| 2007-09-15 21:32:43 | 2007-09-15 21:32:43 |
| | |
| | ** DENIED ** |
| | |
| | LAKES AT PALM BEACH/ AKA MIZNER LAKES ON SOME SHEETS. |
| | BUILDING #5. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2003 NFPA-20 |
| | ** SOME OF THE ABOVE ARE REFERENCED ON PLANS HOWEVER |
| | MOST REFERENCE PREVIOUS CODES WHICH ARE NO LONGER IN |
| | EFFECT. |
| | PLEASE SEE THAT ALL SHEETS CONTAIN THE RELEVANT CODES |
| | FOR DESIGN E, FA, FP ETC. |
| | FBC 106.1.2, 106.1.3, 110.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THE DATE ON THE PLANS IN WHICH THE |
| | ENGINEERED SIGNED PLANS IS DATED BEFORE THEY WERE |
| | ISSUED. HOW IS THIS POSSIBLE? |
| | PLEASE SEE FLORIDA STATUTES 471.025 AS THIS REQUIRES |
| | THE DESIGN PROFESSIONAL TO SIGN AND DATE EACH SHEET |
| | WHEN SIGNING, DATING AND SEALING SAID PLANS. |
| | |
| | 3) NOTE: PLEASE SEE ELECTRICAL PLANS ARE NOT COMPLETE |
| | WITH ALL CIRCUITING, LIGHTING CONTROLS, COORDINATION |
| | WITH MANY OF THE SHEETS. PLEASE SEE MOST OF THE NOTES |
| | BELOW ADDRESS THESE HOWEVER NOT ALL. |
| | PLEASE SEE FOR EXAMPLE THAT SOME SHEETS ARE NOT |
| | COMPLETE AND SOME AREAS CAN NOT BE REVIEWED AT THIS |
| | TIME. |
| | SEE E2.1.2 COMPARED TO E3.1.2, WEST SIDE OF BUILDING IS |
| | NOT THE SAME, DOES NOT SHOW THE SAME LAYOUTS FOR POWER |
| | AND LIGHTING ETC. |
| | FBC 106.3.5.1.2 |
| | NEC 2005 |
| | |
| | 4) NOTE: PLEASE BE SURE THE LIGHTING SHOWN ON THE |
| | LANDSCAPE SHEETS CORRELATE WITH THE LIGHTING ON THE |
| | ELECTRICAL PLANS. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 5) NOTE: PLEASE SEE THE ADDRESS ON THE PERMIT |
| | APPLICATION INDICATES 715 HANK AARON DR, HOWEVER THE |
| | ASSIGNED ADDRESS FOR THIS BUILDING #5 IS 1580 SAMANTHA |
| | LN. |
| | **PLEASE KNOW THERE ARE STILL SEVERAL SHEETS IN PLANS |
| | SETS WHICH REFLECT THE PREVIOUS PROJECT NAME OF MIZNER |
| | LAKES AND SHEETS WHICH NOW REFLECT LAKES AT PALM |
| | BEACH. |
| | ** PLEASE BE SURE TO COORDINATE SHEETS. (NOT A KAMM |
| | CONSULTING COMMENT) |
| | |
| | 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED ARE IN NEED OF CORRECTIONS. |
| | PLEASE SEE THE ADDRESS AND BUILDING INFORMATION NEEDS |
| | TO MATCH WITH PLANS AND PROJECT. COVER SHEET CALLS FOR |
| | AN ADDRESS LOCATED IN MIAMI OR SOME OTHER LOCATION. |
| | PLEASE SEE THE INFORMATION ON LIGHTING NEEDS TO |
| | CORRELATE WITH PLANS. PLEASE SEE THE SUMMARY SHEETS AND |
| | THE INPUT DATA REPORT DOES NOT CONTAIN ANY *EXTERIOR |
| | LIGHTING* ENTERED. HOW IS THIS POSSIBLE WHEN THE PLANS |
| | CONTAIN DOZENS OF EXTERIOR LIGHT FIXTURES? |
| | PLEASE SEE LANDSCAPE PLANS AND ELECTRICAL PLANS WHICH |
| | INDICATE LANDSCAPE LIGHTING FIXTURES. |
| | PLEASE ALSO SEE THE INFORMATION ON THE INPUT DATA |
| | REPORT FOR THE INTERIOR LIGHTING WHICH ALSO DOES NOT |
| | MATCH WITH PLANS. PLEASE SEE THERE ARE ONLY 1 OF EACH |
| | TYPE OF FIXTURE ENTERED WHICH IS NOT POSSIBLE. PLEASE |
| | COORDINATE ALL INFORMATION ON CALCULATIONS WITH PLANS. |
| | PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.3 ETC |
| | |
| | 7) NOTE: PLEASE SEE THERE ARE A FEW AREAS ON PLANS |
| | WHICH SOME DEVICES FOR CONTROLS ON LIGHTING AS REQUIRED |
| | PER 13-415.1.ABC.1.1, .1.2 NEEDS ADDRESSING. PLEASE SEE |
| | METHODS OF CONTROLS FOR EXTERIOR LIGHTING. PLEASE SEE |
| | SOME ROOMS FOR EXAMPLE, CUSTODIAN CLOSET, WOMEN RR AND |
| | MEN RR, RESIDENT STORAGE AREAS, ON E2.3.2 NEAR THE POOL |
| | DECK ACCESS DOORS. |
| | PLEASE KNOW AREA FOR RESTROOMS NEEDS TO PROVIDE DEVICES |
| | WHICH PROVIDE COVERAGE IN ALL AREAS FOR LIFE SAFETY AND |
| | EGRESS SAFETY. |
| | PLEASE ALSO SEE RETAIL TEMPORARY SPACES LOCATED ON |
| | E2.1.1 AND 2.1.2. |
| | |
| | 8) NOTE: PLEASE SEE SHEET E2.1.2 WHICH MENTIONS TO SEE |
| | THE ELECTRICAL ROOM DETAIL ON E5.1.3 HOWEVER E5.1.3 IS |
| | THE TELEPHONE RISER SHEETS. |
| | PLEASE SEE NOTES ETC ON ARCHITECTURAL PLANS WHICH WERE |
| | NOTED UNDER BUILDING |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE PROVIDE THE INFORMATION ON PLANS FOR |
| | THE *EQUAL-POTENTIAL POOL GROUNDING GRID* AS REQUIRED |
| | PER 680.26. |
| | PLEASE KNOW EVEN THOUGH THE POOL IT SELF WILL BE UNDER |
| | SEPARATE PERMIT THE MAIN STRUCTURAL CONTENTS OF THE |
| | POOL WILL BE PART OF THE BUILDING AND WILL REQUIRE THIS |
| | GROUNDING. |
| | |
| | 10) NOTE: PLEASE KNOW THAT THE PLANS WILL BE REQUIRED |
| | TO STATE *NO DUSK TO DAWN SWIMMING*. PLEASE KNOW IF ANY |
| | AFTER DISK SWIMMING WILL TAKE PLACE THE REQUIRED |
| | MINIMUM SIGNED, DATED AND SEALED PHOTO-METRICS WILL BE |
| | REQUIRED TO BE SUBMITTED TO PALM BEACH COUNTY HEALTH |
| | DEPARTMENT FOR REVIEW AND STAMPING. THESE WOULD BE |
| | REQUIRED TO BE SUBMITTED WITH BOTH THE BASE BUILDING |
| | PLANS AND ALONG WITH THE POOL PERMIT. |
| | AS MUCH OF THE ELECTRICAL CONDUITS, LIGHTING CONDUITS |
| | AND GROUNDING OF SYSTEMS IS PART OF THE BASE BUILDING; |
| | THESE PLANS WILL BE REQUIRED TO CONTAIN MUCH OF THIS |
| | INFORMATION. |
| | FBC 106.1.2, NEC 680 |
| | |
| | 11) NOTE: PLEASE SEE SHEET A-SHEETS AND BE SURE THIS |
| | AND ANY OTHER ELECTRICAL REFLECTED ON OTHER SHEETS |
| | COORDINATE WITH THE ELECTRICAL PLANS AS SEVERAL CHANGES |
| | WILL BE MADE AND THE REFLECTED LIGHTING/CEILING PLANS |
| | ETC WILL NEED TO BE ADJUSTED. |
| | FBC 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE SEE THAT THE INFORMATION FOR THIS PUMP |
| | HOUSE ELECTRICAL FOR LIGHTING, SERVICE RECEPTACLES ETC |
| | NEEDS TO BE ADJUSTED. |
| | PLEASE SEE THE ELECTRICAL RISER AND MSB INDICATES A |
| | CIRCUIT TO *PUMP HOUSE* AND NO INFORMATION COULD BE |
| | FOUND FOR THIS. PLEASE ALSO SEE THE CONDUCTORS ARE |
| | SIZED AT 4-#4MCM? |
| | PLEASE SEE CIRCUITING ON PUMP HOUSE PLANS INDICATE A |
| | 3-POLE CIRCUIT COMING FROM A L1SA WHICH LENDS TO A |
| | SEPARATE SERVICE. PLEASE KNOW THAT ELECTRICAL EQUIPMENT |
| | IN THE FIRE PUMP LOCATION WHICH IS FROM ONE SERVICE MAY |
| | NOT CONTAIN ANY CIRCUITING FROM ANOTHER SERVICE.. |
| | PLEASE KNOW AS THIS IS A SEPARATE BUILDING PLEASE SEE |
| | 225.31-225.39, 250.32. |
| | 230.70, 230.71,408.4, 310.16, 240.4 ETC |
| | THE COORDINATION WITH BUILDING #4 AND COORDINATION OF |
| | FIRE PUMPS ELECTRICALAND FIRE MARSHAL OFFICE COMMENTS |
| | WILL ALL AFFECT THE ELECTRICAL PLANS AS SUBMITTED. 13) |
| | NOTE: PLEASE PROVIDE ALL INFORMATION ON THE FIRE PUMPS |
| | AND MINIMUM FUEL BEING PROVIDED PER NFPA-20 11.4.3. |
| | PLACING A NOTE ON THE FP SHEETS WHICH STATES THE FIRE |
| | SPRINKLER CONTRACTOR SHALL PROVIDE A *BIG ENOUGH TANK* |
| | IS NOT ACCEPTABLE IN LIEU OF PROVIDING THE MINIMUM |
| | DESIGN FOR CODE COMPLIANCE. PLEASE SEE FIRE MARSHAL |
| | REVIEW COMMENTS FOR THIS. |
| | ** PLEASE SEE ALL OF CHAPTER 11 IN NFPA-20 2003 |
| | |
| | 14) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS |
| | FOR FIRE PUMP, FIRE PUMP CONTROLLER AND FUEL |
| | TANKS.110.3, 90.7, NFPA-20 CHAPTER 10, 11 ETC. PLEASE |
| | KNOW MUCH OF THIS WILL ALSO BE REVIEWED BY THE |
| | MECHANICAL, BUILDING AND FIRE MARSHAL. |
| | **PLEASE BE SURE TO SEE ANY COMMENTS FROM FIRE MARSHAL |
| | WITH RESPECT TO BOTH BUILDINGS BEING FED FROM ONE FIRE |
| | PUMP AND LOCATION. |
| | |
| | 15) NOTE: PLEASE SEE PLANS ARE MISSING COMPLETED |
| | PHOTO-METRICS FOR ALL EGRESS PATHS UNDER NORMAL AND |
| | EMERGENCY. PLEASE KNOW AS THE GARAGE INDICATES SOME OF |
| | THE LEVELS UNDER EMERGENCY. PLEASE SEE THE GARAGE LEVEL |
| | UNDER NORMAL INDICATES ALL OF THE FIXTURES WITHOUT |
| | BATTERY BACK UP. PLEASE SEE ONLY ONE FIXTURE ON THE |
| | GARAGE PLANS FIRST FLOOR INDICATES A BATTERY BACK UP. |
| | PLEASE CORRELATE WITH EMERGENCY LIGHTING PLANS. PLEASE |
| | SEE STAIRS WHICH INDICATE SOME LEVELS, HOWEVER AS THESE |
| | NUMERIC DESIGNATIONS ARE VERY SMALL THEY ARE NOT EASILY |
| | READ. PLEASE KNOW THE LEVELS ARE REQUIRED TO BE SHOWN |
| | THAT ALL STAIR SURFACE AREAS ARE TO HAVE 10FT CANDLES |
| | MINIMUM UNDER NORMAL AND IS PERMITTED DOWN TO 1FT |
| | CANDLE UNDER EMERGENCY. |
| | FAC 61G15-33.004 |
| | NFPA-101 7.8.1.3, 7.9.2.2 |
| | |
| | 16) NOTE: PLEASE CLARIFY HOW PHOTO-METRIC LEVELS WERE |
| | SUBMITTED FOR POOL DECK AREA UNDER EMERGENCY WHEN THE |
| | FIXTURES ON PLANS DO NOT INDICATE BATTERY BACK UP? |
| | COULD NOT LOCATE THESE? |
| | PLEASE SEE SOME PHOTO-METRICS ARE SHOWN HOWEVER NORMAL |
| | LEVELS FOR STAIR AREAS DO NOT MEET THE MINIMUM UNDER |
| | THE LIFE SAFETY CODE AS SECTIONS NOTED ABOVE. PLEASE |
| | SEE E2.3.1 FOR WHAT ARE SHOWN AS NORMAL AND SEE E3.3.1 |
| | WHICH IS BLANK AND NO LEVELS ARE SHOWN. |
| | LS 101 7.8 AND 7.9 |
| | |
| | 17) NOTE: PLEASE SEE THERE ARE FIXTURE DESIGNATIONS ON |
| | PLANS WHICH DO NOT CORRELATE WITH THE LIGHTING FIXTURE |
| | LEGEND. |
| | PLEASE ALSO SEE THERE ARE EXIT LIGHTING FIXTURES |
| | MISSING IN STAIR TOWERS. PLEASE SEE SHEET E2.1.1 AND |
| | E2.1.2 AS NO EXIT LIGHTS ARE SHOWN. |
| | THESE ARE REQUIRED UNDER NORMAL AND EMERGENCY. PLEASE |
| | SEE SOME OF THESE ARE SHOWN ON THE EMERGENCY LIGHTING |
| | PLANS HOWEVER THEY ARE NOT CIRCUITED OR CONTAIN FIXTURE |
| | DESIGNATIONS. PLEASE SEE SHEET E3.1.1FOR EXAMPLE. |
| | PLEASE KNOW AS NOTED ABOVE IN NOTE #3 PLEASE COMPLETE |
| | AND COORDINATE ALL PLANS AND SHEETS. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 18) NOTE: PLEASE SEE THE FOLLOWING ROOMS WILL BE |
| | REQUIRED TO CONTAIN BATTERY BACK UP LIGHT FIXTURES OF |
| | SOME KIND. MAIN ELECTRICAL ROOM, RETAIL ELECTRICAL |
| | ROOM, TELEPHONE EQUIPMENT ROOM AND RETAIL SPACE WHICH |
| | CONTAIN FIXTURES. THE RETAIL SPACES TO HAVE A BATTERY |
| | BACK UP LIGHT FIXTURE OF SOME TYPE HAS BEEN CONFIRMED |
| | WITH THE FIRE MARSHAL'S OFFICE. |
| | PLEASE SEE 700.16, 700.12F, LS 101 7.8 AND 7.9 PLEASE |
| | BE SURE TO SEE OTHER COMMENTS FROM THIS REVIEW OR FIRE |
| | MARSHAL FOR ANY OTHER LOCATIONS. |
| | |
| | 19) NOTE: PLEASE SEE PHOTO-METRICS FOR E2.2.2WHICH |
| | DOES NOT INDICATE TABLES FOR AVERAGE LEVELS. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | SAME CODE SECTIONS AS NOTED ABOVE FOR LS. PLEASE ALSO |
| | SEE SOME OTHER SHEETS AND AREAS WHICH NEED TO GIVE THE |
| | AVERAGE ON TABLES. |
| | |
| | 20) NOTE: PLEASE SEE ELEVATOR ROOMSAND PITS SHALL |
| | CONTAIN DEDICATED CIRCUITS FOR RECEPTACLES AND LIGHTING |
| | PER 620.23 AND 620.24. |
| | PLEASE SEE AS THE PLANS ARE MISSING FOR FIRST FLOOR |
| | WEST SIDE, REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE. |
| | PLEASE SEE HOWEVER THE CIRCUIT WHICH IS NOTED FOR |
| | ROOF-TOP ROOM ACTUALLY FEEDS OUTSIDE LIGHTING AND OTHER |
| | AREAS BESIDE THIS ROOM WHICH IS NOT PERMITTED. PLEASE |
| | ADJUST ALL CIRCUITING ON PLANS. |
| | |
| | 21) NOTE: PLEASE SEE NOTE #5 ON SHEET E2.1.1 WHICH |
| | CONTAINS A NOTE FOR RATING THE J-BOX AT 500LBS? PLEASE |
| | CLARIFY THIS? WHAT TYPE OF FIXTURE/EQUIPMENT WILL BE |
| | PLACED ON THIS? |
| | FBC 106.1.2 |
| | |
| | 22) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE |
| | OPERATION OF DEVICES FOR ACCESS GATES, DOORS, AND |
| | PERSONNEL GATES. |
| | PLEASE SEE LS 101 7.2.1.5, 7.2.1.5.4, 7.2.1.6.2 ETC ** |
| | PLEASE SEE FIRE MARSHAL REVIEW COMMENTS. |
| | |
| | 23) NOTE: PLEASE CLARIFY MINIMUM LIGHTING LEVELS IN |
| | ELEVATOR PITS PER 620.24. |
| | PLEASE SEE COMMENTARY PROVIDED IN THE NEC FOR STANDARDS |
| | FROM THE ELEVATOR SAFETY CODE. |
| | PLEASE BE SURE TO CONTACT OR SEE ANY STATE ELEVATOR |
| | CODES WHICH ACTUALLY MAY BE MORE RESTRICTIVE FOR |
| | LIGHTING LEVELS. |
| | "ASME/ANSIA17.1-2004, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) |
| | AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE |
| | EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.* |
| | |
| | 24) NOTE: PLEASE PROVIDE INFORMATION FOR EMERGENCY SHUT |
| | OFF OF SPA PER 680.41. |
| | THE DEVICE AS SHOWN DOES NOT PROVIDE LOCATION AND EM |
| | SHUT OFF INFORMATION. |
| | |
| | 25) NOTE: PLEASE KNOW AS THE TIMERS AS SHOWN IN MOST |
| | ELECTRICAL ROOMS DO NOT MEET 110.26D, PLEASE PROVIDE A |
| | DIFFERENT WAY FOR CONTROLLING LIGHTING.(MULTIPLE METHOD |
| | TO ALLEVIATE A SAFETY OR HAZARDOUS CONDITION. PLEASE |
| | SEE13-415.1.ABC.1.1 EXCEPT *C*. |
| | |
| | 26) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS LOCATED |
| | IN THE ELEVATOR EQUIPMENT ROOM ABOVE THE ELEVATOR |
| | MOTORS. PLEASE KNOW AS PER INFORMATION FROM THE STATE |
| | ELEVATOR CODE, THIS AREA WILL REQUIRE ADDITIONAL |
| | LIGHTING. THIS IS NOT IN THE NEC OR LS CODE, HOWEVER IT |
| | MAY BE OF INTEREST TO PLACE ON PLANS AT THIS TIME. |
| | PLEASE VERIFY WITH THE STATE. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NO CHANGES ARE REQUIRED TO PLANS AND THIS NOTE IS FOR |
| | INFORMATIONAL PURPOSE. |
| | |
| | 27) NOTE: PLEASE PROVIDE DISCONNECT DETAILS FOR ROOF |
| | TOP EQUIPMENT FOR SELECTIVE MECHANICAL AND OTHER |
| | EQUIPMENT. |
| | PLEASE SEE MECHANICAL REVIEW COMMENTS FOR POSSIBLE |
| | LOCATIONS AND INFORMATION NEEDED. |
| | 440.11, 422.30 ETC THIS CAN BE A TYPICAL DETAIL FOR ANY |
| | EQUIPMENT WHICH IS MULTIPLE OF THE SAME USE ETC. FBC |
| | 106.1.2 |
| | |
| | 28) NOTE: PLEASE BE SURE THE PANEL SCHEDULE FOR UNITS |
| | ARE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. |
| | PLEAS SEE SECTION 408.4 AND THE FOLLOWING TEXT WHICH IS |
| | EXTRACTED DIRECTLY FROM THE NEC AND COMMENTARY. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 29) NOTE: PLEASE SEE C2L WHICH INDICATES CONDUCTORS AND |
| | CONDUIT FOR CIRCUIT #24 AS BLANK. |
| | |
| | 30) NOTE: PLEASE SEE UNIT C-5 WHICH CIRCUIT C5L-13 IS |
| | ALSO FEEDING THE MASTER BEDROOM HALL LIGHTING AND |
| | RECEPTACLE WHICH IS NOTE PERMITTED PER 210.52D, |
| | 210.11C3. |
| | |
| | 31) NOTE: PLEASE SEE UNIT C-3 WHICH IS SHOWN FOR THE |
| | BATHROOM LIGHTING CIRCUIT IN GUEST BATH ALSO FEEDING |
| | THE CIRCUIT FOR HALF BATH WHICH IS NOT PERMITTED. |
| | PLEASE SEE 210.52D, 210.11.C3. |
| | |
| | 32) NOTE: PLEASE SEE UNIT C-4 WHICH IS MISSING GFI FOR |
| | KITCHEN COUNTER SPACE PER 210.52C1 |
| | |
| | 33) NOTE: PLEASE SEE DINING AREA IN TH1 WHICH DOES NOT |
| | SEEM TO BE DEFINED AND PART OF DINING AREA SEEMS TO BE |
| | ON LIVING ROOM CIRCUIT. |
| | PLEASE BE SURE TO CIRCUIT PER 210.52B1, 210.11C1, |
| | 220.53 |
| | |
| | 34) NOTE: PLEASE SEE UNIT TH2 WHICH IS MISSING |
| | RECEPTACLES REQUIRED FOR WALL SPACE PER 210.52. THIS IS |
| | THE RAIL AREA ON SECOND FLOOR WHICH PER NEC IS |
| | CONSIDERED WALL SPACE. THIS WAS DONE ON BUILDING #4. |
| | |
| | 35) NOTE: PLEASE SEE THE DINING AREA IN UNIT TH2 AS |
| | THIS AREA CONTAINS RECEPTACLES CIRCUITED TO THE LIVING |
| | ROOM/OTHER AREAS. |
| | PLEASE SEE 210.52B1, 210.11C1. |
| | |
| | 36) NOTE:PLEASE SEE NFPA-72FOR DEFINITIONS OF SMOKE |
| | DETECTION DEVICES. |
| | PLANS INDICATE ALL DEVICES IN UNITS AS *SMOKE |
| | DETECTORS* AND NOT * SMOKE ALARMS*. |
| | PLEASE KNOW IF THESE ARE DEVICES WHICH DETECT AND SOUND |
| | AN ALARM. |
| | PLEASE ADJUST PLANS. |
| | PLEASE ALSO BE SURE ALL SMOKE ALARMS ARE MOUNTED ON |
| | WALL LEADING TO THE FLOOR ABOVE. A NOTE IS LOCATED FOR |
| | THIS HOWEVER THE NOTE COULD ALSO BE READ TO MOUNT THIS |
| | UNIT ON WALL ON THE UPPER LEVEL. |
| | PLEASE ADJUST NOTE. |
| | NFPA-7211.5.1.1, 11.8.3 |
| | |
| | 38) NOTE: PLEASE SEE MAIN #4 WHICH IS SHOWN AS 1600AMPS |
| | YET THE RISER ONLY INDICATES ONE RUN OF 500MCM WHICH IS |
| | ONLY RATED FOR 380AMPS. |
| | PLEASE SEE THIS IS THE SAME FOR THE FEEDER/SERVICE |
| | CONDUCTOR LEGEND AND FS DESIGNATIONS. |
| | PLEASE SEE 240.4B FOR DEVICES RATED OVER 800AMPS. |
| | 110.14, 310.16 |
| | |
| | 39) NOTE: PLEASE CLARIFY AND COORDINATE THE FS-1 AND |
| | FS-6 ON RISER. |
| | THE RISER SHOWS FS-1 BEING STUBBED UP IN MAIN |
| | ELECTRICAL ROOM, HOWEVER THE MAIN ELECTRICAL ROOM |
| | LAYOUT ON E5.1.4 INDICATES THIS AS FS-6? |
| | PLEASE ALSO SEE THE RISER SHOWS FS-6 WHICH SEEM TO BE |
| | OUTSIDE OR AT ANOTHER LOCATION FOR STUB UP. |
| | PLEASE SEE ANY FUTURE SERVICES WILL BE REVIEWED PER AHJ |
| | AND IN EITHER AS SHOWN ON THE RISER, FS-6 DOES NOT |
| | APPEAR TO STUB UP IN ROOM, ONLY WHAT E5.1.4 SHOWS. |
| | PLEASE CORRELATE AND COMPLETE SHOWING FS-1 ON FLOOR |
| | LAYOUT ALSO. |
| | FBC 106.3.5.1.2 |
| | NEC 230.72, 230.70, 90.4 |
| | |
| | 40) NOTE: PLEASE SUBMIT WORST CASE VOLTAGE DROP |
| | CALCULATIONS FOR FEEDER(S) AND BRANCH CIRCUIT(S) PER |
| | 13-413.1ABC.1 |
| | |
| | 41) NOTE: PLEASE SEE 422.13 AS LOADS FOR WATER HEATERS |
| | ARE NOW REQUIRED TO BE FIGURED INTO LOAD CALCULATIONS |
| | AT 125% FOR CONTINUOUS LOADS. |
| | THIS CHANGED IN THE 2005 NEC. |
| | |
| | 42) NOTE: PLEASE BE SURE THE ARCHITECT AND STRUCTURAL |
| | ENGINEER OBTAINS THE BUS-WAY/DUCT CURBING DETAIL AND |
| | PLACES ON THEIR RESPECTIVE SHEETS. |
| | THIS AHJ HAS HAD SEVERAL NOT INSTALLED AND CONSTRUCTED |
| | CORRECTLY AS THE DETAIL WAS NOT ON THE A AND S SHEETS |
| | FOR THE BUILDING CONTRACTOR. |
| | THIS IS NOT AN ITEM TO CONSTRUCT AFTER INSTALLATION OF |
| | BUS-WAY. |
| | 106.1.2 |
| | |
| | 43) NOTE: PLEASE SEE THE GUTTER ON E5.1.5 DOES NOT |
| | COORDINATE WITH THE GUTTER ON THE ELECTRICAL RISER. |
| | PLEASE VERIFY SIZE AS THE CONDUCTORS ON RISER WERE NOT |
| | SHOWN FOR 1600AMPS AND THE SIZE OF THE GUTTER CAN NOT |
| | BE CONFIRMED AT THIS TIME. |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND NEC 366 |
| | FOR SIZING. |
| | |
| | 44) NOTE:PLEASE PROVIDE INFORMATION ON MAINS FOR MSB, |
| | SBA, MDR AND MC1A. PLEASE VERIFY MANUAL MEANS OF |
| | DISCONNECT RATED FOR THE LOAD SERVED PER 230.76, |
| | 230.79 |
| | ** PLEASE ALSO SEE THE LOAD SUMMARY FOR MSB SEEMS TO BE |
| | LABELED MSB-1. THIS SEEMS TO BE THE SAME, BUT ONLY |
| | LABELED DIFFERENT. (TYPE-O) |
| | |
| | 45) NOTE: PLEASE SEE RISER IS INDICATING 105 UNITS. |
| | PLEASE BE SURE TO COORDINATE WITH ALL OTHER SHEETS AND |
| | OTHER TRADES. |
| | PLEASE CORRELATE AND ADJUST ALL PLANS AS NEEDED. FBC |
| | 106.3.5.1.2 |
| | |
| | 46) NOTE: PLEASE SEE MC 1,3,4,5,6 AND 7 WHICH ALL |
| | CONTAIN A NOTE #1 IN A CIRCLE AT THE LOWER LEFT HAND |
| | SIDE OF SCHEDULE, HOWEVER NO NOTE #1 COULD BE LOCATED |
| | ON THIS SHEET. |
| | |
| | 47) NOTE: PLEASE SEE MECHANICAL REVIEW SEEMS TO HAVE A |
| | SUBSTANTIAL AMOUNT OF COMMENTS WHICH MAY MOST CERTAINLY |
| | NEED CHANGES ON ELECTRICAL PLANS. PLEASE BE SURE TO SEE |
| | OTHER NOTES FROM ALL TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-15 18:20:06 | |
| | |
| | IN ELEC FOR REVIEW. |