Plan Review Notes
Plan Review Notes For Permit 07080073
Permit Number 07080073
Review Stop G
Sequence Number 1
Notes
Date Text
2007-11-29 15:01:25DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P6.1.5 A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - INDICATE ALL CUT SECTIONS DOWNSTREAM
 OF THE REGULATOR FOR THE GAS WATER HEATERS. FINAL DROP
 LENGTH NOT SHOWN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. - SIZE OF PIPE
 SHOWS 1-1/4" REDUCING TO 1" THEN BACK TO 1-1/4". PLEASE
 CLARIFY.--ALSO SHOW THE MATERIAL TYPE OF THE
 VENTING FROM THE REGULATORS. (MATERIAL SHALL BE NON
 COMBUSTABLE).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - ALSO SHOW THE TOTAL
 DISTANCE FROM THE REGULATOR TO THE MOST REMOTE OUTLET
 DOWNSTREAM OF THE REGULATOR FOR THE GAS WATER HEATERS.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLEASE SUBMIT AN
 APPROVED TABLE FOR 7"W.C. OR INDICATE 1/2PSI DOWNSTREAM
 OF THE REGULATOR. FBC-2004 FUEL GAS HAS NO 7" W.C.
 TABLES TO VERIFY PIPE SIZES.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE GAS
 REGULATORS. INDICATE MODEL NUMBER FOR EACH REGULATOR.
 --A UNION IS REQUIRED NEXT TO THE REGULATOR NOT AT
 THE END OF A RUN. (SEE GAS WATER HEATERS & HVAC SYSTEM
 REGULATORS).
  