| 2007-10-31 19:27:25 | *****DENIED***** |
| | |
| | PLEASE BE ADVISED THAT THIS BUILDING AND/OR PHASE SHALL |
| | STAND UPON ITS OWN MERITS ( I.E. WATER SUPPLY, FIRE |
| | ALARM SYSTEM, FIRE SPRINKLER SYSTEM). |
| | |
| | 01.FIRE HYDRANTS TO BE OPERATIONAL BEFORE, DURING, |
| | AND AFTER CONSTRUCTION. |
| | |
| | 02.A TEMPORARY STANDPIPE IS REQUIRED WHEN THE |
| | BUILDING REACHES THREE STORIES OR THIRTY FEET IN |
| | HEIGHT. |
| | |
| | 03.THE CONSTRUCTION AND PROTECTION OF OF THE |
| | STRUCTURE'S PARKING GARAGE AS WELL AS THE CONTROL OF |
| | HAZARDS SHALL COMPLY WITH NFPA 88A. |
| | |
| | 04.WHAT IS THE VERTICAL CLEARANCE AT THE POINT OF |
| | VEHICLE ENTRY? |
| | |
| | 05.BASED UPON NFPA 72 - 2002 EDITION - EXPLAIN |
| | CRITERIA FOR THE USE OF THE CEILING MOUNTED FIRE ALARM |
| | HORN/STROBE COMBO DEVICE IN THE PARKING GARAGE AS SHOWN |
| | ON A-251 AND A-252 SHEETS. |
| | |
| | 06.WHAT IS THE EXIT AISLE CLEARANCE BETWEEN THE |
| | EXTERIOR REAR WALL OF THE CONDO UNITS AND THE VEHICLE |
| | PARKING SPACES?BE ADVISED THAT DURING ITS SWING, ANY |
| | DOOR IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN |
| | ONE-HALF THE WIDTH OF THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, OR PASSAGEWAY. |
| | |
| | 07.ON SHEET A-251, IT APPEARS THAT THE SWING OF THE |
| | DOOR IS AGAINST THE PATH OF EGRESS IN STAIR #2 AND |
| | STAIR #4. |
| | |
| | 08.PLEASE EXPLAIN EXIT LIGHTS SHOWN IN THE CONDO |
| | UNITS AT GRADE LEVEL.THESE LIGHTS ARE SHOWN ON SHEET |
| | A-251 BUT NOT SHOWN ON SHEET A-350.THE MEANS OF |
| | EGRESS SHALL NOT BE FROM AN AREA TO A MORE HAZARDOUS |
| | AREA (PARKING GARAGE). |
| | |
| | 09.IN THE LIFE SAFETY SHEETS, CLARIFY THE USE OF |
| | SMOKE DETECTORS OR SMOKE ALARMS IN THE CONDO UNITS.BE |
| | ADVISED THAT SMOKE DETECTORS ARE TIED INTO THE |
| | BUILDING'S FIRE ALARM SYSTEM, WHEREAS SMOKE ALARMS |
| | ALERT THE OCCUPANTS OF THE DWELLING UNIT ONLY. |
| | |
| | 10.ON SHEETS A-251 AND A-252,SOME PATHS OF EGRESS |
| | ARE ILLUSTRATED PASSING THRU PARKING SPACES AND OTHER |
| | CHANGES IN ELEVATION. |
| | |
| | 11.POST/DISPLAY THE NUMERICAL ADDRESS ON THE |
| | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS SAMANTHA |
| | LANE.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL |
| | BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| | STROKE. |
| | |
| | 12.PROVIDE FLAME SPREAD DETAILS ON ALL FABRIC |
| | CANOPIES PLANNED FOR USE. |
| | |
| | 13.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE ALUMINUM |
| | RAILINGS. |
| | |
| | 14. ELEVATORS SHALL BE PROVIDED WITH FIRE FIGHTER |
| | SERVICE IN ACCORDANCE WITH ASMEA17.1 |
| | |
| | 15.WARNING SIGNS (DO NOT USE IN THE EVENT OF A FIRE) |
| | SHALL BE REQUIRED IN THE ELEVATOR LOBBIES. |
| | |
| | 16.STAIRWELL IDENTIFICATION SIGNS REQUIRED.THE |
| | SIGNAGE SHALL IDENTIFY FLOOR LEVEL, STAIR NUMBER, AND |
| | TERMINUS TOP AND BOTTOM. |
| | |
| | 17.FIRE DOORS AND FIRE WINDOWS SHALL COMPLY WITH NFPA |
| | 80. |
| | |
| | 18.ON SHEET A-901 (IN REFERENCE TO DOOR REMARK #2), |
| | HOW IS RE-ENTRY ACCOMPLISHED DURING NORMAL OPERATION. |
| | |
| | 19.ON SHEET FA2.1.2, NO FIRE ALARM DEVICE IS SHOWN IN |
| | THE TRANSFORMER ROOM.PROVIDE CRITERIA THAT THIS |
| | ARRANGEMENT IS ACEPTABLE AS PER NFPA 72 - 2002 |
| | EDITION. |
| | |
| | 20.PLEASE EXPLAIN THE LACK OF SMOKE DETECTORS/SMOKE |
| | ALARMS IN THE RETAIL TENANT SPACES. |
| | |
| | 21.ON SHEET FS0.1 IN GENERAL NOTE # 1 AND # 12,THE |
| | 2003 EDITION OF NFPA 20 SHALL BE REFERENCED (NOT |
| | 1999). |
| | |
| | 22.ON SHEET FS4.1.1 THRU FS4.1.3, THE WORDING UNDER |
| | THE LAYOUTS AND THE LAYOUTS ARE GARBLED AND UNCLEAR AS |
| | TO INTENT. |
| | |
| | 23.SHOW THE LOCATION OF THE KNOX BOX (USUALLY AT THE |
| | MAIN ENTRANCE AREA). |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |