FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS PER FBC,M 607.2. WHERE
 CONFLICTS BETWEEN DETAIL ON PLANS AND MANUFACTURER'S
 INSTRUCTIONS OCCUR, THE MANUFACTURER'S INSTRUCTIONS
 SHALL GOVERN.
  
 71. M7.3:THERE ARE TWO DETAILS FOR VERTICAL PIPE FLOOR
 PENETRATIONS ON THIS PAGE. WHICH IS TO BE USED? PROVIDE
 MANUFACTURER AND LISTING FOR ALL THROUGH-PENETRATION
 FIRESTOP SYSTEMS TO BE USED AT RATED ASSEMBLIES.
  
 72. M7.3: GARAGE EF MOUNTING DETAIL DOES NOT SHOW HOW
 FANS, SLEEVES OR SOUND ATTENUATION BOXES ARE TO BE
 SECURED TO STRUCTURE. PROVIDE SUFFICIENT DETAIL AND
 EQUIPMENT SUBMITTALS.
  
 73. M7.3: VERTICAL HP DETAIL, SHOW MEANS OF AUXILIARY
 DRAIN PROTECTION PER FBC,M 307.2.3.
  
 74. M7.4: RISER TERMINATION DAMPER, SEE COMMENTS 14 AND
 15. ALSO, IF FIRE DAMPER IS TO BE USED IN THIS MANNER,
 PROVIDE CORRESPONDING RUSKIN INSTALLATION INSTRUCTIONS
 TO DETERMINE VIABILITY OF THIS UNORTHODOX APPLICATION.
 FBC 106.1.2 AND FBC,M 607.2.
  
 75. M7.4: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO
 THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 76. M7.3: ROOF MOUNTED EF DETAIL HAS A NOTE FOR
 STRUCTURAL ENGINEER TO DETERMINE AND VERIFY ATTACHMENT
 DETAILS FOR REQUIRED WIND LOADS. NO SUCH INFORMATION
 COULD BE FOUND IN STRUCTURAL PLANS. FBC 301.13
  
 77. PROVIDE SUBMITTALS FOR ALL LISTED MECHANICAL
 EQUIPMENT, APPLIANCES AND DEVICES TO BE USED IN THIS
 PROJECT. FBC 106.1.2
  
 ENERGY:
  
 78. OUTDOOR AIR QUANTITIES SHOWN ON SIZING SUMMARY DO
 NOT MATCH THOSE GIVEN ON PG M0.1. THESE VALUES SHOULD
 CORRESPOND. EXAMPLE: EXERCISE ROOM ON SCHEDULE CALLS
 FOR 240 CFM O.A. WHILE THE SUMMARY SHOWS 120 CFM O.A.
  
 79. COIL SIZING/ COOLING CAPACITY SHOWN ON SIZING
 SUMMARY DO NOT MATCH THOSE GIVEN ON PG M6.1. EXAMPLE:
 APT C1 ON SCHEDULE SHOWS 2.5 TONS OR 29.92 MBH AND APT
 C1 ON SUMMARY SHOWS 1.9 TONS OR 23.3 MBH. HVAC SYSTEMS
 AND EQUIPMENT SHALL BE SIZED TO PROVIDE NO MORE THAN
 THE SPACE AND SYSTEM LOADS CALCULATED IN ACCORDANCE
 WITH FBC 13-407.1.ABC.1.
  
 80. SYSTEM REPORT COMPLIANCE: SYSTEM SIZES AS SHOWN ON
 REPORT DO NOT CORRESPOND WITH SYSTEMS IN THE SYSTEM
 SIZING SUMMARY. GROUPING OF SYSTEMS WILL INCREASE THE
 SIZE OF THE SYSTEM IN THE REPORT WILL DISTORT THE
 ALLOWED EFFICIENCY CRITERIA WHICH WOULD PROVIDE UNDUE
 TRADE-OFF CREDIT FOR EFFICIENCY OF THE COOLING SYSTEMS.
 EXAMPLE: SYSTEM 1 IS LISTED FOR ALL TOWNHOMES AS ONE
 "WATER COOLED >240,000 BTU/H" UNIT. THE TOWNHOMES ARE
 EACH COOLED BY INDIVIDUAL UNITS AND WOULD BE
 CATEGORIZED AS "WATER COOLED 17,000 17,000 TO <135,000
 BTU/H" IN ACCORDANCE WITH FBC TABLE 13-407.1.ABC.3.2B.
 THIS TABLE GIVES A MINIMUM EFFICIENCY CRITERIA OF 12.00
 EER. "SYSTEMS" SHOULD CORRESPOND WITH "ZONES" IN THE
 INPUT DATA REPORT. FOR GUIDANCE AS TO WHAT ACTUALLY
 CONSTITUTES A ZONE, PLEASE SEE FBC 13-407.1.ABC.2.2.1.
  
 81. INPUT DATA REPORT: BUILDING ENVELOPE COMPONENTS AS
 SHOWN ON THE INPUT DATE REPORT DO NOT CORRESPOND WITH
 THE TYPE OF CONSTRUCTION SHOWN ON PLANS. EXAMPLE:
 REPORT SHOWS THE ROOF TO BE INSULATED WITH R-19 BATTS.
 DETAILS ON A-652 INDICATE THE ROOF INSULATED WITH RIGID
 BOARD TO A VALUE OF R-14 IN A BUILT-UP ROOF SYSTEM.
 ALSO, NO INFORMATION COULD BE FOUND REGARDING TYPE OR
 R-VALUE OF INSULATION TO BE USED IN THE MANSARD ROOF
 SECTIONS WHICH ARE ABOVE CONDITIONED SPACES. NO
 INFORMATION COULD BE FOUND IN ARCHITECTURAL PLANS OR
 DETAILS SHOWING 1.36" INSULATION AT EXTERIOR WALLS AS
 INDICATED ON THE REPORT. PLEASE CLARIFY ON PLANS AND
 PROVIDE CORRESPONDING INFORMATION ON CALCULATIONS.
  
 82. WHAT IS THE R-VALUE OF THE 3RD FLOOR FLOOR/CEILING
 ASSEMBLY BETWEEN THE PARKING GARAGE AND THE 3RD FLOOR
 APARTMENTS? THIS INFORMATION IS NOT SHOWN ON PLANS OR
 IN THE REPORT. ALSO, PLEASE EXPLAIN HOW AN 8"
 LIGHTWEIGHT CONCRETE BLOCK WITH 1.36" INSULATION SYSTEM
 IS TO BE USED FOR THE FLOOR IN THE LOBBY AS INDICATED
 IN THE REPORT.
  
 83. STAIR AND ELEVATOR SHAFT VENTS SHALL BE EQUIPPED
 WITH MOTORIZED DAMPERS THAT ARE CAPABLE OF BEING
 AUTOMATICALLY CLOSED DURING NORMAL BUILDING OPERATION
 AND ARE INTERLOCKED TO OPEN AS REQUIRED BY FIRE AND
 SMOKE DETECTION SYSTEMS. FBC 13-409.1.ABC.3.1
  
 84. MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT
 BUILDINGS ARE PRESSURIZED WITH RESPECT TO OUTDOORS.
 PROVIDE AIR BALANCE SCHEDULE(S) SHOWING COMPLIANCE FOR
 ALL ZONES/FLOORS. FBC 13-409.1.ABC.2
  
 85. SHOW SHUTOFF DAMPER CONTROLS FOR O.A. SUPPLY AND
 EXHAUST SYSTEMS AS REQUIRED BY FBC 13-409.1.ABC.3.3.
  
 86. ENERGY CALCULATIONS SHOW A "PLANT" CHILLER AT 390
 TONS. THERE IS NO CHILLER SHOWN AS PART OF THIS SYSTEM.
 ALSO, THE CLOSED CIRCUIT COOLERS AND A/C BOILER WERE
 OMITTED FROM THE CALCULATIONS. PLEASE CORRECT AND
 RESUBMIT.
  