| 2007-09-22 16:53:17 | THE LAKES AT PALM BEACH |
| | LUGANO BUILDING NO. 5 |
| | SEPT.22,2007 |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07080073 |
| | ADD:1580 SAMANTHA LANE |
| | CONT: AVS CONSTRUCTION |
| | TEL: (954)655-5162 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2)PLANS SUBMITTED AFTER JULY 1, 2007WILL BE |
| | REVIEWED UNDER THE 2004 BASE FLORIDA BUILDING CODE, |
| | BUILDING WITH 2006 AMENDMENTS AND THE 2007WIND |
| | PROVISIONS. PLEASE CORRECT |
| | SHEET A-002 BUILDING NO. 5 DATA, THE WRONG YEAR CODE. |
| | |
| | 3) SHEET A-002 BUILDING DATA ALSO CORRECT THE HEIGHT |
| | AND AREA LIMITATIONS, AND THE REFERENCE TO TABLE 500 |
| | PLEASE UPDATE TO THE 2004 NOMENCLATURE. PLEASE |
| | CORRELATE WITH THE LIFE SAFETY SHEET FOUND ON SHEET |
| | A-251. |
| | |
| | 4) 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6) FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE |
| | A SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS |
| | ON A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| | OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY553.79(5) FLORIDA STATUTES TO |
| | THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT |
| | HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM |
| | AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE |
| | PERMIT MAY BE ISSUED. |
| | |
| | 8)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 10) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 11) HURRICANE PREPAREDNESS |
| | |
| | 12) CORRELATE PLANS IT APPEARS THAT ON THE CIVIL PLANS |
| | THE PROJECT NAME STILL INDICATES MIZNER LAKES AND NOT |
| | THE LAKES AT PALM BEACH, PLEASE CORRECT. |
| | |
| | 13) SHEETS A-003- A004 INDICATE THE FAIR HOUSING |
| | GUIDELINES, PLEASE NOTE THAT THE FIRST FLOOR MERCANTILE |
| | OCCUPANCY WILL BE UNDER 2004 FBC CHAPTER 11 FLORIDA |
| | ACCESSIBILITY. |
| | |
| | 14) SHEET A-102 & A-202 THE COVERED ENTRY LOADING SPACE |
| | BY THE FRONT ELEVATOR LOBBY # 100 INDICATES STAIRS BUT |
| | NO VERTICAL ACCESSIBILITYIN UNDER THE COVERED CANOPY. |
| | AGAIN |
| | 11-2.2EQUIVALENT FACILITATION, YOU CAN?T DISCRIMINATE |
| | AGAINST TOUGHS WITH DISABILITIES |
| | REQUIRING THEM TO TAKE A ROUTE THAT IS NOT COVERED. |
| | |
| | 15) SHEET A-102 & A-202 AND A-502 ALL INDICATE A |
| | SECURITY OFFICE AND A VALET STATION WITH |
| | WHAT APPEARS TO BE A COUNTER AND SLIDING GLASS WINDOWS, |
| | PLEASE PROVIDE A SECTION OF THIS AREA WITH THE COUNTER |
| | HEIGHT PROVIDED TO MEET FAIR HOUSING GUIDE LINES. |
| | |
| | 16) SHEET A-102 & A-202 BOTH HAVE RAMPS: |
| | 16A) BY THE CONDO UNITTH-1E THERE 2 ACCESSIBLE |
| | PARKING SPACES WITH A 5?-0? WIDE ACCESS AISLE, THIS |
| | AREA IS ALSO THE BOTTOM LANDING FOR TWO RAMPS, THE |
| | BOTTOM LANDING FOR RAMPS REQUIRES A 72? LANDING NOT A |
| | 60? LANDING. 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON |
| | RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF |
| | EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & |
| | LEVEL CLEARANCE. |
| | |
| | 16B) THE SAME TYPE SITUATION OCCURS AT CONDO UNIT TH-1A |
| | , THE BOTTOM LANDING FROM RAMPS IS ONLY 5?-0? NOT THE |
| | REQUIRED 72?. .(2) LANDINGS. ALL LANDINGS ON RAMPS |
| | SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH |
| | RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL |
| | CLEARANCE. |
| | |
| | 17) A-202 DOOR OR GATE G06 & G07 PLEASE PROVIDE |
| | MANUFACTURERS? INFORMATION ON HOW |
| | THESE UNITS WILL OPEN? 106.1.2* ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 18) A-201, THE HANDICAPPED RAMP IN THE UPPER RIGHT |
| | PORTION OF THE SHEET IS MISSING THE BOTTOM LANDING. |
| | .11-4.8.4(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT |
| | BE LESS THAN 60" |
| | CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS |
| | THAN 72" OF STRAIGHT & LEVEL CLEARANCE. |
| | |
| | 19) SHEETA-201 THE HANDICAPPED RAMP ALSO APPEARS THAT |
| | IT IS DIRECTLY IN FRONT OF 5 EXHAUST FANS FOR THE |
| | ENCLOSED PARING GARAGE,THE DISABLED COULD MAKE A |
| | STRONG CASE OF |
| | EQUIVALENT FACILITATION 11-2.2, THAT THEY ARE FORCED TO |
| | USE THE RAMP WHERE THEY WOULD BE SUBJECT TO THE CAR |
| | EXHAUST WHILE OTHERS WHO ARE NOT DISABLED DO NOT HAVE |
| | TO BE OBJECTED TO THE EXHAUST FUMES. |
| | |
| | 20) A-201 WHAT AGAIN ARE RAMPS OR CURB CUTS THE BOTTOM |
| | LANDING IS 5?-0? WHERE : |
| | 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT |
| | BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL |
| | HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCE. |
| | |
| | 21) A-201 & A-501 BOTH INDICATE STAIRS TO THE COVERED |
| | ARCADE BUT THE TREAD DISTANCE IS NOT PROVIDED? PLEASE |
| | PROVIDE A SECTION OF THIS AREA. 1003.5.1 |
| | WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING |
| | 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM |
| | TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM) |
| | AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE |
| | READILY APPARENT. EXCEPTION: WITHIN DWELLING LEVEL. |
| | 1003.5.2 WHERE CHANGE IN ELEVATION OF 12 INCHES (305 |
| | MM) OR LESS OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND |
| | EXIT DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL |
| | BE PROVIDED. |
| | |
| | 22)1009.12 ACCESS TO ROOF.BUILDINGS FOUR STORIES OR |
| | MORE IN HEIGHT, EXCEPT THOSE WITH A ROOF SLOPE GREATER |
| | THAN 4:12, SHALL BE PROVIDED WITH A STAIRWAY TO THE |
| | ROOF. SUCH STAIRWAY SHALL BE MARKED AT STREET AND FLOOR |
| | LEVELS WITH A SIGN INDICATING THAT IT CONTINUES TO THE |
| | ROOF. WHERE ROOFS ARE USED FOR ROOF GARDENS OR FOR |
| | OTHER PURPOSES, STAIRWAYS SHALL BE PROVIDED AS REQUIRED |
| | FOR SUCH USE OR OCCUPANCY. |
| | |
| | 23) SHEET A-201 G-05 DOES NOT HAVE A CURB CUT, THERE IS |
| | NO DESIGNATION FOR AN ACCESSIBLE PATH ACROSS THE ENTRY |
| | AREAS FOR BOTH ENTRIES INTO THE BUILDING BY VEHICLE AND |
| | THERE IS A |
| | CENTER AISLE THAT ALSO DOES NOT HAVE ACCESS ACROSS. |
| | |
| | |
| | 24) HANDICAPPED PARKING SPACES IN THE GARAGE NEED TO |
| | COMPLY WITH 11-4.1.2(5)(B)IN PARKING STRUCTURES, ONE |
| | IN EVERY EIGHT ACCESSIBLE SPACES, BUT NOT LESS THAN |
| | ONE, SHALL BE ?VAN |
| | ACCESSIBLE? AND SHALL BE DESIGNED AS REQUIRED BY |
| | SECTION 11-4.6.3. THE VERTICAL CLEARANCE AT SUCH SPACES |
| | SHALL COMPLY WITH SECTION 11-4.6.5. ALL SUCH SPACES MAY |
| | BE GROUPED ON THE SAME LEVEL OF A PARKING STRUCTURE. |
| | WHEN SUCH SPACES ARE PROVIDED IN A PARKING STRUCTURE |
| | AND ONLY ONE IN EIGHT MEET THE HEIGHT REQUIREMENT OF |
| | SECTION 11-4.6.5, THEY SHALL BE DESIGNATED BY SECTION |
| | 11.6.4. |
| | |
| | 25) A-201 & A-703 BOTH INDICATE A GATE BENEATH THE |
| | STAIRWELL, AND A NOTE ON SHEET A-703 INDICATES THIS IS |
| | A MAINTENANCE GATE. ENCLOSURES UNDER STAIRWAYS. |
| | 1019.1.5. |
| | THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES |
| | UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| | PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION, |
| | OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| | ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED |
| | USABLE SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE |
| | STAIR ENCLOSURE. |
| | |
| | 26) SINCE THE LAST REVIEW UNDER PERMIT # 05091456,THE |
| | CONFIGURATION OF LOFT UNITS VERSES PASSAGE TO THE |
| | PARKING GARAGE WITH NO EXIT ACCESS CORRIDOR WAS BROUGHT |
| | TO THE ATTENTION OF THE BUILDING OFFICIAL. WE ARE |
| | SEEING MORE OF THIS TYPE DESIGN AND THE BUILDING |
| | OFFICIAL |
| | HAS RULED THAT THIS IS AN UNSAFE PRACTICE. THE |
| | OCCUPANTS LEAVE THE R-2 UNIT AND HAVE NO EXIT ACCESS |
| | CORRIDOR WHEN ENTERING THE PARKING GARAGE AREA. |
| | ALTHOUGH THE CODE DOESN'T QUOTE A |
| | SECTION, THAT AN EXIT ACCESS CORRIDOR IS REQUIRED THE |
| | BUILDING OFFICIAL IS USING THESE (2) CODE SECTIONS TO |
| | ENFORCE REQUIRING A EXIT ACCESS CORRIDOR TAKING THE |
| | OCCUPANT TO THE SAFETY OF AN EXIT. 103.6** |
| | REQUIREMENTS NOT COVERED BY THE CODE. ANY REQUIREMENTS |
| | NECESSARY FOR THE STRENGTH, STABILITY OR PROPER |
| | OPERATION OF EXITING OR PROPOSED BUILDING, STRUCTURE, |
| | ELECTRIC, GAS, MECHANICAL OR PLUMBING SYSTEM, OR FOR |
| | PUBLIC SAFETY, HEALTH AND GENERAL WELFARE , NOT |
| | SPECIFICALLY COVERED BY THIS OR OTHER TECHNICAL CODES, |
| | SHALL BE DETERMINED BY THE BUILDING OFFICIAL. IN |
| | ADDITION, OTHER REQUIREMENTS TO IMPLEMENT, CLARIFY OR |
| | SET PROCEDURES TO IMPLEMENT THIS CODE MAY BE SET IN |
| | WRITING BY THE BUILDING OFFICIAL AND BE POSTED |
| | ELECTRONICALLY FOR PUBLIC ACCESS. 1001.1.4 WHEN |
| | UNUSUALLY HAZARDOUS CONDITIONS EXIST, THE BUILDING |
| | OFFICIAL MAY REQUIRE ADDITIONAL MEANS OF EGRESS TO |
| | ASSURE THE SAFETY OF |
| | THE OCCUPANTS. 1016.1 CONSTRUCTION. CORRIDORS SHALL BE |
| | FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1016.1 . |
| | THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED |
| | SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. 27) |
| | 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| | EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN |
| | CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; |
| | RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| | VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED, |
| | INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED |
| | RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING |
| | UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 28) 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492. |
| | |
| | 29)DOOR SCHEDULE A-901. SEE TABLE 302.3.REQUIRING A |
| | 2HR WALLSS2 TO R2, OPENING PROTECTIVES |
| | 715.3 1 / HR OPENING PROTECTIVES. |
| | |
| | 30) THIS WILL BE A COMMON NOTE FOR ALL R2 UNITS FOR |
| | WALL AND FLOOR SOUND INSULATION REQUIREMENTS27) SHEET |
