| Date |
Text |
| 2007-10-06 16:49:08 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | WPB MUNICIPAL CODE |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT IS REQUIRED IN THE TITLE |
| | BLOCK OF EACH SHEET. FAC 61G1-16.004(6) & FS 481.2055. |
| | PLEASE SHOW PRINTED NAME IN TITLE BLOCK OF EACH SHEET. |
| | |
| | 2. SHT A-002 BUILDING #4 DATA. THE BUILDING CODE |
| | EDITION IS SHOWN AS 2001 FBC. THE CODE IN EFFECT IS THE |
| | FBC-2004. PLEASE CORRECT CODE REFERENCE. |
| | |
| | 3. SHT A-200 BUILDING #4 DATA. ONE INTENDED USE |
| | ACCESSORY OCCUPANCY IS INDICATED AS MERCANTILE RETAIL |
| | AREA. PLEASE INDICATE THE LOCATION OF THE RETAIL AREA. |
| | SECTION 106.1.1. |
| | |
| | 4. SHT A-003 DETAIL E. THE CLEAR FLOOR SPACE FOR THE |
| | LAV IS NOT SHOWN. PLEASE SHOW CLEAR FLOOR SPACE AS |
| | INDICATED ON PAGE 7.47. |
| | |
| | 5. SHT A-0003A DETAILS A & B. THE WATER CLOSET CAN NOT |
| | BE IN THE CLEAR FLOOR SPACE REQUIRED FOR THE LAV, |
| | (DETAIL A), OR SHOWER, (DETAIL B). PLEASE SHOW |
| | COMPLIANCE WITH THE CLEAR FLOOR SPACE REQUIREMENTS. |
| | |
| | 6. SHT A-104 ROOF DRAIN CALCULATIONS. NO MENTION OF THE |
| | CONTRIBUTION FROM THE ROOF AREA ABOVE DRAINING ONTO THE |
| | ROOF AREAS. SECTION 1106.3. PLEASE SHOW THE UPPER ROOF |
| | CONTRIBUTION IN THE CALCULATIONS FOR THE ROOF/DECK |
| | DRAINS. |
| | |
| | 7. SHT A-104 ROOF DRAIN CALCULATIONS. AREA "C" SCALES |
| | OUT TO BE ROUGHLY 15FT SHORTER THAN AREAS "D & E", BUT |
| | SHOWS MORE TOTAL AREA. PLEASE CLARIFY. SECTION 106.1.1. |
| | IS THERE MORE VERTICAL SF OR UPPER ROOF AREA? |
| | |
| | 8. SHT A-104 AREAS "D & E" SCALE OUT TO BE |
| | APPROXIMATELY THE SAME LENGTH, BUT AREA "E" IS |
| | INDICATED AS ABOUT TWICE THE AREA. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 9. SHT A-104. AREA "F" SHOWS NO CALCULATIONS FOR THE |
| | PRIMARY AND SECONDARY ROOF DRAINS. PLEASE SHOW |
| | CALCULATIONS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. SHOW THE SQUARE FOOTAGE OF THE ROOF AREA, |
| | WITH 1/2 THE AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS AS WELL AS THE AREA FROM THE UPPER ROOF THAT |
| | DRAINS ONTO THE ROOF FROM ABOVE. |
| | |
| | 10. SHT A-104 CALCULATIONS ARE REQUIRED FOR THE OUTDOOR |
| | LIVING PATIO & DECK DRAINS. SHOW THE SQUARE FOOTAGE OF |
| | THE DECK AREA AND SHOW 1/2 AREA OF ALL VERTICAL WALLS |
| | AND INDICATE THE SQUARE FOOT AREA OF THE ROOFS THAT |
| | DRAIN ONTO THE DECK AREA FROM ABOVE. SECTIONS 1106 & |
| | 1107 AND ALL SUBSECTIONS. |
| | |
| | 11. SHT A-104 SHOW THE LOCATIONS FOR ALL SECONDARY |
| | DRAINAGE ON THE DECK. INDICATE ALL AREAS THAT DRAIN OFF |
| | THE SIDE OF THE BUILDING IF ANY. |
| | |
| | 12. SHT A-104 THE LOCATIONS OF THE DECK DRAINS IN THE |
| | OUTDOOR LIVING PATIO & DECK DRAINS ARE APPROXIMATELY |
| | 6FT FROM THE SLIDING GLASS DOOR, BUT THE DISTANCE TO |
| | THE AREA WHERE THE OVERFLOW LEAVES THEPATIO AREA IS |
| | APPROXIMATELY 11FT. IS THERE ANY CONCERN THAT THE STORM |
| | WATER WILL ENTER THE UNIT BEFORE THE STORM WATER |
| | REACHES THE OVERFLOW AREA? PLEASE CLARIFY. SECTION |
| | 106.1.2. (MORE INFORMATION REQUIRED). |
| | |
| | 13. SHT A-104 THERE ARE ABOUT FIVE PLANTER DRAINS THAT |
| | RECIEVE THE WATER OF THE VERTICAL WALL FROM THE ROOF |
| | AREA. WHEN INDICATING THE SQUARE FOOTAGE BEING DRAINED |
| | BY THESE PLANTER DRAINS, PLEASE SHOW 1/2 THE AREA OF |
| | THE VERTICAL WALLS INCLUDED IN THE TOTAL SQUARE |
| | FOOTAGE. SECTION 1106.4. |
| | |
| | 14. SHT A-108 THE ROOF DRAINS DO NOT APPEAR TO BE |
| | LOCATED AT THE LOW POINT OF THE ROOF. THE LOW AREA FOR |
| | AREA"G" APPEARS TO BE IN THE ELEVATOR MACHINE ROOM. |
| | NO SLOPE INDICATION IS SHOWN FOR AREA "F" PLEASE |
| | CLARIFY. SECTION 106.1.1. ELEVATIONS SHALL BE SUBMITTED |
| | FOR ALL AREAS OF THE ROOF TO VERIFY IF THE ROOF DRAINS |
| | ARE IN THE LOWEST POINT OF THE ROOF. |
| | |
| | 15. SHTS A-205 & A-206 SHOW THE SECONDARY DRAINS FOR |
| | ALL AREAS PER SECTION 1107. |
| | |
| | 16. SHT A-206 SHOW COMPLIANCE FOR THE TOILET ROOMS. |
| | (337 & 338). |
| | ____W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | ____URINAL |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | ____LAVS |
| | A.11-4.19.3 CLEAR FLOOR SPACE |
| | ____TOILET ROOMS |
| | A. 11-4.22.3 SHOW THE 5' TURNING AREA IN THE TOILET |
| | ROOM, ITS NOT REQUIRED IN STALL |
| | |
| | 17. SHT A-907 FINISH SCHEDULE INDICATES PAINT ON GWB |
| | FOR THE ADCP TOILET ROOM, MEN'S TOILET ROOM & WOMEN'S |
| | TOILET ROOM. SECTION 1210.2 REQUIRES THE WALL WITHIN |
| | 2FT OF WATER CLOSETS OR URINALS TO HAVE A "SMOOTH, |
| | HARD, NONABSORBENT" SURFACE. PAINTED GWB DOES NOT MEET |
| | THE "HARD" REQUIREMENT OF THE CODE SECTION. PLEASE SHOW |
| | COMPLIANCE. |
| | |
| | 18. ALL CIVIL SHEETS ARE NOT SIGNED, SEALED OR DATED AS |
| | REQUIRED PER SECTION 106.1 AND FAC 61G15-23.002(2) & FS |
| | 472.025. PLEASE SIGN, SEAL AND DATE ALL SHEETS. |
| | |
| | 19. SHTS CS-2 & A-001B. THE PRINTED NAME OF THE PERSON |
| | SIGNING & SEALING THE DOCUMENT IS REQUIRED ON EACH |
| | SHEET. FAC 61G1-16.004(6) & FS 481.2055. |
| | |
| | 20. ALL ENGINEERED SHEETS SHALL BE DATED PRIOR TO PLANS |
| | BEING ISSUED. THE DATE THE SEAL AND SIGNATURE ARE |
| | AFFIXED TO THE DOCUMENTS SHALL BE ENTERED ON THE PLANS, |
| | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. FAC |
| | 61G15-23.002(1)(2) & FS 471.025. |
| | |
| | 21. SHT P0.1 PLUMBING LEGEND. ALL WATER LINES ARE SOLID |
| | LINES WITH NO DIFFERENCES. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 22. SHT P2.1.1 KEY NOTES 1 & 3. PLEASE INDICATE THE |
| | SYSTEM FOR THESE LINES. (STORM, CONDENSATE)? SECTION |
| | 106.1.1. |
| | |
| | 23. SHT P2.1.1 SHOW THE CLEANOUTS REQUIRED IN THE STORM |
| | DRAINAGE LINES PER SECTION 1101.8. |
| | |
| | 24. SHT P2.1.1 INDICATE THE UNIT NUMBERS FOR EACH |
| | TOWNHOUSE UNIT. SECTION 106.1.2. |
| | |
| | 25. SHT P2.1.1 INDICATE THE RISER NUMBERS FOR EACH |
| | TOWNHOUSE UNIT. (TH3(A), TH3(B), TH3(C) ETC). SECTION |
| | 106.1.2. |
| | |
| | 26. SHT P2.1.1 RISER DESIGNATION FOR CONDENSATE RISER |
| | IS NOT LEGIBLE. SECTION 106.1.1. PLEASE MAKE SURE ALL |
| | RISERS ARE LEGIBLE. |
| | |
| | 27. SHT P2.1.1 8" POOL DRAIN & 4" JACUZZI SPA DRAIN |
| | SHALL CONNECT TO THE STORM, NOT THE SANITARY. PLEASE |
| | SHOW DRAINS CONNECTING TO STORM. |
| | |
| | 28. SHT P2.1.1 SHOW ALL RISER NUMBERS FOR THE STORM |
| | RISERS. (RWL-1, RWL-2 OR SD-1, SD-2 ETC). SECTION |
| | 106.1.1. |
| | |
| | 29. SHT P2.1.1A CONDENSATE RISER IS INDICATED AS 1/2" |
| | RISER. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 30. SHT P2.1.1 CONDENSATE RISER #1&2 AND SANT. RISER #1 |
| | ARE SHOWN IN A STEM WALL. SECTION 1906.3 CONDUITS AND |
| | PIPES EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. |
| | |
| | 31. SHT P2.1.1 IDENTIFY THE SYSTEM SHOWN TO THE RIGHT |
| | OF CATCH BASIN #2 INDICATED BY THE NOTE "UP TO 2ND |
| | FLOOR". SECTION 106.1.1. |
| | |
| | 32. SHT P2.1.2 SHOW ALL RISER NUMBERS FOR THE STORM |
| | RISERS. (RWL-1, RWL-2 OR SD-1, SD-2 ETC). SECTION |
| | 106.1.2. |
| | |
| | 33. SHT P2.1.2 SANT. RISER #8 IS SHOWN IN COLUMN AND |
| | UNDER THE SHEAR WALL. SECTION 1906.3 CONDUITS AND PIPES |
| | EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION |
| | 305.3 SLEEVES MAY BE REQUIRED. |
| | |
| | 34, SHT P2.1.2 THE SANITARY BUILDING DRAIN IS SHOWN IN |
| | AND UNDER COLUMNS. SECTION 1906.3 CONDUITS AND PIPES |
| | EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION |
| | 305.3 SLEEVES MAY BE REQUIRED. |
| | |
| | 35. SHT P2.1.2 SANITARY RISERS 21 & 25 ARE SHOWN IN |
| | COLUMNS. SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN |
| | CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION |
| | 305.3 SLEEVES MAY BE REQUIRED. |
| | |
| | 36. SHT P2.1.2 CLEANOUTS ARE REQUIRED IN THE STORM |
| | STYTEM PER SECTION 1101.8. PLEASE SHOW ON FLOOR PLAN TO |
| | REFLECT THE RISER DIAGRAM. |
| | |
| | 37. SHT P2.1.2 THE WASH MACHINE IS INDICATED BEYOND THE |
| | LAV IN "TH" UNIT BETWEEN SANT. RISERS 22 & 25. ALSO |
| | SHOWN ON THE RISER DIAGRAM. PLEASE CLARIFY AS THE W/M |
| | SEEMS TO BE LOCATED BY KITCHEN, NOT IN THE CLOSET NEXT |
| | TO THE POWDER ROOM. SECTION 106.1.1. |
| | |
| | 38. SHT P2.1.2 CONDENSATE RISER 17/18 IS SHOWN |
| | CONNECTING TO THE STORM LINE. PLEASE CLARIFY. |
| | CONDENSATE SHALL DISCHARGE OUTSIDE THE BUILDING |
| | SEPARATELY. |
| | |
| | 39. SHT P2.1.2 CONDENSATE FITTING SHALL GUIDE WASTE IN |
| | THE DIRECTION OF FLOW. SECTION 706.3. SEE FITTING NEAR |
| | SANT. RISER 26. CORRECT FITTING TO GUIDE WASTE IN THE |
| | DIRECTION OF FLOW. |
| | |
| | 40. SHT P2.1.2 THE CONDENSATE LINE APPEARS TO RUN THRU |
| | CATCH BASIN #3. PLEASE CLAIRFY. SECTION 106.1.1. |
| | |
| | 41. SHT P2.1.2 NO KEY NOTES 1, 2 OR 3 INDICATED ON |
| | SHEET. PLEASE INDICATE WHAT ITEMS (1)(2)(3) REPRESENT. |
| | IDENTIFY SYSTEMS FOR KEY NOTES 1 & 3. SECTION 106.1.2. |
| | |
| | 42. SHT P2.1.2 INDICATE THE UNIT NUMBER FOR EACH |
| | TOWNHOUSE UNIT. SECTION 106.1.2. |
| | |
| | 43. SHT P2.2.1 SANT. RISER #5 IS SHOWN IN A COLUMN. |
| | SECTION 1906.3 CONDUITS AND PIPES EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION |
| | 305.3 SLEEVES MAY BE REQUIRED. |
| | |
| | 44. SHT P2.2.1 INDICATE THE UNIT NUMBER FOR EACH |
| | TOWNHOUSE UNIT. SECTION 106.1.2. |
| | |
| | 45. SHT P2.2.1 INDICATE THE RISER NUMBERS FOR THE |
| | TOWNHOUSES. (TH3(A)(B)(C) OR (D). SECTION 106.1.2. |
| | |
| | 46. SHT P2.2.1 INDICATE STORM RISER NUMBERS. (RWL-1, |
| | RWL-2 OR SD-1, SD-2 ETC). SECTION 106.1.2. |
| | |
| | 47. SHT P2.2.1 THE SANITARY RISER UP TO 3RD FLOOR SINK |
| | SHALL NOT DRAIN THROUGH THE HORIZONTAL WET VENT OF THE |
| | BATHROOM FIXTURES. SECTION 909.1. THE SINK SHALL |
| | DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP. |
| | |
| | 48. SHT P2.2.2 THE SHEET IDENTIFICATION INDICATES 2ND |
| | FLOOR "SOUTH". ALL PREVIOUS SHEETS ARE IDENTIFIED AS |
| | "EAST" OR "WEST" PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 49. SHT P2.2.2 SANT. RISER #23 IS NOT SHOWN ON THE |
| | FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1. PLEASE |
| | SHOW THE LOCATION OF SANT. RISER #23. |
| | |
| | 50. SHT P2.2.2 CONDENSATE RISER 17/18IS NOT SHOWN ON |
| | THE FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1. PLEASE |
| | SHOW THE LOCATION OF COND. RISER 17/18. |
| | |
| | 51. SHT P2.2.2 SANT. RISERS 21 & 25 ARE NOT SHOWN ON |
| | THE FLOOR PLAN. ARE THEY RUN IN THE COLUMNS? IF SO |
| | PLEASE COMPLY WITH SECTION 1906.3. IF NOT SHOW THE |
| | LOCATION OF THE RISERS. SECTIONS 106.1.2 & 106.1.1. |
| | |
| | 52. SHT P2.2.2 SANT. RISER 15 AND RISER DESIGNATION ARE |
| | NOT SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY. SECTION |
| | 106.1.1. PLEASE SHOW THE LOCATION OF SANT. RISER 15. |
| | |
| | 53. SHT P2.2.2 INDICATE STORM RISER NUMBERS FOR EACH |
| | RISER. (RWL-1, RWL-2 OR SD-1, SD-2 ETC). SECTION |
| | 106.1.2. |
| | |
| | 54. SHT P2.2.2 IDENTIFY THE SYSTEM WITH THE "OD LINE |
| | DOWN/UP". SECTION 106.1.2. |
| | |
| | 55. SHT P2.3.1 THE CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINAGE ON SHT A-104 AREAS "A" THRU "E" |
| | DO NOT REFLECT WHAT IS SHOWN ON THE ROOF PLANS FOR |
| | THOSE AREAS. PLEASE CLARIFY. RECHECK THE TOTAL SQUARE |
| | FOOTAGE BEING DRAINED IN EACH AREA. SECTION 1106 & |
| | TABLE 1106.3. |
| | |
| | 56. SHT P2.3.1 SHOW THE LOCATION OF ALL REQUIRED |
| | SECONDARY DRAINS FOR THE DECK AREA. SECTION 1107 WITH |
| | ALL SUBSECTIONS & TABLES. |
| | |
| | 57. SHT P2.3.1 A RELIEF VENT IS REQUIRED FOR THE AIR |
| | ADMITTENCE VALVE AT THE PAVILLION SINK. SECTION |
| | 917.3.2. PLEASE SHOW ON THE FLOOR PLAN AND THE RISER |
| | DIAGRAM. |
| | |
| | 58. SHT P2.3.1 SUBMIT THE INVERT ELEVATIONS FOR THE |
| | STORM PIPING FOR THE ROOFS OF RETAIL UNITS AND AT THE |
| | POINT WHERE THEY TURN DOWN TO THE FLOOR BELOW. SECTION |
| | 106.1.2. ALSO INCLUDE THE ELEVATION OF THE PARKING |
| | GARAGE BELOW THE PIPING. |
| | |
| | 59. SHT P2.3.1 IDENTIFY AND SHOW THE SQUARE FOOTAGE |
| | BEING DRAINED BY ALL DRAINS. SECTIONS 106.1.1, 1106 |
| | WITH ALL SUBSECTIONS & TABLES. |
| | |
| | 60. SHT P2.3.1 IDENTIFY SYSTEM & PIPING IN THE POOL |
| | EQUIPMENT ROOM. (SHOWN AS DD ON SHT A-205). SECTION |
| | 106.1.2. |
| | |
| | 61. SHT P2.3.1 THE SQUARE FOOTAGE FOR THE PATIOS |
| | OUTSIDE THE CONDO UNITS DOES NOT APPEAR TO BE CORRECT. |
| | (EXAMPLE THE DRAIN BY UNIT C-5A 320 SHOWS DD 900 SF. |
| | SCALING SHOWS APPROX 1,015 SF NOT COUNTING 1/2 VERTICAL |
| | WALLS TO ROOF LEVEL PLUS THE UPPER ROOF CONTRIBUTION |
| | DRAINING ONTO THE PATIO AREA. PLEASE CLARIFY. SECTION |
| | 1106.3 & TABEL 1106.3. |
| | |
| | 62. SHT P2.3.1 THE RISER BY STAIR #3 IS NOT LEGIBLE. |
| | SECTION 106.1.1. PLEASE CLARIFY. |
| | |
| | 63. SHT P2.3.1 EXTRA RISER INDICATORS ARE SHOWN ON |
| | RISER 2, (2) (BY W/C & LAV),RISER 3, (1) (BY LAV) & |
| | RISER 4, (1) (BY LAV). PLEASE INDICATE WHAT THE RISERS |
| | ARE INDICATED FOR. SECTION 106.1.1. |
| | |
| | 64. SHT P2.3.1 THERE ARE 2 SANITARY LINES THRU COLUMNS. |
| | UNITS C-2 (317)(319). SECTION 301.2 & SECTION 1906.3 |
| | CONDUITS AND PIPES EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION |
| | 305.3 SLEEVES MAY BE REQUIRED. |
| | |
| | 65. SHT P2.3.2 SANT RISER 13 SHOWS A FLOOR DRAIN UNDER |
| | THE ROOF IN WHAT APPEARS TO BE OUTSIDE THE BUILDING. |
| | MORE INFORMATION IS REQUIRED. PLEASE INDICATE WHAT WILL |
| | BE DRAINED. SECTION 106.1.2. |
| | |
| | 66. SHT P2.3.2 IDENTIFY ALL DRAINS IN THE DECK AREA AND |
| | SHOW THE SQUARE FOOTAGE BEING DRAINED BY EACH DRAIN. |
| | SECTION 106.1.2. |
| | |
| | 67. SHT P2.3.2 NO SQUARE FOOTAGE IS SHOWN FOR AREA "F" |
| | OF THE LOWER ROOF AREA. PLEASE SUBMIT CALCULATIONS FOR |
| | THE DRAINS OF AREA "F" SHOWING THE SQUARE FOOTAGE OF |
| | THE ROOF AREA, 1/2 AREA OF VERTICAL WALLS INCULDING |
| | PARAPETS, AND ROOF AREAS THAT DRAIN ONTO THE ROOF FROM |
| | ABOVE IN THE CALCULATION. SECTION 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. |
| | |
| | 68. SHT P2.3.2 THE WASTE ARMS TO THE LAVS IN UNITS C-1, |
| | (326), & C-1, (332), ARE NOT SHOWN AT THE FIXTURE. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 69. SHT P2.3.2 ONLY ONE RISER 20 SHOWN AT THE W/M, |
| | WHEREAS TWO RISERS ARE SHOWN ON THE RISER DIAGRAM. |
| | SECTION 106.1.1. PLEASE HAVE THE FLOOR PLAN AND RISER |
| | DIAGRAM REFLECT. |
| | |
| | 70. SHT P2.3.2 THE SANITARY RISER NUMBER FOR THE DOUBLE |
| | LAV IN UNIT C1B (315) IS MISSING. SECTION 106.1.1. |
| | PLEASE INDICATE RISER NUMBER. |
| | |
| | 71. SHT P2.4.1 THE SANITARY RISER NUMBER IS MISSING |
| | BEHIND THE TUB IN UNIT C-4 (418). SECTION 106.1.1. |
| | PLEASE INDICATE RISER NUMBER. |
| | |
| | 72. SHT P2.4.1 INDICATE THE STORM RISER NUMBERS FOR |
| | EACH STORM RISER. SECTION 106.1.2. |
| | |
| | 73. SHT P2.4.1 SANITARY LINES ARE SHOWN RUNNING THRU |
| | COLUMNS. SECTION 301.2 & SECTION 1906.3 CONDUITS AND |
| | PIPES EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION |
| | 305.3 SLEEVES MAY BE REQUIRED. |
| | |
| | 74. SHT P2.4.2SANITARY RISER 13 SHOWS A FLOOR DRAIN |
| | THAT APPEARS TO BE OUTSIDE THE BUILDING. MORE |
| | INFORMATION IS REQUIRED. PLEASE INDICATE WHAT WILL BE |
| | DRAINED. SECTION 106.1.2. |
| | |
| | 75. SHT P2.4.2 SHEET IDENTIFICATION IS SHOWN AS 4TH |
| | FLOOR "SOUTH" PREVIOUS SHEETS WERE INDICATED AS "EAST" |
| | & "WEST". PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 76. SHT P2.4.2 THE WASTE ARM FOR THE LAV IS NOT SHOWN |
| | AT THE FIXTURE IN UNIT C1 (430). PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 77. SHT P2.4.2 INDICATE THE STORM RISER NUMBERS FOR |
| | EACH STORM RISER. SECTION 106.1.2. |
| | |
| | 78. SHT P2.5.1 SHOW THE RISER NUMBERS FOR THE |
| | CONDENSATE RISERS. SECTION 106.1.2. |
| | |
| | 79. SHT P2.5.1 SHOW THE STORM RISER NUMBERS FOR EACH |
| | STORM RISER. SECTION 106.1.2. |
| | |
| | 80. SHT P2.5.2 SANITARY RISER 13 SHOWS A FLOOR DRAIN |
| | THAT APPEARS TO BE OUTSIDE THE BUILDING. MORE |
| | INFORMATION IS REQUIRED. PLEASE INDICATE WHAT WILL BE |
| | DRAINED. SECTION 106.1.2. |
| | |
| | 81. SHT P2.5.2 INDICATE THE STORM RISER NUMBERS FOR |
| | EACH STORM RISER. SECTION 106.1.2. |
| | |
| | 82. SHT P2.5.2 THE SANITARY RISER NUMBER FOR RISER |
| | BEHIND THE LAV IN UNIT C1 (524) IS MISSING. PLEASE SHOW |
| | RISER NUMBER. SECTION 106.1.1. |
| | |
| | 83. SHT P2.6.1 INDICATE THE STORM RISER NUMBERS FOR |
| | EACH STORM RISER. SECTION 106.1.2. |
| | |
| | 84. SHT P2.6.2 INDICATE THE STORM RISER NUMBERS FOR |
| | EACH STORM RISER. SECTION 106.1.2. |
| | |
| | 85. SHT P2.6.2 THE WASTE ARM IS NOT SHOWN AT THE LAV |
| | FIXTURE IN UNIT C1 (730). PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 86. SHT P2.6.2 SANITARY RISER 13 SHOWS A FLOOR DRAIN |
| | THAT APPEARS TO BE OUTSIDE THE BUILDING. MORE |
| | INFORMATION IS REQUIRED. PLEASE INDICATE WHAT WILL BE |
| | DRAINED. SECTION 106.1.2. |
| | |
| | 87. SHT P2.6.2 THE SANITARY RISER NUMBER IS MISSING BY |
| | THE LAV IN UNIT C1 (724). PLEASE SHOW RISER NUMBER. |
| | SECTION 106.1.2. |
| | |
| | 88. SHT P2.7.1 ROOF DRAINS DO NOT APPEAR TO BE LOCATED |
| | AT THE LOW POINT OF THE ROOF. PLEASE SUBMIT ELEVATIONS |
| | AT DIFFERENT AREAS OF THE ROOF SHOWING THE LOW POINTS |
| | AND THE HIGH POINTS OF THE ROOF TO VERIFY PROPER |
| | DRAINAGE TO THE ROOF DRAINS. SECTION 106.1.2. |
| | |
| | 89. SHT P2.7.2 ROOF DRAINS DO NOT APPEAR TO BE LOCATED |
| | AT THE LOW POINT OF THE ROOF. PLEASE SUBMIT ELEVATIONS |
| | AT DIFFERENT AREAS OF THE ROOF SHOWING THE LOW POINTS |
| | AND THE HIGH POINTS OF THE ROOF TO VERIFY PROPER |
| | DRAINAGE TO THE ROOF DRAINS. SECTION 106.1.2. |
| | |
| | 90.SHT P2.7.2 SANITARY RISER VTR #14 SHALL NOT BE |
| | LOCATED IN THE STAIRWELL. NFPA 101 SECTION |
| | 7.1.3.2.1(6). PLEASE OFFSET OUT OF STAIRWELL. |
| | |
| | 91. SHT P2.7.2 SANITARY RISER VTR #17 IS SHOWN UNDER |
| | CCC-3. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS FOR |
| | THIS UNIT TO MAKE SURE THERE IS NO AIR INTAKE OR OTHER |
| | REQUIREMENTS PROHIBITING THE VENT FROM BEING UNDER THIS |
| | UNIT. SECTION 106.1.2. |
| | |
| | 92. SHT P2.7.2 ROOF AREA "F" SHOWS NO SLOPE TO DRAIN. |
| | PLEASE INDICATE SLOPE TO ROOF DRAIN. SECTION 106.1.2. |
| | |
| | 93. SHT P2.7.2 ROOF AREA "G" ROOF DRAIN AND OD NOT |
| | LABELED. PLEASE INDICATE WHICH IS THE ROOF DRAIN AND |
| | WHICH IS THE OD. SECTION 106.1.1. |
| | |
| | 94. SHT P2.7.2 PLAN NOTES (1) DOES NOT SHOW PIPING TO |
| | THE ROOF DRAIN. PLEASE CLAIRFY AS NOTE INDICATES |
| | PIPING. SECTION 106.1.1. |
| | |
| | 95. SHT P2.7.2 PLAN NOTES (3) &(4). MORE INFORMATION IS |
| | REQUIRED. WHAT DRAINS FROM CCC-1, CCC-2 & CCC-3. IF THE |
| | DRAINAGE IS CONDENSATE, THEN IT SHALL NOT DRAIN INTO |
| | THE SANITARY SYSTEM. ARTICLE III SECTION 90-125(5)-- |
| | PLEASE INDICATE WHAT DRAINS FROM THE UNITS AND IF IT |
| | SHALL INDEED DRAIN INTO THE SANITARY SYSTEM, THEN |
| | SUBMIT A DETAIL SHOWING HOW STORM WATER WILL NOT DRAIN |
| | INTO THE FUNNEL DRAIN. SECTION 106.1.2. |
| | |
| | 96. SHT P3.1.2 INDICATE THE MATERIAL USED FOR THE 3" |
| | UNDERGROUND WATER SERVICE TO THE PUMP ROOM. MATERIAL |
| | SHALL COMPLY WITH TABLE 605.3 AND SECTION 605.3. |
| | |
| | 97. SHT P3.2.1 SHOWS THE HOT & COLD WATER LINES THRU A |
| | COLUMN. SLEEVES MAY BE REQUIRED, AND PER SECTION 1906.3 |
| | CONDUITS AND PIPES EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION |
| | 305.3 SLEEVES MAY BE REQUIRED. |
| | |
| | 98. SHT P3.2.2 WATER RISER 13 IS SHOWN THRU A COLUMN. |
| | SLEEVES MAY BE REQUIRED. PER SECTION 1906.3 CONDUITS |
| | AND PIPES EMBEDDED IN CONCRETE. |
| | CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| | TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| | SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| | WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| | PLEASE SUBMIT APPROVAL FROM DESIGN ENGINEER. SECTION |
| | 305.3 SLEEVES MAY BE REQUIRED. |
| | |
| | 99. SHT P3.2.2 WATER RISER 23 DOES NOT SHOW A |
| | CONNECTION TO THE WATER MAIN. SECTION 106.1.2. PLEASE |
| | INDICATE WHERE THE RISER CONNECTS TO THE WATER MAIN. |
| | |
| | 100. SHT P3.3.2 WATER RISER 11 SHOWS 2 SLEEVES FOR HOT |
| | & COLD WATER, BUT THE GAS PIPING ALSO IS INDICATED AS |
| | RUNNING ALONG SIDE OF THE WATER.PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 101. SHT P3.3.2 WATER RISER 23, (HOT RECIRCULATION), |
| | SHOWS 2 SLEEVES. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 102. SHT P3.4.2 WATER RISER 11 SHOWS 2 SLEEVES FOR HOT |
| | & COLD WATER, BUT THE GAS PIPING ALSO IS INDICATED AS |
| | RUNNING ALONG SIDE OF THE WATER.PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 103. SHT P3.4.2 THE COLD WATER RISER LINE FOR THE CHUTE |
| | WASHDOWN APPEARS TO BE LOCATED OUTSIDE THE BUILDING. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 104. SHT P3.5.2 WATER RISER 11 SHOWS 2 SLEEVES FOR HOT |
| | & COLD WATER, BUT THE GAS PIPING ALSO IS INDICATED AS |
| | RUNNING ALONG SIDE OF THE WATER.PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 105. SHT P3.5.2 THE COLD WATER RISERLINE FOR THE |
| | CHUTE WASHDOWN APPEARS TO BE LOCATED OUTSIDE THE |
| | BUILDING. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 106. SHT P3.6.1 THE WATER RISER DESIGNATIONS HAVE |
| | CHANGED. PLEASE CORRELATE THE RISER DIAGRAMS WITH OTHER |
| | SHEETS. SECTION 106.1.1. |
| | |
| | 107. SHT P3.6.2 THE WATER RISER DESIGNATIONS HAVE |
| | CHANGED. PLEASE CORRELATE THE RISER DIAGRAMS WITH OTHER |
| | SHEETS. SECTION 106.1.1. |
| | |
| | 108. SHT P3.6.2 THE COLD WATER RISER LINE FOR THE CHUTE |
| | WASHDOWN APPEARS TO BE LOCATED OUTSIDE THE BUILDING. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 109. SHT P3.7.2 THE COLD WATER RISER LINE FOR THE CHUTE |
| | WASHDOWN APPEARS TO BE LOCATED OUTSIDE THE BUILDING. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 110. SHT 3.7.2 NOTE INDICATES HOT WATER "UP TO" WATER |
| | HEATERS, BUT FROM THE HOT RISER DIAGRAM, IT APPEARS |
| | THAT IT SHOULD READ HOT WATER "DOWN FROM" THE WATER |
| | HEATERS. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 111. SHT P3.7.2WATER RISER 11 SHOWS 2 SLEEVES FOR HOT |
| | & COLD WATER, BUT THE GAS PIPING ALSO IS INDICATED AS |
| | RUNNING ALONG SIDE OF THE WATER.PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 112. SHT P3.8.1 THE WATER SUPPLY ROOF PLAN EAST SECTION |
| | SHOWS NO WATER. PLEASE CLARIFY. SECTION 106.1.1. PLEASE |
| | INDICATE WHERE THE WATER IS LOCATED. |
| | |
| | 113. SHT P3.8.2 NOTE BY THE WATER HEATER ROOM ABOVE |
| | G.W.H. - 1 IS NOT LEGIBLE. SECTION 106.1.1. PLEASE MAKE |
| | ALL INFORMATION LEGIBLE. |
| | |
| | 114. SHT P4.1.1 UNIT "C2" NO COLD WATER SUPPLY TO |
| | KITCHEN SINK IS SHOWN. SECTION 106.1.1. PLEASE SHOW |
| | COLD WATER SUPPLY. |
| | |
| | 115. SHT P4.1.1 UNIT "C2 MIRRORED" NO COLD WATER SUPPLY |
| | TO KITCHEN SINK IS SHOWN. SECTION 106.1.1. PLEASE SHOW |
| | COLD WATER SUPPLY. |
| | |
| | 116. SHT P4.1.1 3RD FLOOR TOILET ROOMS. THE DRINKING |
| | FOUNTAIN WATER SUPPLY IS SHOWN CONNECTING TO THE HOT |
| | WATER. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 117. SHT P4.1.2 THE HOT & COLD WATER DESIGNATIONS ARE |
| | NOT SHOWN. PLEASE INDICATE HOT & COLD WATER LINES. |
| | SECTION 106.1.1. |
| | |
| | 118. SHT P4.1.3 THE HOT & COLD WATER DESIGNATIONS ARE |
| | NOT SHOWN. PLEASE INDICATE HOT & COLD WATER LINES. |
| | SECTION 106.1.1. |
| | |
| | 119. SHT P4.1.5 NO WATER RISER DIAGRAMS FOR THE TPICAL |
| | UNIT "TH3" HAS BEEN SUBMITTED. PLEASE SUBMIT THE WATE |
| | RISER DIAGRAM. SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 120. SHT P5.1.1 THE SANITARY RISER ISOMETRIC DOES NOT |
| | REFLECT THE FLOOR PLAN IN FIVE AREAS. SECTION 1-6.1.1. |
| | PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | |
| | 121. SHT P5.1.1 THE WASH MACHINE SHALL CONNECT TO A |
| | BRANCH DRAIN A MINIMUM 3" IN DIAMETER. SECTION 406.3. |
| | 2" SHOWN PLEASE CORRECT. |
| | |
| | 122. SHT P5.1.1 VARIOUS NOTES INDICATE VENT TO CONNECT |
| | TO THE NEAREST RISER ABOVE. PLEASE INDICATE WHICH RISER |
| | EACH VENT WILL CONNECT TO AND MAKE SURE THE RISER |
| | INDICATED REFLECTS THE VENT FROM BELOW CONNECTING TO |
| | THAT RISER. TABLE 916.1.--(ONE VENT STATES "CONNECT |
| | TO 2" VENT AT RISER #12 ABOVE". RISER #12 DOES NOT SHOW |
| | THE VENT CONNECTING FROM BELOW). PLEASE CLARIFY. |
| | |
| | 123. SHT P5.1.2 THE SANITARY RISER DOES NOT REFLECT THE |
| | FLOOR PLAN IN APPROXIMATELY 17 PLACES. SECTION 106.1.1. |
| | PLEASE RECHECK THE RISER DIAGRAM AND MAKE SURE IT |
| | REFLECTS THE FLOOR PLAN. |
| | |
| | 124. SHT P5.1.2 RISER #8 SHOW THE EXTENDED RUN TO THE |
| | BASE OF THE RISER TO REFLECT THE FLOOR PLAN. SECTION |
| | 106.1.1. |
| | |
| | 125. SHT P5.1.2 THE WASH MACHINES SHALL CONNECT TO A |
| | BRANCH DRAIN A MINIMUM OF 3" IN DIAMETER. SECTION |
| | 406.3. PLEASE CHANGE PIPE SIZE. |
| | |
| | 126. SHT P5.1.2 THE DRAINAGE FIXTURE UNITS FOR A 4" |
| | FLOOR DRAIN IS 6DFU, NOT 2DFU AS SHOWN. TABLE 709.2. |
| | PLEASE CORRECT FIXTURE UNITS FOR ALL FLOOR DRAINS PER |
| | TABLE AND RECHECK THE FIXTURE UNITS AS THEY ACCUMULATE |
| | IN THE SYSTEM. |
| | |
| | 127. SHT P5.1.2NO FLOOR PLAN PIPING IS SHOWN FOR THE |
| | TOWNHOUSE UNITS. SECTION 106.1.2. PLEASE PROVIDE THE |
| | FLOOR PLAN PIPING FOR UNITS. SECTION |
| | 105.35.1.3(1)(2)(3)(4)(5)(10). |
| | |
| | 128. SHT P5.1.2 INDICATE WHERE ALL VENTS CONNECT ABOVE |
| | THE UNITS. WILL THEY VENT THRU ROOF OR CONNECT TO A |
| | VENT STACK ABOVE? SECTION 106.1.2. IF THEY CONNECT TO A |
| | RISER ABOVE, PLEASE INDICATE WHICH RISER AND THE RISER |
| | SHALL REFLECT THE VENT CONNECTION. |
| | |
| | 129. SHT P5.1.3 ALL RISERS. INDICATE THE FLOOR LEVELS |
| | ON THE RISERS. SECTION 106.1.2. |
| | |
| | 130. SHT P5.1.3 RISER DIAGRAM #2 DOES NOT REFLECT THE |
| | FLOOR PLAN DOWNSTREAM OF THE SHOWER ON LEVELS 4 THRU 7 |
| | AND AT THE BASE OF THE STACK, (4" 40 DFU). SECTION |
| | 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS |
| | THE PIPING ON THE FLOOR PLAN. |
| | |
| | 131. SHT P5.1.3 RISER DIAGRAM #3 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE BASE OF ONE KITCHEN SINK STACK AND |
| | THE KITCHEN SINK ARE ON THE RISER BY THE WASH MACHINES. |
| | SECTION 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM |
| | REFLECTS THE PIPING ON THE FLOOR PLAN. |
| | |
| | 132. SHT P5.1.3 RISER DIAGRAM #4 DOES NOT REFLECT THE |
| | FLOOR PLAN . THE LAV SHALL CONNECT PRIOR TO THE SHOWER |
| | 3RD FLOOR AT JACUZZI BATHROOM. DOWNSTREAM OF THE BASE |
| | OF THE TUB BATH STACK DOES NOT REFLECT THE FLOOR PLAN. |
| | VENTS ARE REQUIRED FOR THE LAVS BY THE WATER CLOSET IN |
| | THE JACUZZI BATH. SECTIONS 106.1.1 & 901.2.1. PLEASE |
| | MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE |
| | FLOOR PLAN. |
| | |
| | 133. SHT P5.1.3 RISER DIAGRAMS #5 AND #7 DO NOT REFLECT |
| | THE FLOOR PLAN AT THE KITCHEN SINK. SECTION 106.1.1. |
| | PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING |
| | ON THE FLOOR PLAN. |
| | |
| | 134. SHT P5.1.3 RISER DIAGRAM #6 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE TUB BATH 3RD FLOOR, AND FOR THE LAV |
| | ARM IN THE TUB BATH AT THE END OF THE RISER ALL FLOORS |
| | AND AT THE OFFSET DOWNSTREAM OF THE JACUZZI/LAV RISER. |
| | SECTION 1-6.1.1. PLEASE MAKE SURE THE RISER DIAGRAM |
| | REFLECTS THE PIPING ON THE FLOOR PLAN. |
| | |
| | 135. SHT P5.1.3 RISER DIAGRAM #8 DOES NOT REFLECT THE |
| | FLOOR PLAN. WASH MACHINE RISERS TO CONNECT PRIOR TO |
| | JACUZZI/LAV RISER, AND THE LAV ARM IN THE LAST TUB BATH |
| | ON THE 3RD FLOOR. SECTION 106.1.1. PLEASE MAKE SURE THE |
| | RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN. |
| | |
| | 136. SHTS P5.1.3, P5.1.4 & P5.1.5 PLEASE INDICATE THE |
| | FLOOR LEVELS ON ALL RISER DIAGRAMS. SECTION 106.1.2. |
| | |
| | 137. SHT P5.1.4 RISER DIAGRAM #9 KITCHEN SINK ARMS DO |
| | NOT REFLECT THE FLOOR PLAN. SECTION 106.1.1. PLEASE |
| | MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE |
| | FLOOR PLAN. |
| | |
| | 138. SHT P5.1.4 RISER DIAGRAM #12 DOES NOT REFLECT THE |
| | FLOOR PLAN WHERE THE SHOWER BATH BRANCH CONNECTS TO THE |
| | BUILDING DRAIN. SECTION 106.1.1. PLEASE MAKE SURE THE |
| | RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN. |
| | |
| | 139. SHT P5.1.4 RISER DIAGRAM #13 TOTAL DFUS ARE 25, |
| | NOT 10 AS SHOWN. TABLE 709.2. PLEASE SHOW CORRECT |
| | DFUS. |
| | |
| | 140. SHT P5.1.4 RISER DIAGRAM 16/20 DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE WASH MACHINE BRANCH LINE, NOR AT |
| | THE WATER CLOSET/ LAV PIPING DOWNSTREAM OF THE DOUBLE |
| | LAV ON THE THIRD FLOOR.--THE JACUZZI TUB IS NOT |
| | IDENTIFIED ON THE THIRD FLOOR.--PLEASE INDICATE THE |
| | SYMBOL USED FOR THE DRAIN DOWNSTREAM OF CCC-1. SYMBOL |
| | NOT SHOWN ON THE PLUMBING LEGEND.--DRAIN FOR CCC-2 |
| | INDICATED AS 3" 4" PLEASE CLARIFY. SECTIONS 106.1.2 & |
| | 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS |
| | THE PIPING ON THE FLOOR PLAN. |
| | |
| | 141. SHT P5.1.5 RISER DIAGRAM #18 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE BASE OF BOTH WASH MACHINES RISERS. |
| | THE FLOOR PLAN SHOWS THE LAUNDRY BOX BETWEEN THE |
| | RISERS. PLEASE CLARIFY. SECTION 106.1.1. PLEASE MAKE |
| | SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR |
| | PLAN. |
| | |
| | 142. SHT P5.1.5 RISER DIAGRAM #19 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE BASE OF THE WASH MACHINE RISERS FOR |
| | THE OFFSETS AND THE LAUNDRY BOX SHOWN BETWEEN THE |
| | RISERS. NOR DOES IT REFLECT THE FLOOR PLAN WHERE THE |
| | BRANCH CONNECTION FOR THE JACUZZI TUB/LAV TO DRAIN LINE |
| | AS WELL AS THE LAV ARM IN THE SHOWER BATH. SECTION |
| | 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS |
| | THE PIPING ON THE FLOOR PLAN. |
| | |
| | 143. SHT P5.1.5 RISER DIAGRAM #21 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE BRANCH LINE TO THE |
| | KITCHEN/LAV/JACUZZI & AT THE WASH MACHINE RISERS WHERE |
| | THEY CONNECT TO THE DRAIN LINE. SECTION 106.1.1. PLEASE |
| | MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE |
| | FLOOR PLAN. |
| | |
| | 144. SHT P5.1.5 RISER DIAGRAM #25 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE BASE OF THE WASH MACHINE STACK, OFF |
| | SET NOT SHOWN AND JACUZZI TUB IS NOT LEFT OF STACK. |
| | SECTION 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM |
| | REFLECTS THE PIPING ON THE FLOOR PLAN. |
| | |
| | 145. SHT P5.1.5 RISER DIAGRAM #26 DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE WASH MACHINE STACK BASE, (LAUNDRY BOX |
| | SHOWN BETWEEN THE W/M STACKS), AND AT THE LAV ARM IN |
| | THE TUB BATH ALL FLOORS.--A DRY HORIZONTAL VENT IS |
| | SHOWN UPSTREAM OF THE W/C AT THE BASE OF THE W/C STACK. |
| | SECTION 106.1.1. DRY HORIZONTAL VENTS ARE NOT APPROVED. |
| | PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING |
| | ON THE FLOOR PLAN AND MEETS CODE REQUIREMENTS. SECTION |
| | 905.3. |
| | |
| | 146. SHT P5.1.6 SANT RISERS TH3A, TH3B, TH3C & TH3D DO |
| | NOT REFLECT THE FLOOR PLANS. THE WASH MACHINE SHALL |
| | CONNECT TO A BRANCH LINE A MINIMUM 3" IN DIAMETER PER |
| | SECTION 406.3. SECTION 106.1.1. PLEASE MAKE SURE THE |
| | RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN. |
| | |
| | 147. SHT P5.2.1 ALL CONDENSATE RISER VENTS SHOW "TO |
| | NEAREST SANT. VENT". THIS IS NOT APPROVED. VENTS FOR |
| | CONDENSATE SHALL TERMINATE SEPARATELY FROM THE SANITARY |
| | VENTS.THESE ARE TWO SEPARATE SYSTEMS AND SHALL NOT BE |
| | CROSS CONNECTED.--UNABLE TO REVIEW THE MOST |
| | UPSTREAM SECTION OF THE RISER UPSTREAM OF RD #1 AT THE |
| | BASE OF THE CONDENSATE RISER #1. THE INFORMATION IS NOT |
| | ACCESSIBLE AS THE PLANS DO NOT OPEN UP TO SHOW THAT |
| | INFORMATION.--THE STORM/CONDENSATE RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN IN MANY AREAS. SECTION |
| | 106.1.2 & SECTION 106.1.1. PLEASE MAKE SURE THE RISER |
| | DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN. |
| | |
| | 148. SHT P5.2.2 STORM/CONDENSATE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. SECTION 106.1.1. PLEASE MAKE |
| | SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR |
| | PLAN. |
| | |
| | 149. SHT P5.2.3STORM/CONDENSATE RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. SECTION 106.1.1. PLEASE |
| | MAKE SURE THE RISER DIAGRAM REFLECTS THE PIPING ON THE |
| | FLOOR PLAN. |
| | |
| | 150. SHT P6.1.1 RISER DOES NOT REFLECT THE FLOOR PLAN. |
| | SHOW ALL OFFSETS, CONNECTIONS TO MAINS ETC TO REFLECT |
| | THE FLOOR PLAN.--2 COLD LINES FROM PUMP ROOM AND |
| | AROUND THE 2ND FLOOR SHOWN ON THE FLOOR PLAN ARE NOT ON |
| | THE RISER DIAGRAM. SECTION 106.1.1. PLEASE MAKE SURE |
| | THE RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR |
| | PLAN. --RPZV BACKFLOW SHALL BE LOCATED AS CLOSE TO |
| | THE METER AS POSSIBLE ON PRIVATE PROPERTY. |
| | |
| | 151. SHT P6.1.2 RISER DOES NOT REFLECT THE FLOOR PLAN |
| | WHERE SOME RISERS OR DROPS CONNECT TO THE MAIN, AT |
| | OFFSETS AND AT THE TOP OF RISER 23.--CHECK VALVES |
| | ARE NOT REQUIRED AT THE BASE OF THE DROPS. (HOW CAN |
| | RISERS BE DRAINED IF REQUIRED FOR SERVICE)?SECTION |
| | 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS |
| | THE PIPING ON THE FLOOR PLAN. |
| | |
| | 152. SHT P6.1.3 UNIT "C1" WATER HAMMER ARRESTOR IS |
| | REQUIRED AT THE COLD WATER TO THE WASH MACHINE. SECTION |
| | 604.9. |
| | |
| | 153. SHT P6.1.3 TYPICAL UNITS C2, C2 MIRRORED, C3, C3A, |
| | C4, & C5DO NOT REFLECT THE FLOOR PLAN. SECTION |
| | 106.1.1. PLEASE MAKE SURE THE RISER DIAGRAM REFLECTS |
| | THE PIPING ON THE FLOOR PLAN. |
| | |
| | 154. SHT P6.1.3 IN UNIT "C3", A WATER HAMMER ARRESTOR |
| | IS REQUIRED AT THE ICE MAKER. SECTION 604.9. |
| | |
| | 155. SHT P6.1.3 3RD FLOOR TOILET ROOMS DO NOT REFLECT |
| | THE FLOOR PLAN. SECTION 106.1.1. PLEASE MAKE SURE THE |
| | RISER DIAGRAM REFLECTS THE PIPING ON THE FLOOR PLAN. |
| | |
| | 156. SHT P6.1.3 TYPICAL UNIT "TH3" A WATER RISER |
| | DIAGRAM REQUIRED. SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 157. SHT P6.1.4 ALL UNITS. SUBMIT FLOOR PLANS FOR THESE |
| | UNITS. SECTION 106.1.2--THE RISERS SHALL REFLECT |
| | THE FLOOR PLANS SUBMITTED.--SOME RISERS MISSING |
| | WATER HAMMER ARRESTORS AT DISHWASHERS OR ICE MAKERS. |
| | SECTION 604.9. |
| | |
| | 158. SHT P6.1.5 A SEPARATE GAS PERMIT IS REQUIRED. |
| | SUBMIT THE FOLLOWING INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - INDICATE ALL CUT SECTIONS DOWNSTREAM |
| | OF THE REGULATOR FOR THE GAS WATER HEATERS. FINAL DROP |
| | LENGTH NOT SHOWN. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. - SIZE OF PIPE |
| | SHOWS 1-1/4" REDUCING TO 1" THEN BACK TO 1-1/4". PLEASE |
| | CLARIFY.--ALSO SHOW THE MATERIAL TYPE OF THE |
| | VENTING FROM THE REGULATORS. (MATERIAL SHALL BE NON |
| | COMBUSTABLE). |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - ALSO SHOW THE TOTAL |
| | DISTANCE FROM THE REGULATOR TO THE MOST REMOTE OUTLET |
| | DOWNSTREAM OF THE REGULATOR FOR THE GAS WATER HEATERS. |
| | |
| | D. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLEASE SUBMIT AN |
| | APPROVED TABLE FOR 7"W.C. OR INDICATE 1/2PSI DOWNSTREAM |
| | OF THE REGULATOR. FBC-2004 FUEL GAS HAS NO 7" W.C. |
| | TABLES TO VERIFY PIPE SIZES. |
| | |
| | F. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | H. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE GAS |
| | REGULATORS. INDICATE MODEL NUMBER FOR EACH REGULATOR. |
| | --A UNION IS REQUIRED NEXT TO THE REGULATOR NOT AT |
| | THE END OF A RUN. (SEE GAS WATER HEATERS & HVAC SYSTEM |
| | REGULATORS). |
| | |
| | 159. SHT P9.1.1 ROOFTOP EQUIPMENT. CONDENSATION |
| | CONNECTION DETAIL INDICATES A LINE TO DISCHARGE THAT |
| | RUNS BELOW THE ROOF & CONNECTS TO NEAREST CATCH BASIN, |
| | BUT SHT P2.7.2 SHOWS RTU-2 DISCHARGING TO NEAREST ROOF |
| | DRAIN. PLEASE CORRELATE DETAIL AND ROOF PLAN. SECTION |
| | 106.1.1. |
| | |
| | 160. THERE IS A MOP SINK INDICATED IN ROOM 339 THAT HAS |
| | NO SANITARY OR WATER PIPING SHOWN. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 161. SHT A-001B INDEX OF DRAWINGS VOL II INDICATES |
| | IRRIGATION PLANS. NO IRRIGATION PLANS FOUND. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 162. ENERGY CALCULATION INDICATE HEAT PUMPS FOR THE |
| | WATER HEATERS UNDER THE WATER HEATER COMPLIANCE AND FOR |
| | THE INPUT DATA REPORT. PLANS INDICATE GAS WATER |
| | HEATERS. PLEASE CORRELATE PLANS AND ENERGY |
| | CALCULATIONS. SECTION 106.1.1. |
| | |
| | 163. THE PLANS DO NOT APPEAR TO BE 100% COMPLETE AT |
| | THIS TIME. MORE COMMENTS MAY FOLLOW WHEN PLANS ARE |
| | COMPLETE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |