Plan Review Notes
Plan Review Notes For Permit 07080073
Permit Number 07080073
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-22 16:53:17THE LAKES AT PALM BEACH
 LUGANO BUILDING NO. 5
 SEPT.22,2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07080073
 ADD:1580 SAMANTHA LANE
 CONT: AVS CONSTRUCTION
 TEL: (954)655-5162
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)PLANS SUBMITTED AFTER JULY 1, 2007WILL BE
 REVIEWED UNDER THE 2004 BASE FLORIDA BUILDING CODE,
 BUILDING WITH 2006 AMENDMENTS AND THE 2007WIND
 PROVISIONS. PLEASE CORRECT
 SHEET A-002 BUILDING NO. 5 DATA, THE WRONG YEAR CODE.
  
 3) SHEET A-002 BUILDING DATA ALSO CORRECT THE HEIGHT
 AND AREA LIMITATIONS, AND THE REFERENCE TO TABLE 500
 PLEASE UPDATE TO THE 2004 NOMENCLATURE. PLEASE
 CORRELATE WITH THE LIFE SAFETY SHEET FOUND ON SHEET
 A-251.
  
 4) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS. 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE
 A SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS
 ON A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY553.79(5) FLORIDA STATUTES TO
 THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED.
  
 8)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 10) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 11) HURRICANE PREPAREDNESS
  
 12) CORRELATE PLANS IT APPEARS THAT ON THE CIVIL PLANS
 THE PROJECT NAME STILL INDICATES MIZNER LAKES AND NOT
 THE LAKES AT PALM BEACH, PLEASE CORRECT.
  
 13) SHEETS A-003- A004 INDICATE THE FAIR HOUSING
 GUIDELINES, PLEASE NOTE THAT THE FIRST FLOOR MERCANTILE
 OCCUPANCY WILL BE UNDER 2004 FBC CHAPTER 11 FLORIDA
 ACCESSIBILITY.
  
 14) SHEET A-102 & A-202 THE COVERED ENTRY LOADING SPACE
 BY THE FRONT ELEVATOR LOBBY # 100 INDICATES STAIRS BUT
 NO VERTICAL ACCESSIBILITYIN UNDER THE COVERED CANOPY.
 AGAIN
 11-2.2EQUIVALENT FACILITATION, YOU CAN?T DISCRIMINATE
 AGAINST TOUGHS WITH DISABILITIES
 REQUIRING THEM TO TAKE A ROUTE THAT IS NOT COVERED.
  
 15) SHEET A-102 & A-202 AND A-502 ALL INDICATE A
 SECURITY OFFICE AND A VALET STATION WITH
 WHAT APPEARS TO BE A COUNTER AND SLIDING GLASS WINDOWS,
 PLEASE PROVIDE A SECTION OF THIS AREA WITH THE COUNTER
 HEIGHT PROVIDED TO MEET FAIR HOUSING GUIDE LINES.
  
 16) SHEET A-102 & A-202 BOTH HAVE RAMPS:
 16A) BY THE CONDO UNITTH-1E THERE 2 ACCESSIBLE
 PARKING SPACES WITH A 5?-0? WIDE ACCESS AISLE, THIS
 AREA IS ALSO THE BOTTOM LANDING FOR TWO RAMPS, THE
 BOTTOM LANDING FOR RAMPS REQUIRES A 72? LANDING NOT A
 60? LANDING. 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON
 RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF
 EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE.
  
 16B) THE SAME TYPE SITUATION OCCURS AT CONDO UNIT TH-1A
 , THE BOTTOM LANDING FROM RAMPS IS ONLY 5?-0? NOT THE
 REQUIRED 72?. .(2) LANDINGS. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARANCE.
  
 17) A-202 DOOR OR GATE G06 & G07 PLEASE PROVIDE
 MANUFACTURERS? INFORMATION ON HOW
 THESE UNITS WILL OPEN? 106.1.2* ADDITIONAL INFORMATION
 REQUIRED.
  
 18) A-201, THE HANDICAPPED RAMP IN THE UPPER RIGHT
 PORTION OF THE SHEET IS MISSING THE BOTTOM LANDING.
 .11-4.8.4(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT LESS
 THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 19) SHEETA-201 THE HANDICAPPED RAMP ALSO APPEARS THAT
 IT IS DIRECTLY IN FRONT OF 5 EXHAUST FANS FOR THE
 ENCLOSED PARING GARAGE,THE DISABLED COULD MAKE A
 STRONG CASE OF
 EQUIVALENT FACILITATION 11-2.2, THAT THEY ARE FORCED TO
 USE THE RAMP WHERE THEY WOULD BE SUBJECT TO THE CAR
 EXHAUST WHILE OTHERS WHO ARE NOT DISABLED DO NOT HAVE
 TO BE OBJECTED TO THE EXHAUST FUMES.
  
 20) A-201 WHAT AGAIN ARE RAMPS OR CURB CUTS THE BOTTOM
 LANDING IS 5?-0? WHERE :
 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
 21) A-201 & A-501 BOTH INDICATE STAIRS TO THE COVERED
 ARCADE BUT THE TREAD DISTANCE IS NOT PROVIDED? PLEASE
 PROVIDE A SECTION OF THIS AREA. 1003.5.1
 WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING
 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM
 TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM)
 AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE
 READILY APPARENT. EXCEPTION: WITHIN DWELLING LEVEL.
 1003.5.2 WHERE CHANGE IN ELEVATION OF 12 INCHES (305
 MM) OR LESS OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND
 EXIT DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL
 BE PROVIDED.
  
 22)1009.12 ACCESS TO ROOF.BUILDINGS FOUR STORIES OR
 MORE IN HEIGHT, EXCEPT THOSE WITH A ROOF SLOPE GREATER
 THAN 4:12, SHALL BE PROVIDED WITH A STAIRWAY TO THE
 ROOF. SUCH STAIRWAY SHALL BE MARKED AT STREET AND FLOOR
 LEVELS WITH A SIGN INDICATING THAT IT CONTINUES TO THE
 ROOF. WHERE ROOFS ARE USED FOR ROOF GARDENS OR FOR
 OTHER PURPOSES, STAIRWAYS SHALL BE PROVIDED AS REQUIRED
 FOR SUCH USE OR OCCUPANCY.
  
 23) SHEET A-201 G-05 DOES NOT HAVE A CURB CUT, THERE IS
 NO DESIGNATION FOR AN ACCESSIBLE PATH ACROSS THE ENTRY
 AREAS FOR BOTH ENTRIES INTO THE BUILDING BY VEHICLE AND
 THERE IS A
 CENTER AISLE THAT ALSO DOES NOT HAVE ACCESS ACROSS.
  
  
 24) HANDICAPPED PARKING SPACES IN THE GARAGE NEED TO
 COMPLY WITH 11-4.1.2(5)(B)IN PARKING STRUCTURES, ONE
 IN EVERY EIGHT ACCESSIBLE SPACES, BUT NOT LESS THAN
 ONE, SHALL BE ?VAN
 ACCESSIBLE? AND SHALL BE DESIGNED AS REQUIRED BY
 SECTION 11-4.6.3. THE VERTICAL CLEARANCE AT SUCH SPACES
 SHALL COMPLY WITH SECTION 11-4.6.5. ALL SUCH SPACES MAY
 BE GROUPED ON THE SAME LEVEL OF A PARKING STRUCTURE.
 WHEN SUCH SPACES ARE PROVIDED IN A PARKING STRUCTURE
 AND ONLY ONE IN EIGHT MEET THE HEIGHT REQUIREMENT OF
 SECTION 11-4.6.5, THEY SHALL BE DESIGNATED BY SECTION
 11.6.4.
  
 25) A-201 & A-703 BOTH INDICATE A GATE BENEATH THE
 STAIRWELL, AND A NOTE ON SHEET A-703 INDICATES THIS IS
 A MAINTENANCE GATE. ENCLOSURES UNDER STAIRWAYS.
 1019.1.5.
 THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES
 UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION,
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 USABLE SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE
 STAIR ENCLOSURE.
  
 26) SINCE THE LAST REVIEW UNDER PERMIT # 05091456,THE
 CONFIGURATION OF LOFT UNITS VERSES PASSAGE TO THE
 PARKING GARAGE WITH NO EXIT ACCESS CORRIDOR WAS BROUGHT
 TO THE ATTENTION OF THE BUILDING OFFICIAL. WE ARE
 SEEING MORE OF THIS TYPE DESIGN AND THE BUILDING
 OFFICIAL
 HAS RULED THAT THIS IS AN UNSAFE PRACTICE. THE
 OCCUPANTS LEAVE THE R-2 UNIT AND HAVE NO EXIT ACCESS
 CORRIDOR WHEN ENTERING THE PARKING GARAGE AREA.
 ALTHOUGH THE CODE DOESN'T QUOTE A
 SECTION, THAT AN EXIT ACCESS CORRIDOR IS REQUIRED THE
 BUILDING OFFICIAL IS USING THESE (2) CODE SECTIONS TO
 ENFORCE REQUIRING A EXIT ACCESS CORRIDOR TAKING THE
 OCCUPANT TO THE SAFETY OF AN EXIT. 103.6**
 REQUIREMENTS NOT COVERED BY THE CODE. ANY REQUIREMENTS
 NECESSARY FOR THE STRENGTH, STABILITY OR PROPER
 OPERATION OF EXITING OR PROPOSED BUILDING, STRUCTURE,
 ELECTRIC, GAS, MECHANICAL OR PLUMBING SYSTEM, OR FOR
 PUBLIC SAFETY, HEALTH AND GENERAL WELFARE , NOT
 SPECIFICALLY COVERED BY THIS OR OTHER TECHNICAL CODES,
 SHALL BE DETERMINED BY THE BUILDING OFFICIAL. IN
 ADDITION, OTHER REQUIREMENTS TO IMPLEMENT, CLARIFY OR
 SET PROCEDURES TO IMPLEMENT THIS CODE MAY BE SET IN
 WRITING BY THE BUILDING OFFICIAL AND BE POSTED
 ELECTRONICALLY FOR PUBLIC ACCESS. 1001.1.4 WHEN
 UNUSUALLY HAZARDOUS CONDITIONS EXIST, THE BUILDING
 OFFICIAL MAY REQUIRE ADDITIONAL MEANS OF EGRESS TO
 ASSURE THE SAFETY OF
 THE OCCUPANTS. 1016.1 CONSTRUCTION. CORRIDORS SHALL BE
 FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1016.1 .
 THE CORRIDOR WALLS REQUIRED TO BE FIRE-RESISTANCE RATED
 SHALL COMPLY WITH SECTION 708 FOR FIRE PARTITIONS. 27)
 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 28) 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  
 29)DOOR SCHEDULE A-901. SEE TABLE 302.3.REQUIRING A
 2HR WALLSS2 TO R2, OPENING PROTECTIVES
 715.3 1 / HR OPENING PROTECTIVES.
  
 30) THIS WILL BE A COMMON NOTE FOR ALL R2 UNITS FOR
 WALL AND FLOOR SOUND INSULATION REQUIREMENTS27) SHEET
 A-201 THE CONDO ENTRY UNIT DOORS 133 & 134 BOTH ARE
 MISSING AFIRE RATING ON THE. LEASE PLEASE PROVIDE THE
 STC RATINGS FOR WALLS AND FLOORS WHERE REQUIRED. SEE
 CODE SECTIONS BELOW
  
  
 31) SHEET A-202THE DOOR SCHEDULE THAT TIES TO DOORS
 111, 1132 & 115 CONDO ENTRY DOORS ARE NOT FIRE RATED.
 RS2 VS S2 TABLE 302.3.2 2HR WALLS 715.3 11/2 HR OPENING
 PROTECTIVE.
  
 32) 32) SHEET A-205 DOOR 342, 347,367 & 358 ALL
 INDICATE THE USE OF SLIDING GLASS DOORS ONTO
 PATIO DECKS, PLANS DO NOT INDICATE (3) ITEMS THAT ARE
 CONCERNS TO FAIR HOUSING REQUIREMENTS FOR SLIDING GLASS
 DOORS (SECONDARY DOORS) THAT LEAD ONTO A IMPERVIOUS
 SURFACE.
 A) PLEASE PROVIDE A DETAIL INDICATING THE BOTTOM TRACK
 HEIGHT IN RELATIONSHIP TO THE INTERIOR FINISH FLOOR AND
 THE FINISH FLOOR OF THE PATIO ON THE EXTERIOR.
 B) PLEASE PROVIDE THE CLEAR OPENING SIZE FOR THE 6?-2?
 SLIDING GLASS DOORS.
 C) PROVIDE DETAILS FOR THE LATCHING MECHANISM FOR THE
 SLIDING GLASS DOOR.
 PLEASE SEE PAGE 4.14 OF FAIR HOUSING MANUAL DETAIL FOR
 SLIDING GLASS DOORS AT CONCRETE LANDINGS.
  
  
  
  
 32) SHEET A-203 DOOR # 208 DOOR TO STAIR# 4 NOT RATED,
 TABLE 715.3 OPENING PROTECTIVE
 < THAN 4STORIES 45 MINUTE DOOR.
  
 33) SHEET A-206 THE STAIR# 1 DOOR 302 IS MISSING FROM
 THE DOOR SCHEDULE, TABLE 715.3 OPENING PROTECTIVE 2HR
 SHAFT REQUIRES 1 ? HR OPENING PROTECTIVE.
  
 34) SHEET A-205 DOOR 342, 347,367 & 358 ALL INDICATE
 THE USE OF SLIDING GLASS DOORS ONTO
 PATIO DECKS, PLANS DO NOT INDICATE (3) ITEMS THAT ARE
 CONCERNS TO FAIR HOUSING REQUIREMENTS FOR SLIDING GLASS
 DOORS (SECONDARY DOORS) THAT LEAD ONTO A IMPERVIOUS
 SURFACE.
 A) PLEASE PROVIDE A DETAIL INDICATING THE BOTTOM TRACK
 HEIGHT IN RELATIONSHIP TO THE INTERIOR FINISH FLOOR AND
 THE FINISH FLOOR OF THE PATIO ON THE EXTERIOR.
 B) PLEASE PROVIDE THE CLEAR OPENING SIZE FOR THE 6?-2?
 SLIDING GLASS DOORS.
 C) PROVIDE DETAILS FOR THE LATCHING MECHANISM FOR THE
 SLIDING GLASS DOOR.
  
  
 35) SHEET A-300 THE ELEVATOR LOBBY# 100 IT APPEARS THIS
 AREA MAY BE CONSIDERED EITHER A MEZZANINE OR ATRIUM,
 PLEASE PROVIDE THE AREA CALCULATIONS OF THE AND THE
 ADJOINING AREAS AND PLEASE DO SO FOR THE AREA ABOVE
 THAT HAS A 42? HANDRAIL. IT APPEARS THIS AREA MAY
 QUALIFY FOR BEING CONSIDERED A MEZZANINE. IF IT DOES
 NOT MEET THE QUALIFICATION BY AREA WE WILL THEN
 CONSIDER IT A 2 STORY ATRIUM AND THE ASSOCIATED
 REQUIREMENTS OF AN ATRIUM WITH THE EXCEPTION OF 404 FOR
 A 2 STORY ATRIUM.
  
 36) SHEET A-300 PLEASE SEE ROOMS 120 -123 IN EACH OF
 THESE ROOMS THERE IS A CHANGE OF GRADE,
 PLEASE SEE1003.5.2 WHERE CHANGE IN ELEVATION OF 12
 INCHES (305 MM) OR LESS OCCURS IN EXIT ACCESS
 CORRIDORS, EXITS AND EXIT DISCHARGE, RAMPS COMPLYING
 WITH SECTION 1010 SHALL BE PROVIDED. 1003.5.3
  
 37) SHEET A-300, THIS NOTE WILL BE COMMON TO ALL ??
 FLOOR PLANS, THESE SHEETS INDICATE THE WALL TYPES BUT
 NEGLECT TO IDENTIFY ALL DOORS. WHEN REVIEWING FOR WALL
 RATINGS IN SECTION 708 WE REVIEW ALSO FOR THE
 CORRESPONDINGOPENING PROTECTIVE IN SECTION 715 AND
 TABLE 715.3 PLEASE IDENTIFY BOTH ON THE SAME SHEET,
 ADDITIONAL INFORMATION REQUIRED, 106.1.2, IN COMPLYING
 WITH THIS REQUEST IT MAY SAVE THE CONTRACTOR &
 DEVELOPER TIME AND MONEY IN MISTAKES THAT MAY NOT OF
 BEEN CAUGHT IN PLAN REVIEW BUT CAUGHT IN INSPECTIONS IN
 THE CONSTRUCTION PHASE OF THE PROJECT.THIS IS
 SOMETHING WE TRY TO AVOID BUT THE HARDER IT IS TO FIND
 THE WALL AND ASSOCIATED DOOR RATINGS, MISTAKES CAN
 HAPPEN.
  
 38) SHEET A-300,STAIRWELL# 1, IS MISSING WALL I. D.
 TAGS ON VARIOUS WALLS REQUIRES 2 HR RATING, SECTION
 707.4.MISSING TAGSH.C. RESTROOM, TRASH TERMINATION
 ROOM WALL LEADING TO ELEVATOR LOBBY.
  
 39) THE SHEET A-905 INDICATES WALL TYPE AND UL NUMBERS
 ASSOCIATED WITH MASONRY WALLS.
 PLEASE PROVIDE LETTERS FROM THE BLOCK MANUFACTURER
 INDICATING THE MINIMUM EQUIVALENT THICKNESS FOR THE
 MASONRY UNITS. SECTION 721.3.8EQUIVALENT THICKNESS.
  
 40) SHEET A-300 TRASH TERMINATION ROOM, IT APPEARS
 THERE IS AN UNIDENTIFIED OBJECT IN THE UPPER LEFT HAND
 CORNER OF THIS ROOM. ADDITIONAL INFORMATION REQUIRED
 106.1.2.
  
 41) SHEET A-300/ A-202 THE TRASH COMPACTOR ROOMS DOOR
 146 IS MISSING THE FIRE RATING AND THE DOOR SCHEDULE
 INDICATES IT AS A TYPE ?E? LOUVER DOOR.710.5.1
 LOUVERS .
 DOORS IN SMOKE PARTITIONS SHALL NOT INCLUDE LOUVERS.
 707.13.4 TERMINATION ROOM.
  
 42) SHEET A-300/ A-202 BOTH FAIL TO INDICATE WALL
 RATINGS ON THE COMMON WALL TO THE S2 OCCUPANCY, THE
 DOOR SCHEDULE INDICATES A 45 MINUTE RATED DOOR E & F
 BOTH BEING LOUVERED DOORS. 710.5.1 LOUVERS . DOORS IN
 SMOKE PARTITIONS SHALL NOT INCLUDE LOUVERS.
  
 43)SHEET A-300/ A-202 FPL TRANSFORMER VAULT, PLEASE
 TAKE NOTE THAT FPL MAY HAVE HIGHER WALL RATING AND
 CEILING RATINGS THAN INDICATED. 106.1.2. ADDITIONAL
 INFORMATION REQUIRED.
  
 44) SHEET A-300/ A-202 BOTH INDICATE 2 ELEVATORS, SHEET
 A-701 INDICATES STAIR AND ELEVATOR SECTION PLAN NO
 PLANS INDICATE COMPLIANCE WITH STRETCHER REQUIREMENTS,
 PLEASE PROVIDE DETAIL.
 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.
 IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST
 ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE
 STRETCHERIN THE HORIZONTAL, OPEN POSITION AND SHALL
 BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED
 INSIDE ON BOTH SIDES OF THE HOIST WAY DOOR FRAME.
  
 45) SHEET A-300/ A-202 THE EGRESS PATH IN FRONT OF
 REFUSE TERMINATION ROOM, FIRE BOOSTER PUMP AND THE MAIN
 ELECTRIC ROOM ALL SWING INTO THE EGRESS PATHWAY. 1005.2
 DOOR ENCROACHMENT.
 DOORS OPENING INTO THE PATH OF EGRESS TRAVEL SHALL NOT
 REDUCE THE REQUIRED WIDTH TO LESS THAN ONE-HALF DURING
 THE COURSE OF THE SWING. WHEN FULLY OPEN, THE DOOR
 SHALL NOT PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH.
  
 46) SHEET A-202 STAIR TOWER# 2 WHEN YOU LEAVE THE 2
 HOUR RATED ENCLOSURE YOU ARE STILL UNDER THE BUILDING,
 AND DOES NOT QUALIFY FOR ANY EXEMPTION UNDER 1023.1
 GENERAL. EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR
 OF THE BUILDING. THE EXIT DISCHARGE SHALL BE AT GRADE
 OR SHALL PROVIDE DIRECT ACCESS TO GRADE. THE EXIT
 DISCHARGE SHALL NOT REENTER A BUILDING.PLANS ALSO
 INDICATE A 54"X96" LOUVER WHICH WOULD NOT MAKE ANY FIRE
 RATING OF THE EXTERIOR WALL THAT BACKS UP TO THE EXIT
 DISCHARGE OF THE STAIR TOWER.
  
 46) FL BLD CODE 1606.1.5: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTINGREPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED/ STOREFRONT
 B) WINDOWS OPERABLE
 C) MULLIONS
 D) EXTERIOR DOORS GLAZED, SLIDERS
 E) EXTERIOR LOUVERED DOORS
 F) DOORS STEEL
 G)EXTERIOR OVERHEAD DOORS
 H)HANDRAILS
 I) STORM SHUTTERS
 J) TRUSS ANCHORS
 K) ROOFING ASSEMBLIES
 L) PRE-MANUFACTURED A/C STANDS
 M) STORM SHUTTERS
  
 47) NOTE)) AN INTERPRETATION FROM THE BUILDING OFFICIAL
 ON STORM SHUTTERS THAT ARE USED ON LARGE PROJECTS:
 QUESTION# 13) RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME AND EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004 EDITION,
 PROVIDES THE ABILITY FOR THE BUILDING OFFICIAL TO
 IMPLEMENT REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF EXISTING BUILDINGS.
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE SAME PROPERTY,
 PRE-STORM PREPARATION PLANS MUST BE SUBMITTED BY THE
 PROPERTY OWNERS OR MANAGING AGENTS FOR REVIEW BY THE
 CONSTRUCTION SERVICES DEPARTMENT. ANY SUCH PLAN SHALL
 INCLUDE, AT A MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE SHUTTERS (SAID
 PARTIES MUST BE LOCATED WITHIN PALM BEACH COUNTY),
 TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND TOTAL TIME
 REQUIRED TO SECURE ALL OPENINGS. PROTECTION OF OPENINGS
 SHALL BE ACCOMPLISHED WITHIN TWELVE (12) HOURS OR LESS
 OF THE OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER
 SERVICE OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE BUILDING OFFICIAL
 TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION,
 ACCEPTANCE OF ALTERNATE MATERIALSAND METHODS MAY BE
 APPROVED ON A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO SUBSTANTIATE ANY CLAIM
 MADE REGARDING THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE
 FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES? NO, EXCEPT ON THE GROUND
 FLOOR. ON COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL, IMPACT RESISTANT
 GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE INSTALLED.
 PERMANENTLY AFFIXED PROTECTIVE DEVICES SHALL REQUIRE
 THE WRITTEN APPROVAL OF THE BUILDING OFFICIAL.
  
 48) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 48A) FL BLD CODE 2001 SECTION 1609.1.4, 1714.5
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 48B) PROVIDE ROOF PRESSURE ZONES FOR ZONES 4&5. SEE
 1609.1.1/ ASCE 7-02.
  
  
 49) SHEET A-650 SHOWS VARIOUS SUN SHADES, DETAIL 1& 5
 INDICATE THE USE OF CLOTH SUN SHADES, NOTE HOW YOU WILL
 MEET THE WIND REQUIREMENTS OF 3105.4.2.1 OR 3105.4.2.2.
 SHOP DRAWINGS MAY BE SUBMITTED AFTER PERMIT.
  
 50) PLEASE COMPLY WITH FIRE TREATED FABRIC FOR AWNINGS.
 3105.3.1FABRIC USED FOR AWNINGS OR FABRIC-COVERED
 FRAMES SHALL BE FLAME RESISTANT IN ACCORDANCE WITH NFPA
 701.
  
 51) SHEET A652 DETAIL# 06 PROVIDEPRODUCT TESTING
 REPORT FOR EXHAUST FAN AND PRE-MANUFACTURED CURB,
 PROVIDE THE +/- PRESSURES THIS ASSEMBLY HAS BEEN TESTED
 FOR.
 1609.6. 1.2 COMPONENTS & CLADDING.
  
 52) SHEET A-652 DETAILS 24 & 26 BOTH SHOW RAIN WATER
 LITER DETAILS, THESE ARE GOING TO BE PLACED IN 1 HR
 FIRE RATED CORRIDORS, BUT THERE IS ONLY 1 LAYER OF
 DRYWALL AROUND THE PIPE, PLEASE PROVIDE UL RATING OR
 SOME OTHER APPROVED AGENCY THAT THIS IS A 1 HR FIRE
 RATED SYSTEM. TABLE 1016.1.
  
 53)SHEETS A801-A801E ALL INDICATE A DOOR D-11 BUT NOT
 FOUND ON THE DOOR SCHEDULE
 A-903. PLEASE PROVIDE ADDITIONAL INFORMATION, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 54) SHEET A801 TH1A UNITS (2STORY CONDOS) THE GROUND
 FLOOR OF THESE UNITS STILL HAVE TO COMPLY WITH FAIR
 HOUSING, DOOR D-1 IS A 2?-6? DOOR AND BY DEFINITION A
 USEABLE DOOR A NOMINAL 32? CLEAR.
  
 55) SHEET A801 TH1A UNITS THERE ARE DOORS ON THE FIRST
 FLOOR AND ALSO THE 2ND FLOOR LOFT PORTION OF THE UNIT
 THAT BOTH HAVE EXTERIOR DOORS LEADING TO BALCONIES AND
 DO NOT HAVE A DOOR IDENTIFICATION MARKER. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 56) SHEET A801B-E TH1B-E UNITS(2STORY CONDOS) THE
 GROUND FLOOR OF THESE UNITS STILL HAVE TO COMPLY WITH
 FAIR HOUSING, DOOR D-1 IS A 2?-6? DOOR AND BY
 DEFINITION A USEABLE DOOR A NOMINAL 32? CLEAR.
  
 57) SHEET A801B-E TH1B-E UNITS THERE ARE DOORS ON THE
 FIRST FLOOR AND ALSO THE 2ND FLOOR LOFT PORTION OF THE
 UNIT THAT BOTH HAVE EXTERIOR DOORS LEADING TO BALCONIES
 AND DO NOT HAVE A DOOR IDENTIFICATION MARKER. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 58) SHEET A802- A802C (2STORY CONDOS) THE GROUND FLOOR
 OF THESE UNITS STILL HAVE TO COMPLY WITH FAIR HOUSING,
 DOOR D-1 IS A 2?-6? DOOR AND BY DEFINITION A USEABLE
 DOOR A NOMINAL 32? CLEAR.
  
 59) SHEET A802-A802C THE DOORS ON THE FIRST FLOOR AND
 ALSO THE 2ND FLOOR LOFT PORTION OF THE UNIT THAT BOTH
 HAVE EXTERIOR DOORS LEADING TO BALCONIES AND DO NOT
 HAVE A DOOR IDENTIFICATION MARKER. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 60) SHEET A-803 FRONT ENTRY DOOR, AGAIN THIS DOOR IS
 NOT LISTED ON THE DOOR SCHEDULE, THIS FRONT ENTRY DOOR
 IS IN A FIRE RATED WALL BEING BETWEEN A S2 OCCUPANCY
 AND R2 OCCUPANCY, THIS DOOR WILL NEED A CLOSER AND
 LATCH AS WELL AS FIRE RATING, PLEASE SEE ANSI A117.1-
 98 DOOR CLEAR WIDTH 404.2.3 AND MINIMUM CLEARANCES SEE
 FIGURE 404.2.4.1(B)REQUIRES 12 INCHES WHERE BOTH A
 DOOR CLOSER AND LATCH ARE PROVIDED. ALSO FBC TABLE
 715.3, COMMON TO ALL UNITS.
  
 61) SHEET A-803A- A-803B BOTH ARE MISSING INFORMATION
 ON THE FRONT DOOR AS WELL AS THE SECONDARY DOOR LEADING
 TO THE BALCONY, PLEASE SEE COMMENT ABOVE NUMBER 60 ALSO
 RELATES, 106.1.2 ADDITIONAL INFORMATION REQUIRED. ALSO
 SEE TABLE 715.3.
  
 62)SHEET A-804A- A-804HTHE FRONT DOOR AND BALCONY
 DOORS DO NOT HAVE IDENTIFICATION TAGS INDICATING THEIR
 SIZE AND OR FIRE RATING. FAIR HOUSING ACCESSIBLE DOORS
 AND FBC TABLE 715.3.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 63) SHEET A-804D AT BEDROOM NUMBER 2 ON THE BALCONY
 THERE APPEARS TO BE A LINE INDICATING A CHANGE IN
 GRADE, 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 64) SHEET A-801 SERIES IS MISSING THE DIMENSION BETWEEN
 DOORS IN THE VESTIBULE, FAIR HOSING
 ANSI 4.13 MINIMUM SPACE BETWEEN DOORS IN SERIES 4?-0?
 PLUS DOOR WIDTH IF SWINGS IN.
 PROVIDE DIMENSION.
  
 65) SHEET A-805, A-806, A-807 & A-807A ALL NEED TO
 PROVIDE THE CLEAR OPENING WIDTH FOR THE 6?-0? SLIDING
 GLASS DOORS FOR SECONDARY DOORS MINIMUM OF 32? CLEAR,
 SEE FAIR HOUSING
 404.2.3 (B).
  
 66) SHEET A-903 DOOR NOTES, HURRICANE MISSILE IMPACT
 NOTES, FRENCH DOORS TO COMPLY WITH
 COMMENT 47 & 48A.
  
 67) SHEET A-903 BURGLAR INTRUSION NOTES (3), INDICATES
 THE USE OF PINS FOR EXTRA SECURITY DEVICES, SEE FAIR
 HOUSING SECONDARY EXTERIOR DOORS SLIDING GLASS DOORS
 PAGE 3.10-3.12 CLEAR WIDTH AND HARDWARE REQUIREMENTS
 AND RECOMMENDATIONS.
  
 68)SHEET A-903 BURGLAR INTRUSION NOTE NUMBER (7),
 INACTIVE LEAF OF A PAIR OF DOORS SHALL BE PROVIDED WITH
 MULTIPLE POINT LOCKS AS REQUIRED BY THE PRODUCT
 APPROVALS. AGAIN THESE LOCKS HAVE TO BE ABLE TO OPERATE
 FROM A WHEELCHAIR.ANSI A117.1-98, 404.2.7.
  
 69) SHEET S4.5 DETAIL SECTION 5-4.5 INDICATES USE OF
 5/8? EXTERIOR GRADE PLYWOOD PLEASE SEE
 TABLE 601 FOOTNOTE ( C ) (2) WHEN FIRE TREATED PLYWOOD
 CAN AND CAN NOT BE USED. THIS BUILDING IS CLASSIFIED AS
 A TYPE IB BUILDING.
  
 70) ?S? SHEETS THE SEAL IS NOT EMBOSSED TO WHERE IT IS
 LEGIBLE AND OR SOME SHEETS ARE NOT SEALED AT ALL. THE
 EMBOSSED SEAL SHALL BE LEGIBLE 61G15-23.002.
  
 71) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  