| | A-201 THE CONDO ENTRY UNIT DOORS 133 & 134 BOTH ARE |
| | MISSING AFIRE RATING ON THE. LEASE PLEASE PROVIDE THE |
| | STC RATINGS FOR WALLS AND FLOORS WHERE REQUIRED. SEE |
| | CODE SECTIONS BELOW |
| | |
| | |
| | 31) SHEET A-202THE DOOR SCHEDULE THAT TIES TO DOORS |
| | 111, 1132 & 115 CONDO ENTRY DOORS ARE NOT FIRE RATED. |
| | RS2 VS S2 TABLE 302.3.2 2HR WALLS 715.3 11/2 HR OPENING |
| | PROTECTIVE. |
| | |
| | 32) 32) SHEET A-205 DOOR 342, 347,367 & 358 ALL |
| | INDICATE THE USE OF SLIDING GLASS DOORS ONTO |
| | PATIO DECKS, PLANS DO NOT INDICATE (3) ITEMS THAT ARE |
| | CONCERNS TO FAIR HOUSING REQUIREMENTS FOR SLIDING GLASS |
| | DOORS (SECONDARY DOORS) THAT LEAD ONTO A IMPERVIOUS |
| | SURFACE. |
| | A) PLEASE PROVIDE A DETAIL INDICATING THE BOTTOM TRACK |
| | HEIGHT IN RELATIONSHIP TO THE INTERIOR FINISH FLOOR AND |
| | THE FINISH FLOOR OF THE PATIO ON THE EXTERIOR. |
| | B) PLEASE PROVIDE THE CLEAR OPENING SIZE FOR THE 6?-2? |
| | SLIDING GLASS DOORS. |
| | C) PROVIDE DETAILS FOR THE LATCHING MECHANISM FOR THE |
| | SLIDING GLASS DOOR. |
| | PLEASE SEE PAGE 4.14 OF FAIR HOUSING MANUAL DETAIL FOR |
| | SLIDING GLASS DOORS AT CONCRETE LANDINGS. |
| | |
| | |
| | |
| | |
| | 32) SHEET A-203 DOOR # 208 DOOR TO STAIR# 4 NOT RATED, |
| | TABLE 715.3 OPENING PROTECTIVE |
| | < THAN 4STORIES 45 MINUTE DOOR. |
| | |
| | 33) SHEET A-206 THE STAIR# 1 DOOR 302 IS MISSING FROM |
| | THE DOOR SCHEDULE, TABLE 715.3 OPENING PROTECTIVE 2HR |
| | SHAFT REQUIRES 1 ? HR OPENING PROTECTIVE. |
| | |
| | 34) SHEET A-205 DOOR 342, 347,367 & 358 ALL INDICATE |
| | THE USE OF SLIDING GLASS DOORS ONTO |
| | PATIO DECKS, PLANS DO NOT INDICATE (3) ITEMS THAT ARE |
| | CONCERNS TO FAIR HOUSING REQUIREMENTS FOR SLIDING GLASS |
| | DOORS (SECONDARY DOORS) THAT LEAD ONTO A IMPERVIOUS |
| | SURFACE. |
| | A) PLEASE PROVIDE A DETAIL INDICATING THE BOTTOM TRACK |
| | HEIGHT IN RELATIONSHIP TO THE INTERIOR FINISH FLOOR AND |
| | THE FINISH FLOOR OF THE PATIO ON THE EXTERIOR. |
| | B) PLEASE PROVIDE THE CLEAR OPENING SIZE FOR THE 6?-2? |
| | SLIDING GLASS DOORS. |
| | C) PROVIDE DETAILS FOR THE LATCHING MECHANISM FOR THE |
| | SLIDING GLASS DOOR. |
| | |
| | |
| | 35) SHEET A-300 THE ELEVATOR LOBBY# 100 IT APPEARS THIS |
| | AREA MAY BE CONSIDERED EITHER A MEZZANINE OR ATRIUM, |
| | PLEASE PROVIDE THE AREA CALCULATIONS OF THE AND THE |
| | ADJOINING AREAS AND PLEASE DO SO FOR THE AREA ABOVE |
| | THAT HAS A 42? HANDRAIL. IT APPEARS THIS AREA MAY |
| | QUALIFY FOR BEING CONSIDERED A MEZZANINE. IF IT DOES |
| | NOT MEET THE QUALIFICATION BY AREA WE WILL THEN |
| | CONSIDER IT A 2 STORY ATRIUM AND THE ASSOCIATED |
| | REQUIREMENTS OF AN ATRIUM WITH THE EXCEPTION OF 404 FOR |
| | A 2 STORY ATRIUM. |
| | |
| | 36) SHEET A-300 PLEASE SEE ROOMS 120 -123 IN EACH OF |
| | THESE ROOMS THERE IS A CHANGE OF GRADE, |
| | PLEASE SEE1003.5.2 WHERE CHANGE IN ELEVATION OF 12 |
| | INCHES (305 MM) OR LESS OCCURS IN EXIT ACCESS |
| | CORRIDORS, EXITS AND EXIT DISCHARGE, RAMPS COMPLYING |
| | WITH SECTION 1010 SHALL BE PROVIDED. 1003.5.3 |
| | |
| | 37) SHEET A-300, THIS NOTE WILL BE COMMON TO ALL ?? |
| | FLOOR PLANS, THESE SHEETS INDICATE THE WALL TYPES BUT |
| | NEGLECT TO IDENTIFY ALL DOORS. WHEN REVIEWING FOR WALL |
