Plan Review Notes
Plan Review Notes For Permit 07080073
Permit Number 07080073
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-15 21:32:432007-09-15 21:32:43
  
 ** DENIED **
  
 LAKES AT PALM BEACH/ AKA MIZNER LAKES ON SOME SHEETS.
 BUILDING #5.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 ** SOME OF THE ABOVE ARE REFERENCED ON PLANS HOWEVER
 MOST REFERENCE PREVIOUS CODES WHICH ARE NO LONGER IN
 EFFECT.
 PLEASE SEE THAT ALL SHEETS CONTAIN THE RELEVANT CODES
 FOR DESIGN E, FA, FP ETC.
 FBC 106.1.2, 106.1.3, 110.1.2
  
 2) NOTE: PLEASE SEE THE DATE ON THE PLANS IN WHICH THE
 ENGINEERED SIGNED PLANS IS DATED BEFORE THEY WERE
 ISSUED. HOW IS THIS POSSIBLE?
 PLEASE SEE FLORIDA STATUTES 471.025 AS THIS REQUIRES
 THE DESIGN PROFESSIONAL TO SIGN AND DATE EACH SHEET
 WHEN SIGNING, DATING AND SEALING SAID PLANS.
  
 3) NOTE: PLEASE SEE ELECTRICAL PLANS ARE NOT COMPLETE
 WITH ALL CIRCUITING, LIGHTING CONTROLS, COORDINATION
 WITH MANY OF THE SHEETS. PLEASE SEE MOST OF THE NOTES
 BELOW ADDRESS THESE HOWEVER NOT ALL.
 PLEASE SEE FOR EXAMPLE THAT SOME SHEETS ARE NOT
 COMPLETE AND SOME AREAS CAN NOT BE REVIEWED AT THIS
 TIME.
 SEE E2.1.2 COMPARED TO E3.1.2, WEST SIDE OF BUILDING IS
 NOT THE SAME, DOES NOT SHOW THE SAME LAYOUTS FOR POWER
 AND LIGHTING ETC.
 FBC 106.3.5.1.2
 NEC 2005
  
 4) NOTE: PLEASE BE SURE THE LIGHTING SHOWN ON THE
 LANDSCAPE SHEETS CORRELATE WITH THE LIGHTING ON THE
 ELECTRICAL PLANS.
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE THE ADDRESS ON THE PERMIT
 APPLICATION INDICATES 715 HANK AARON DR, HOWEVER THE
 ASSIGNED ADDRESS FOR THIS BUILDING #5 IS 1580 SAMANTHA
 LN.
 **PLEASE KNOW THERE ARE STILL SEVERAL SHEETS IN PLANS
 SETS WHICH REFLECT THE PREVIOUS PROJECT NAME OF MIZNER
 LAKES AND SHEETS WHICH NOW REFLECT LAKES AT PALM
 BEACH.
 ** PLEASE BE SURE TO COORDINATE SHEETS. (NOT A KAMM
 CONSULTING COMMENT)
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE IN NEED OF CORRECTIONS.
 PLEASE SEE THE ADDRESS AND BUILDING INFORMATION NEEDS
 TO MATCH WITH PLANS AND PROJECT. COVER SHEET CALLS FOR
 AN ADDRESS LOCATED IN MIAMI OR SOME OTHER LOCATION.
 PLEASE SEE THE INFORMATION ON LIGHTING NEEDS TO
 CORRELATE WITH PLANS. PLEASE SEE THE SUMMARY SHEETS AND
 THE INPUT DATA REPORT DOES NOT CONTAIN ANY *EXTERIOR
 LIGHTING* ENTERED. HOW IS THIS POSSIBLE WHEN THE PLANS
 CONTAIN DOZENS OF EXTERIOR LIGHT FIXTURES?
 PLEASE SEE LANDSCAPE PLANS AND ELECTRICAL PLANS WHICH
 INDICATE LANDSCAPE LIGHTING FIXTURES.
 PLEASE ALSO SEE THE INFORMATION ON THE INPUT DATA
 REPORT FOR THE INTERIOR LIGHTING WHICH ALSO DOES NOT
 MATCH WITH PLANS. PLEASE SEE THERE ARE ONLY 1 OF EACH
 TYPE OF FIXTURE ENTERED WHICH IS NOT POSSIBLE. PLEASE
 COORDINATE ALL INFORMATION ON CALCULATIONS WITH PLANS.
 PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.3 ETC
  
 7) NOTE: PLEASE SEE THERE ARE A FEW AREAS ON PLANS
 WHICH SOME DEVICES FOR CONTROLS ON LIGHTING AS REQUIRED
 PER 13-415.1.ABC.1.1, .1.2 NEEDS ADDRESSING. PLEASE SEE
 METHODS OF CONTROLS FOR EXTERIOR LIGHTING. PLEASE SEE
 SOME ROOMS FOR EXAMPLE, CUSTODIAN CLOSET, WOMEN RR AND
 MEN RR, RESIDENT STORAGE AREAS, ON E2.3.2 NEAR THE POOL
 DECK ACCESS DOORS.
 PLEASE KNOW AREA FOR RESTROOMS NEEDS TO PROVIDE DEVICES
 WHICH PROVIDE COVERAGE IN ALL AREAS FOR LIFE SAFETY AND
 EGRESS SAFETY.
 PLEASE ALSO SEE RETAIL TEMPORARY SPACES LOCATED ON
 E2.1.1 AND 2.1.2.
  
 8) NOTE: PLEASE SEE SHEET E2.1.2 WHICH MENTIONS TO SEE
 THE ELECTRICAL ROOM DETAIL ON E5.1.3 HOWEVER E5.1.3 IS
 THE TELEPHONE RISER SHEETS.
 PLEASE SEE NOTES ETC ON ARCHITECTURAL PLANS WHICH WERE
 NOTED UNDER BUILDING
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE PROVIDE THE INFORMATION ON PLANS FOR
 THE *EQUAL-POTENTIAL POOL GROUNDING GRID* AS REQUIRED
 PER 680.26.
 PLEASE KNOW EVEN THOUGH THE POOL IT SELF WILL BE UNDER
 SEPARATE PERMIT THE MAIN STRUCTURAL CONTENTS OF THE
 POOL WILL BE PART OF THE BUILDING AND WILL REQUIRE THIS
 GROUNDING.
  
 10) NOTE: PLEASE KNOW THAT THE PLANS WILL BE REQUIRED
 TO STATE *NO DUSK TO DAWN SWIMMING*. PLEASE KNOW IF ANY
 AFTER DISK SWIMMING WILL TAKE PLACE THE REQUIRED
 MINIMUM SIGNED, DATED AND SEALED PHOTO-METRICS WILL BE
 REQUIRED TO BE SUBMITTED TO PALM BEACH COUNTY HEALTH
 DEPARTMENT FOR REVIEW AND STAMPING. THESE WOULD BE
 REQUIRED TO BE SUBMITTED WITH BOTH THE BASE BUILDING
 PLANS AND ALONG WITH THE POOL PERMIT.
 AS MUCH OF THE ELECTRICAL CONDUITS, LIGHTING CONDUITS
 AND GROUNDING OF SYSTEMS IS PART OF THE BASE BUILDING;
 THESE PLANS WILL BE REQUIRED TO CONTAIN MUCH OF THIS
 INFORMATION.
 FBC 106.1.2, NEC 680
  
 11) NOTE: PLEASE SEE SHEET A-SHEETS AND BE SURE THIS
 AND ANY OTHER ELECTRICAL REFLECTED ON OTHER SHEETS
 COORDINATE WITH THE ELECTRICAL PLANS AS SEVERAL CHANGES
 WILL BE MADE AND THE REFLECTED LIGHTING/CEILING PLANS
 ETC WILL NEED TO BE ADJUSTED.
 FBC 106.3.5.1.2
  
 12) NOTE: PLEASE SEE THAT THE INFORMATION FOR THIS PUMP
 HOUSE ELECTRICAL FOR LIGHTING, SERVICE RECEPTACLES ETC
 NEEDS TO BE ADJUSTED.
 PLEASE SEE THE ELECTRICAL RISER AND MSB INDICATES A
 CIRCUIT TO *PUMP HOUSE* AND NO INFORMATION COULD BE
 FOUND FOR THIS. PLEASE ALSO SEE THE CONDUCTORS ARE
 SIZED AT 4-#4MCM?
 PLEASE SEE CIRCUITING ON PUMP HOUSE PLANS INDICATE A
 3-POLE CIRCUIT COMING FROM A L1SA WHICH LENDS TO A
 SEPARATE SERVICE. PLEASE KNOW THAT ELECTRICAL EQUIPMENT
 IN THE FIRE PUMP LOCATION WHICH IS FROM ONE SERVICE MAY
 NOT CONTAIN ANY CIRCUITING FROM ANOTHER SERVICE..
 PLEASE KNOW AS THIS IS A SEPARATE BUILDING PLEASE SEE
 225.31-225.39, 250.32.
 230.70, 230.71,408.4, 310.16, 240.4 ETC
 THE COORDINATION WITH BUILDING #4 AND COORDINATION OF
 FIRE PUMPS ELECTRICALAND FIRE MARSHAL OFFICE COMMENTS
 WILL ALL AFFECT THE ELECTRICAL PLANS AS SUBMITTED. 13)
 NOTE: PLEASE PROVIDE ALL INFORMATION ON THE FIRE PUMPS
 AND MINIMUM FUEL BEING PROVIDED PER NFPA-20 11.4.3.
 PLACING A NOTE ON THE FP SHEETS WHICH STATES THE FIRE
 SPRINKLER CONTRACTOR SHALL PROVIDE A *BIG ENOUGH TANK*
 IS NOT ACCEPTABLE IN LIEU OF PROVIDING THE MINIMUM
 DESIGN FOR CODE COMPLIANCE. PLEASE SEE FIRE MARSHAL
 REVIEW COMMENTS FOR THIS.
 ** PLEASE SEE ALL OF CHAPTER 11 IN NFPA-20 2003
  
 14) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS
 FOR FIRE PUMP, FIRE PUMP CONTROLLER AND FUEL
 TANKS.110.3, 90.7, NFPA-20 CHAPTER 10, 11 ETC. PLEASE
 KNOW MUCH OF THIS WILL ALSO BE REVIEWED BY THE
 MECHANICAL, BUILDING AND FIRE MARSHAL.
 **PLEASE BE SURE TO SEE ANY COMMENTS FROM FIRE MARSHAL
 WITH RESPECT TO BOTH BUILDINGS BEING FED FROM ONE FIRE
 PUMP AND LOCATION.
  
 15) NOTE: PLEASE SEE PLANS ARE MISSING COMPLETED
 PHOTO-METRICS FOR ALL EGRESS PATHS UNDER NORMAL AND
 EMERGENCY. PLEASE KNOW AS THE GARAGE INDICATES SOME OF
 THE LEVELS UNDER EMERGENCY. PLEASE SEE THE GARAGE LEVEL
 UNDER NORMAL INDICATES ALL OF THE FIXTURES WITHOUT
 BATTERY BACK UP. PLEASE SEE ONLY ONE FIXTURE ON THE
 GARAGE PLANS FIRST FLOOR INDICATES A BATTERY BACK UP.
 PLEASE CORRELATE WITH EMERGENCY LIGHTING PLANS. PLEASE
 SEE STAIRS WHICH INDICATE SOME LEVELS, HOWEVER AS THESE
 NUMERIC DESIGNATIONS ARE VERY SMALL THEY ARE NOT EASILY
 READ. PLEASE KNOW THE LEVELS ARE REQUIRED TO BE SHOWN
 THAT ALL STAIR SURFACE AREAS ARE TO HAVE 10FT CANDLES
 MINIMUM UNDER NORMAL AND IS PERMITTED DOWN TO 1FT
 CANDLE UNDER EMERGENCY.
 FAC 61G15-33.004
 NFPA-101 7.8.1.3, 7.9.2.2
  
 16) NOTE: PLEASE CLARIFY HOW PHOTO-METRIC LEVELS WERE
 SUBMITTED FOR POOL DECK AREA UNDER EMERGENCY WHEN THE
 FIXTURES ON PLANS DO NOT INDICATE BATTERY BACK UP?
 COULD NOT LOCATE THESE?
 PLEASE SEE SOME PHOTO-METRICS ARE SHOWN HOWEVER NORMAL
 LEVELS FOR STAIR AREAS DO NOT MEET THE MINIMUM UNDER
 THE LIFE SAFETY CODE AS SECTIONS NOTED ABOVE. PLEASE
 SEE E2.3.1 FOR WHAT ARE SHOWN AS NORMAL AND SEE E3.3.1
 WHICH IS BLANK AND NO LEVELS ARE SHOWN.
 LS 101 7.8 AND 7.9
  
 17) NOTE: PLEASE SEE THERE ARE FIXTURE DESIGNATIONS ON
 PLANS WHICH DO NOT CORRELATE WITH THE LIGHTING FIXTURE
 LEGEND.
 PLEASE ALSO SEE THERE ARE EXIT LIGHTING FIXTURES
 MISSING IN STAIR TOWERS. PLEASE SEE SHEET E2.1.1 AND
 E2.1.2 AS NO EXIT LIGHTS ARE SHOWN.
 THESE ARE REQUIRED UNDER NORMAL AND EMERGENCY. PLEASE
 SEE SOME OF THESE ARE SHOWN ON THE EMERGENCY LIGHTING
 PLANS HOWEVER THEY ARE NOT CIRCUITED OR CONTAIN FIXTURE
 DESIGNATIONS. PLEASE SEE SHEET E3.1.1FOR EXAMPLE.
 PLEASE KNOW AS NOTED ABOVE IN NOTE #3 PLEASE COMPLETE
 AND COORDINATE ALL PLANS AND SHEETS.
 FBC 106.3.5.1.2, 106.1.2
  
 18) NOTE: PLEASE SEE THE FOLLOWING ROOMS WILL BE
 REQUIRED TO CONTAIN BATTERY BACK UP LIGHT FIXTURES OF
 SOME KIND. MAIN ELECTRICAL ROOM, RETAIL ELECTRICAL
 ROOM, TELEPHONE EQUIPMENT ROOM AND RETAIL SPACE WHICH
 CONTAIN FIXTURES. THE RETAIL SPACES TO HAVE A BATTERY
 BACK UP LIGHT FIXTURE OF SOME TYPE HAS BEEN CONFIRMED
 WITH THE FIRE MARSHAL'S OFFICE.
 PLEASE SEE 700.16, 700.12F, LS 101 7.8 AND 7.9 PLEASE
 BE SURE TO SEE OTHER COMMENTS FROM THIS REVIEW OR FIRE
 MARSHAL FOR ANY OTHER LOCATIONS.
  
 19) NOTE: PLEASE SEE PHOTO-METRICS FOR E2.2.2WHICH
 DOES NOT INDICATE TABLES FOR AVERAGE LEVELS.
 FBC 106.3.5.1.2, 106.1.2
 SAME CODE SECTIONS AS NOTED ABOVE FOR LS. PLEASE ALSO
 SEE SOME OTHER SHEETS AND AREAS WHICH NEED TO GIVE THE
 AVERAGE ON TABLES.
  
 20) NOTE: PLEASE SEE ELEVATOR ROOMSAND PITS SHALL
 CONTAIN DEDICATED CIRCUITS FOR RECEPTACLES AND LIGHTING
 PER 620.23 AND 620.24.
 PLEASE SEE AS THE PLANS ARE MISSING FOR FIRST FLOOR
 WEST SIDE, REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE.
 PLEASE SEE HOWEVER THE CIRCUIT WHICH IS NOTED FOR
 ROOF-TOP ROOM ACTUALLY FEEDS OUTSIDE LIGHTING AND OTHER
 AREAS BESIDE THIS ROOM WHICH IS NOT PERMITTED. PLEASE
 ADJUST ALL CIRCUITING ON PLANS.
  
 21) NOTE: PLEASE SEE NOTE #5 ON SHEET E2.1.1 WHICH
 CONTAINS A NOTE FOR RATING THE J-BOX AT 500LBS? PLEASE
 CLARIFY THIS? WHAT TYPE OF FIXTURE/EQUIPMENT WILL BE
 PLACED ON THIS?
 FBC 106.1.2
  
 22) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE
 OPERATION OF DEVICES FOR ACCESS GATES, DOORS, AND
 PERSONNEL GATES.
 PLEASE SEE LS 101 7.2.1.5, 7.2.1.5.4, 7.2.1.6.2 ETC **
 PLEASE SEE FIRE MARSHAL REVIEW COMMENTS.
  
 23) NOTE: PLEASE CLARIFY MINIMUM LIGHTING LEVELS IN
 ELEVATOR PITS PER 620.24.
 PLEASE SEE COMMENTARY PROVIDED IN THE NEC FOR STANDARDS
 FROM THE ELEVATOR SAFETY CODE.
 PLEASE BE SURE TO CONTACT OR SEE ANY STATE ELEVATOR
 CODES WHICH ACTUALLY MAY BE MORE RESTRICTIVE FOR
 LIGHTING LEVELS.
 "ASME/ANSIA17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.*
  
 24) NOTE: PLEASE PROVIDE INFORMATION FOR EMERGENCY SHUT
 OFF OF SPA PER 680.41.
 THE DEVICE AS SHOWN DOES NOT PROVIDE LOCATION AND EM
 SHUT OFF INFORMATION.
  
 25) NOTE: PLEASE KNOW AS THE TIMERS AS SHOWN IN MOST
 ELECTRICAL ROOMS DO NOT MEET 110.26D, PLEASE PROVIDE A
 DIFFERENT WAY FOR CONTROLLING LIGHTING.(MULTIPLE METHOD
 TO ALLEVIATE A SAFETY OR HAZARDOUS CONDITION. PLEASE
 SEE13-415.1.ABC.1.1 EXCEPT *C*.
  
 26) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS LOCATED
 IN THE ELEVATOR EQUIPMENT ROOM ABOVE THE ELEVATOR
 MOTORS. PLEASE KNOW AS PER INFORMATION FROM THE STATE
 ELEVATOR CODE, THIS AREA WILL REQUIRE ADDITIONAL
 LIGHTING. THIS IS NOT IN THE NEC OR LS CODE, HOWEVER IT
 MAY BE OF INTEREST TO PLACE ON PLANS AT THIS TIME.
 PLEASE VERIFY WITH THE STATE.
 FBC 106.3.5.1.2, 106.1.2
 NO CHANGES ARE REQUIRED TO PLANS AND THIS NOTE IS FOR
 INFORMATIONAL PURPOSE.
  
 27) NOTE: PLEASE PROVIDE DISCONNECT DETAILS FOR ROOF
 TOP EQUIPMENT FOR SELECTIVE MECHANICAL AND OTHER
 EQUIPMENT.
 PLEASE SEE MECHANICAL REVIEW COMMENTS FOR POSSIBLE
 LOCATIONS AND INFORMATION NEEDED.
 440.11, 422.30 ETC THIS CAN BE A TYPICAL DETAIL FOR ANY
 EQUIPMENT WHICH IS MULTIPLE OF THE SAME USE ETC. FBC
 106.1.2
  
 28) NOTE: PLEASE BE SURE THE PANEL SCHEDULE FOR UNITS
 ARE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 PLEAS SEE SECTION 408.4 AND THE FOLLOWING TEXT WHICH IS
 EXTRACTED DIRECTLY FROM THE NEC AND COMMENTARY.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 29) NOTE: PLEASE SEE C2L WHICH INDICATES CONDUCTORS AND
 CONDUIT FOR CIRCUIT #24 AS BLANK.
  
 30) NOTE: PLEASE SEE UNIT C-5 WHICH CIRCUIT C5L-13 IS
 ALSO FEEDING THE MASTER BEDROOM HALL LIGHTING AND
 RECEPTACLE WHICH IS NOTE PERMITTED PER 210.52D,
 210.11C3.
  
 31) NOTE: PLEASE SEE UNIT C-3 WHICH IS SHOWN FOR THE
 BATHROOM LIGHTING CIRCUIT IN GUEST BATH ALSO FEEDING
 THE CIRCUIT FOR HALF BATH WHICH IS NOT PERMITTED.
 PLEASE SEE 210.52D, 210.11.C3.
  
 32) NOTE: PLEASE SEE UNIT C-4 WHICH IS MISSING GFI FOR
 KITCHEN COUNTER SPACE PER 210.52C1
  
 33) NOTE: PLEASE SEE DINING AREA IN TH1 WHICH DOES NOT
 SEEM TO BE DEFINED AND PART OF DINING AREA SEEMS TO BE
 ON LIVING ROOM CIRCUIT.
 PLEASE BE SURE TO CIRCUIT PER 210.52B1, 210.11C1,
 220.53
  
 34) NOTE: PLEASE SEE UNIT TH2 WHICH IS MISSING
 RECEPTACLES REQUIRED FOR WALL SPACE PER 210.52. THIS IS
 THE RAIL AREA ON SECOND FLOOR WHICH PER NEC IS
 CONSIDERED WALL SPACE. THIS WAS DONE ON BUILDING #4.
  
 35) NOTE: PLEASE SEE THE DINING AREA IN UNIT TH2 AS
 THIS AREA CONTAINS RECEPTACLES CIRCUITED TO THE LIVING
 ROOM/OTHER AREAS.
 PLEASE SEE 210.52B1, 210.11C1.
  
 36) NOTE:PLEASE SEE NFPA-72FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES.
 PLANS INDICATE ALL DEVICES IN UNITS AS *SMOKE
 DETECTORS* AND NOT * SMOKE ALARMS*.
 PLEASE KNOW IF THESE ARE DEVICES WHICH DETECT AND SOUND
 AN ALARM.
 PLEASE ADJUST PLANS.
 PLEASE ALSO BE SURE ALL SMOKE ALARMS ARE MOUNTED ON
 WALL LEADING TO THE FLOOR ABOVE. A NOTE IS LOCATED FOR
 THIS HOWEVER THE NOTE COULD ALSO BE READ TO MOUNT THIS
 UNIT ON WALL ON THE UPPER LEVEL.
 PLEASE ADJUST NOTE.
 NFPA-7211.5.1.1, 11.8.3
  
 38) NOTE: PLEASE SEE MAIN #4 WHICH IS SHOWN AS 1600AMPS
 YET THE RISER ONLY INDICATES ONE RUN OF 500MCM WHICH IS
 ONLY RATED FOR 380AMPS.
 PLEASE SEE THIS IS THE SAME FOR THE FEEDER/SERVICE
 CONDUCTOR LEGEND AND FS DESIGNATIONS.
 PLEASE SEE 240.4B FOR DEVICES RATED OVER 800AMPS.
 110.14, 310.16
  
 39) NOTE: PLEASE CLARIFY AND COORDINATE THE FS-1 AND
 FS-6 ON RISER.
 THE RISER SHOWS FS-1 BEING STUBBED UP IN MAIN
 ELECTRICAL ROOM, HOWEVER THE MAIN ELECTRICAL ROOM
 LAYOUT ON E5.1.4 INDICATES THIS AS FS-6?
 PLEASE ALSO SEE THE RISER SHOWS FS-6 WHICH SEEM TO BE
 OUTSIDE OR AT ANOTHER LOCATION FOR STUB UP.
 PLEASE SEE ANY FUTURE SERVICES WILL BE REVIEWED PER AHJ
 AND IN EITHER AS SHOWN ON THE RISER, FS-6 DOES NOT
 APPEAR TO STUB UP IN ROOM, ONLY WHAT E5.1.4 SHOWS.
 PLEASE CORRELATE AND COMPLETE SHOWING FS-1 ON FLOOR
 LAYOUT ALSO.
 FBC 106.3.5.1.2
 NEC 230.72, 230.70, 90.4
  
 40) NOTE: PLEASE SUBMIT WORST CASE VOLTAGE DROP
 CALCULATIONS FOR FEEDER(S) AND BRANCH CIRCUIT(S) PER
 13-413.1ABC.1
  
 41) NOTE: PLEASE SEE 422.13 AS LOADS FOR WATER HEATERS
 ARE NOW REQUIRED TO BE FIGURED INTO LOAD CALCULATIONS
 AT 125% FOR CONTINUOUS LOADS.
 THIS CHANGED IN THE 2005 NEC.
  
 42) NOTE: PLEASE BE SURE THE ARCHITECT AND STRUCTURAL
 ENGINEER OBTAINS THE BUS-WAY/DUCT CURBING DETAIL AND
 PLACES ON THEIR RESPECTIVE SHEETS.
 THIS AHJ HAS HAD SEVERAL NOT INSTALLED AND CONSTRUCTED
 CORRECTLY AS THE DETAIL WAS NOT ON THE A AND S SHEETS
 FOR THE BUILDING CONTRACTOR.
 THIS IS NOT AN ITEM TO CONSTRUCT AFTER INSTALLATION OF
 BUS-WAY.
 106.1.2
  
 43) NOTE: PLEASE SEE THE GUTTER ON E5.1.5 DOES NOT
 COORDINATE WITH THE GUTTER ON THE ELECTRICAL RISER.
 PLEASE VERIFY SIZE AS THE CONDUCTORS ON RISER WERE NOT
 SHOWN FOR 1600AMPS AND THE SIZE OF THE GUTTER CAN NOT
 BE CONFIRMED AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND NEC 366
 FOR SIZING.
  
 44) NOTE:PLEASE PROVIDE INFORMATION ON MAINS FOR MSB,
 SBA, MDR AND MC1A. PLEASE VERIFY MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED PER 230.76,
 230.79
 ** PLEASE ALSO SEE THE LOAD SUMMARY FOR MSB SEEMS TO BE
 LABELED MSB-1. THIS SEEMS TO BE THE SAME, BUT ONLY
 LABELED DIFFERENT. (TYPE-O)
  
 45) NOTE: PLEASE SEE RISER IS INDICATING 105 UNITS.
 PLEASE BE SURE TO COORDINATE WITH ALL OTHER SHEETS AND
 OTHER TRADES.
 PLEASE CORRELATE AND ADJUST ALL PLANS AS NEEDED. FBC
 106.3.5.1.2
  
 46) NOTE: PLEASE SEE MC 1,3,4,5,6 AND 7 WHICH ALL
 CONTAIN A NOTE #1 IN A CIRCLE AT THE LOWER LEFT HAND
 SIDE OF SCHEDULE, HOWEVER NO NOTE #1 COULD BE LOCATED
 ON THIS SHEET.
  
 47) NOTE: PLEASE SEE MECHANICAL REVIEW SEEMS TO HAVE A
 SUBSTANTIAL AMOUNT OF COMMENTS WHICH MAY MOST CERTAINLY
 NEED CHANGES ON ELECTRICAL PLANS. PLEASE BE SURE TO SEE
 OTHER NOTES FROM ALL TRADES WHICH MAY AFFECT THE
 ELECTRICAL SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-15 18:20:06 
  
 IN ELEC FOR REVIEW.