| | RATINGS IN SECTION 708 WE REVIEW ALSO FOR THE |
| | CORRESPONDINGOPENING PROTECTIVE IN SECTION 715 AND |
| | TABLE 715.3 PLEASE IDENTIFY BOTH ON THE SAME SHEET, |
| | ADDITIONAL INFORMATION REQUIRED, 106.1.2, IN COMPLYING |
| | WITH THIS REQUEST IT MAY SAVE THE CONTRACTOR & |
| | DEVELOPER TIME AND MONEY IN MISTAKES THAT MAY NOT OF |
| | BEEN CAUGHT IN PLAN REVIEW BUT CAUGHT IN INSPECTIONS IN |
| | THE CONSTRUCTION PHASE OF THE PROJECT.THIS IS |
| | SOMETHING WE TRY TO AVOID BUT THE HARDER IT IS TO FIND |
| | THE WALL AND ASSOCIATED DOOR RATINGS, MISTAKES CAN |
| | HAPPEN. |
| | |
| | 38) SHEET A-300,STAIRWELL# 1, IS MISSING WALL I. D. |
| | TAGS ON VARIOUS WALLS REQUIRES 2 HR RATING, SECTION |
| | 707.4.MISSING TAGSH.C. RESTROOM, TRASH TERMINATION |
| | ROOM WALL LEADING TO ELEVATOR LOBBY. |
| | |
| | 39) THE SHEET A-905 INDICATES WALL TYPE AND UL NUMBERS |
| | ASSOCIATED WITH MASONRY WALLS. |
| | PLEASE PROVIDE LETTERS FROM THE BLOCK MANUFACTURER |
| | INDICATING THE MINIMUM EQUIVALENT THICKNESS FOR THE |
| | MASONRY UNITS. SECTION 721.3.8EQUIVALENT THICKNESS. |
| | |
| | 40) SHEET A-300 TRASH TERMINATION ROOM, IT APPEARS |
| | THERE IS AN UNIDENTIFIED OBJECT IN THE UPPER LEFT HAND |
| | CORNER OF THIS ROOM. ADDITIONAL INFORMATION REQUIRED |
| | 106.1.2. |
| | |
| | 41) SHEET A-300/ A-202 THE TRASH COMPACTOR ROOMS DOOR |
| | 146 IS MISSING THE FIRE RATING AND THE DOOR SCHEDULE |
| | INDICATES IT AS A TYPE ?E? LOUVER DOOR.710.5.1 |
| | LOUVERS . |
| | DOORS IN SMOKE PARTITIONS SHALL NOT INCLUDE LOUVERS. |
| | 707.13.4 TERMINATION ROOM. |
| | |
| | 42) SHEET A-300/ A-202 BOTH FAIL TO INDICATE WALL |
| | RATINGS ON THE COMMON WALL TO THE S2 OCCUPANCY, THE |
| | DOOR SCHEDULE INDICATES A 45 MINUTE RATED DOOR E & F |
| | BOTH BEING LOUVERED DOORS. 710.5.1 LOUVERS . DOORS IN |
| | SMOKE PARTITIONS SHALL NOT INCLUDE LOUVERS. |
| | |
| | 43)SHEET A-300/ A-202 FPL TRANSFORMER VAULT, PLEASE |
| | TAKE NOTE THAT FPL MAY HAVE HIGHER WALL RATING AND |
| | CEILING RATINGS THAN INDICATED. 106.1.2. ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 44) SHEET A-300/ A-202 BOTH INDICATE 2 ELEVATORS, SHEET |
| | A-701 INDICATES STAIR AND ELEVATOR SECTION PLAN NO |
| | PLANS INDICATE COMPLIANCE WITH STRETCHER REQUIREMENTS, |
| | PLEASE PROVIDE DETAIL. |
| | 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE |
| | STRETCHER. |
| | IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST |
| | ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT |
| | EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL |
| | BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A |
| | 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE |
| | STRETCHERIN THE HORIZONTAL, OPEN POSITION AND SHALL |
| | BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY |
| | MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT |
| | BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED |
| | INSIDE ON BOTH SIDES OF THE HOIST WAY DOOR FRAME. |
| | |
| | 45) SHEET A-300/ A-202 THE EGRESS PATH IN FRONT OF |
| | REFUSE TERMINATION ROOM, FIRE BOOSTER PUMP AND THE MAIN |
| | ELECTRIC ROOM ALL SWING INTO THE EGRESS PATHWAY. 1005.2 |
| | DOOR ENCROACHMENT. |
| | DOORS OPENING INTO THE PATH OF EGRESS TRAVEL SHALL NOT |
| | REDUCE THE REQUIRED WIDTH TO LESS THAN ONE-HALF DURING |
| | THE COURSE OF THE SWING. WHEN FULLY OPEN, THE DOOR |
| | SHALL NOT PROJECT MORE THAN 7 INCHES (178 MM) INTO THE |
| | REQUIRED WIDTH. |
| | |
| | 46) SHEET A-202 STAIR TOWER# 2 WHEN YOU LEAVE THE 2 |
| | HOUR RATED ENCLOSURE YOU ARE STILL UNDER THE BUILDING, |
| | AND DOES NOT QUALIFY FOR ANY EXEMPTION UNDER 1023.1 |
| | GENERAL. EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR |
| | OF THE BUILDING. THE EXIT DISCHARGE SHALL BE AT GRADE |
| | OR SHALL PROVIDE DIRECT ACCESS TO GRADE. THE EXIT |
| | DISCHARGE SHALL NOT REENTER A BUILDING.PLANS ALSO |
| | INDICATE A 54"X96" LOUVER WHICH WOULD NOT MAKE ANY FIRE |
| | RATING OF THE EXTERIOR WALL THAT BACKS UP TO THE EXIT |
| | DISCHARGE OF THE STAIR TOWER. |
| | |
| | 46) FL BLD CODE 1606.1.5: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTINGREPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS FIXED/ STOREFRONT |
| | B) WINDOWS OPERABLE |
| | C) MULLIONS |
| | D) EXTERIOR DOORS GLAZED, SLIDERS |
| | E) EXTERIOR LOUVERED DOORS |
| | F) DOORS STEEL |
| | G)EXTERIOR OVERHEAD DOORS |
| | H)HANDRAILS |
| | I) STORM SHUTTERS |
| | J) TRUSS ANCHORS |
| | K) ROOFING ASSEMBLIES |
| | L) PRE-MANUFACTURED A/C STANDS |
| | M) STORM SHUTTERS |
| | |
| | 47) NOTE)) AN INTERPRETATION FROM THE BUILDING OFFICIAL |
| | ON STORM SHUTTERS THAT ARE USED ON LARGE PROJECTS: |
| | QUESTION# 13) RECOGNIZING SUCH CONCERNS AS ABSENTEE |
| | OWNERS, OR CASES WHERE LONGER TIME AND EFFORT IS |
| | NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR |
| | IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR |
| | SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE EVENT? |
| | |
| | IN MATTERS FLORIDA BUILDING CODE, 2004 EDITION, |
| | PROVIDES THE ABILITY FOR THE BUILDING OFFICIAL TO |
| | IMPLEMENT REQUIREMENTS FOR ENSURING STABILITY, |
| | STRENGTH, AND PROPER OPERATION OF EXISTING BUILDINGS. |
| | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY |
| | BUILDING, OR MULTIPLE BUILDINGS ON THE SAME PROPERTY, |
| | PRE-STORM PREPARATION PLANS MUST BE SUBMITTED BY THE |
| | PROPERTY OWNERS OR MANAGING AGENTS FOR REVIEW BY THE |
| | CONSTRUCTION SERVICES DEPARTMENT. ANY SUCH PLAN SHALL |
| | INCLUDE, AT A MINIMUM, ON-SITE LOCATION OF SHUTTERS, |
| | PARTY RESPONSIBLE FOR SECURING THE SHUTTERS (SAID |
| | PARTIES MUST BE LOCATED WITHIN PALM BEACH COUNTY), |
| | TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND TOTAL TIME |
| | REQUIRED TO SECURE ALL OPENINGS. PROTECTION OF OPENINGS |
| | SHALL BE ACCOMPLISHED WITHIN TWELVE (12) HOURS OR LESS |
| | OF THE OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER |
| | SERVICE OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATIVE |
| | MATERIALS AND METHODS, AND ALLOW THE BUILDING OFFICIAL |
| | TO REVIEW AND APPROVE |
| | ANY ALTERNATE DEEMED EQUIVALENT IN QUALITY, STRENGTH, |
| | EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY |
| | PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION, |
| | ACCEPTANCE OF ALTERNATE MATERIALSAND METHODS MAY BE |
| | APPROVED ON A CASE-BY-CASE BASIS AND SHALL REQUIRE |
| | SUFFICIENT EVIDENCE OR PROOF TO SUBSTANTIATE ANY CLAIM |
| | MADE REGARDING THE ALTERNATE. |
| | |
| | QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE |
| | FOR USE ON VERY LARGE, MID |
| | OR HIGH-RISE STRUCTURES? NO, EXCEPT ON THE GROUND |
| | FLOOR. ON COMMERCIAL AND MULTI-UNIT RESIDENTIAL |
| | STRUCTURES, ABOVE THE FIRST LEVEL, IMPACT RESISTANT |
| | GLAZING OR PERMANENTLY |
| | AFFIXED PROTECTIVE DEVICES SHALL BE INSTALLED. |
| | PERMANENTLY AFFIXED PROTECTIVE DEVICES SHALL REQUIRE |
| | THE WRITTEN APPROVAL OF THE BUILDING OFFICIAL. |
| | |
| | 48) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.4. |
| | |
| | 48A) FL BLD CODE 2001 SECTION 1609.1.4, 1714.5 |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE |
| | SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS, |
| | UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING |
| | REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC., |
| | SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO |
| | FACILITATE PLAN REVIEW AND PERMIT ISSUANCE. |
| | |
| | 48B) PROVIDE ROOF PRESSURE ZONES FOR ZONES 4&5. SEE |
| | 1609.1.1/ ASCE 7-02. |
| | |
| | |
| | 49) SHEET A-650 SHOWS VARIOUS SUN SHADES, DETAIL 1& 5 |
| | INDICATE THE USE OF CLOTH SUN SHADES, NOTE HOW YOU WILL |
| | MEET THE WIND REQUIREMENTS OF 3105.4.2.1 OR 3105.4.2.2. |
| | SHOP DRAWINGS MAY BE SUBMITTED AFTER PERMIT. |
| | |
| | 50) PLEASE COMPLY WITH FIRE TREATED FABRIC FOR AWNINGS. |
| | 3105.3.1FABRIC USED FOR AWNINGS OR FABRIC-COVERED |
| | FRAMES SHALL BE FLAME RESISTANT IN ACCORDANCE WITH NFPA |
| | 701. |
| | |
| | 51) SHEET A652 DETAIL# 06 PROVIDEPRODUCT TESTING |
| | REPORT FOR EXHAUST FAN AND PRE-MANUFACTURED CURB, |
| | PROVIDE THE +/- PRESSURES THIS ASSEMBLY HAS BEEN TESTED |
| | FOR. |
| | 1609.6. 1.2 COMPONENTS & CLADDING. |
| | |
| | 52) SHEET A-652 DETAILS 24 & 26 BOTH SHOW RAIN WATER |
| | LITER DETAILS, THESE ARE GOING TO BE PLACED IN 1 HR |
| | FIRE RATED CORRIDORS, BUT THERE IS ONLY 1 LAYER OF |
| | DRYWALL AROUND THE PIPE, PLEASE PROVIDE UL RATING OR |
| | SOME OTHER APPROVED AGENCY THAT THIS IS A 1 HR FIRE |
| | RATED SYSTEM. TABLE 1016.1. |
| | |
| | 53)SHEETS A801-A801E ALL INDICATE A DOOR D-11 BUT NOT |
| | FOUND ON THE DOOR SCHEDULE |
| | A-903. PLEASE PROVIDE ADDITIONAL INFORMATION, 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 54) SHEET A801 TH1A UNITS (2STORY CONDOS) THE GROUND |
| | FLOOR OF THESE UNITS STILL HAVE TO COMPLY WITH FAIR |
| | HOUSING, DOOR D-1 IS A 2?-6? DOOR AND BY DEFINITION A |
| | USEABLE DOOR A NOMINAL 32? CLEAR. |
| | |
| | 55) SHEET A801 TH1A UNITS THERE ARE DOORS ON THE FIRST |
| | FLOOR AND ALSO THE 2ND FLOOR LOFT PORTION OF THE UNIT |
| | THAT BOTH HAVE EXTERIOR DOORS LEADING TO BALCONIES AND |
| | DO NOT HAVE A DOOR IDENTIFICATION MARKER. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 56) SHEET A801B-E TH1B-E UNITS(2STORY CONDOS) THE |
| | GROUND FLOOR OF THESE UNITS STILL HAVE TO COMPLY WITH |
| | FAIR HOUSING, DOOR D-1 IS A 2?-6? DOOR AND BY |
| | DEFINITION A USEABLE DOOR A NOMINAL 32? CLEAR. |
| | |
| | 57) SHEET A801B-E TH1B-E UNITS THERE ARE DOORS ON THE |
| | FIRST FLOOR AND ALSO THE 2ND FLOOR LOFT PORTION OF THE |
| | UNIT THAT BOTH HAVE EXTERIOR DOORS LEADING TO BALCONIES |
| | AND DO NOT HAVE A DOOR IDENTIFICATION MARKER. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 58) SHEET A802- A802C (2STORY CONDOS) THE GROUND FLOOR |
| | OF THESE UNITS STILL HAVE TO COMPLY WITH FAIR HOUSING, |
| | DOOR D-1 IS A 2?-6? DOOR AND BY DEFINITION A USEABLE |
| | DOOR A NOMINAL 32? CLEAR. |
| | |
| | 59) SHEET A802-A802C THE DOORS ON THE FIRST FLOOR AND |
| | ALSO THE 2ND FLOOR LOFT PORTION OF THE UNIT THAT BOTH |
| | HAVE EXTERIOR DOORS LEADING TO BALCONIES AND DO NOT |
| | HAVE A DOOR IDENTIFICATION MARKER. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 60) SHEET A-803 FRONT ENTRY DOOR, AGAIN THIS DOOR IS |
| | NOT LISTED ON THE DOOR SCHEDULE, THIS FRONT ENTRY DOOR |
| | IS IN A FIRE RATED WALL BEING BETWEEN A S2 OCCUPANCY |
| | AND R2 OCCUPANCY, THIS DOOR WILL NEED A CLOSER AND |
| | LATCH AS WELL AS FIRE RATING, PLEASE SEE ANSI A117.1- |
| | 98 DOOR CLEAR WIDTH 404.2.3 AND MINIMUM CLEARANCES SEE |
| | FIGURE 404.2.4.1(B)REQUIRES 12 INCHES WHERE BOTH A |
| | DOOR CLOSER AND LATCH ARE PROVIDED. ALSO FBC TABLE |
| | 715.3, COMMON TO ALL UNITS. |
| | |
| | 61) SHEET A-803A- A-803B BOTH ARE MISSING INFORMATION |
| | ON THE FRONT DOOR AS WELL AS THE SECONDARY DOOR LEADING |
| | TO THE BALCONY, PLEASE SEE COMMENT ABOVE NUMBER 60 ALSO |
| | RELATES, 106.1.2 ADDITIONAL INFORMATION REQUIRED. ALSO |
| | SEE TABLE 715.3. |
| | |
| | 62)SHEET A-804A- A-804HTHE FRONT DOOR AND BALCONY |
| | DOORS DO NOT HAVE IDENTIFICATION TAGS INDICATING THEIR |
| | SIZE AND OR FIRE RATING. FAIR HOUSING ACCESSIBLE DOORS |
| | AND FBC TABLE 715.3. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 63) SHEET A-804D AT BEDROOM NUMBER 2 ON THE BALCONY |
| | THERE APPEARS TO BE A LINE INDICATING A CHANGE IN |
| | GRADE, 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 64) SHEET A-801 SERIES IS MISSING THE DIMENSION BETWEEN |
| | DOORS IN THE VESTIBULE, FAIR HOSING |
| | ANSI 4.13 MINIMUM SPACE BETWEEN DOORS IN SERIES 4?-0? |
| | PLUS DOOR WIDTH IF SWINGS IN. |
| | PROVIDE DIMENSION. |
| | |
| | 65) SHEET A-805, A-806, A-807 & A-807A ALL NEED TO |
| | PROVIDE THE CLEAR OPENING WIDTH FOR THE 6?-0? SLIDING |
| | GLASS DOORS FOR SECONDARY DOORS MINIMUM OF 32? CLEAR, |
| | SEE FAIR HOUSING |
| | 404.2.3 (B). |
| | |
| | 66) SHEET A-903 DOOR NOTES, HURRICANE MISSILE IMPACT |
| | NOTES, FRENCH DOORS TO COMPLY WITH |
| | COMMENT 47 & 48A. |
| | |
| | 67) SHEET A-903 BURGLAR INTRUSION NOTES (3), INDICATES |
| | THE USE OF PINS FOR EXTRA SECURITY DEVICES, SEE FAIR |
| | HOUSING SECONDARY EXTERIOR DOORS SLIDING GLASS DOORS |
| | PAGE 3.10-3.12 CLEAR WIDTH AND HARDWARE REQUIREMENTS |
| | AND RECOMMENDATIONS. |
| | |
| | 68)SHEET A-903 BURGLAR INTRUSION NOTE NUMBER (7), |
| | INACTIVE LEAF OF A PAIR OF DOORS SHALL BE PROVIDED WITH |
| | MULTIPLE POINT LOCKS AS REQUIRED BY THE PRODUCT |
| | APPROVALS. AGAIN THESE LOCKS HAVE TO BE ABLE TO OPERATE |
| | FROM A WHEELCHAIR.ANSI A117.1-98, 404.2.7. |
| | |
| | 69) SHEET S4.5 DETAIL SECTION 5-4.5 INDICATES USE OF |
| | 5/8? EXTERIOR GRADE PLYWOOD PLEASE SEE |
| | TABLE 601 FOOTNOTE ( C ) (2) WHEN FIRE TREATED PLYWOOD |
| | CAN AND CAN NOT BE USED. THIS BUILDING IS CLASSIFIED AS |
| | A TYPE IB BUILDING. |
| | |
| | 70) ?S? SHEETS THE SEAL IS NOT EMBOSSED TO WHERE IT IS |
| | LEGIBLE AND OR SOME SHEETS ARE NOT SEALED AT ALL. THE |
| | EMBOSSED SEAL SHALL BE LEGIBLE 61G15-23.002. |
| | |
| | 71) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |