Plan Review Notes
Plan Review Notes For Permit 07080072
Permit Number 07080072
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-14 20:07:462007-09-14 20:07:46
  
 ** DENIED **
  
 LAKES AT PALM BEACH FORMERLY MIZNER LAKES. BUILDING
 #4.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 ** SOME OF THE ABOVE ARE REFERENCED ON PLANS HOWEVER
 SOME REFERENCED ARE NO LONGER IN EFFECT.
 PLEASE SEE THAT ALL SHEETS CONTAIN THE RELEVANT CODES
 FOR DESIGN.
 FBC 106.1.2, 106.1.3, 110.1.2
  
 2) NOTE: PLEASE SEE THE DATE ON THE PLANS IN WHICH THE
 ENGINEERED SIGNED PLANS IS DATED BEFORE THEY WERE
 ISSUED. HOW IS THIS POSSIBLE?
 PLEASE SEE FLORIDA STATUTES471.025 AS THIS REQUIRES
 THE DESIGN PROFESSIONAL TO SIGN AND DATE EACH SHEET
 WHEN SIGNING, DATING AND SEALING SAID PLANS.
  
 3) NOTE: PLEASE SEE THE LANDSCAPE PLANS IN WHICH THE
 TITLE BLOCKS ARE MISSING REQUIRED LICENSE INFORMATION
 PER FLORIDA ADMINISTRATIVE CODE 61G1-16.004, AND FS
 481.219.
 ** PLEASE VERIFY WITH THE STATE BOARD OF LANDSCAPE
 ARCHITECTS WITH ANY CHANGES IN THE SEAL REQUIREMENTS TO
 THE NEW 2INCH SEAL.
 61G1-16.002, 61G10-11.010
 ** THIS IS REQUIRED FOR ALL LANDSCAPE SHEETS AND PLANS
 WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES/REVIEWER(S).
  
 4) NOTE: PLEASE BE SURE THE LIGHTING SHOWN ON THE
 LANDSCAPE SHEETS CORRELATE WITH THE LIGHTING ON THE
 ELECTRICAL PLANS.
 FBC 106.1.2 FOR COORDINATION.
  
 5) NOTE: PLEASE SEE THE ADDRESS ON THE PERMIT
 APPLICATION INDICATES 715 HANK AARON DR, HOWEVER THE
 ASSIGNED ADDRESS FOR THIS BUILDING #4 IS 1596 VANDAN
 DR.
 **PLEASE KNOW THERE ARE STILL SEVERAL SHEETS IN PLANS
 SETS WHICH REFLECT THE PREVIOUS PROJECT NAME OF MIZNER
 LAKES AND SHEETS WHICH NOW REFLECT LAKES AT PALM
 BEACH.
 ** PLEASE BE SURE TO COORDINATE SHEETS. (NOT A KAMM
 CONSULTING COMMENT)
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED ARE IN NEED OF CORRECTIONS.
 PLEASE SEE THE ADDRESS AND BUILDING INFORMATION NEEDS
 TO MATCH WITH PLANS AND PROJECT. COVER SHEET CALLS FOR
 AN ADDRESS LOCATED IN MIAMI, CALLS FOR MIZNER LAKES,
 ETC.
 PLEASE SEE THE INFORMATION ON LIGHTING NEEDS TO
 CORRELATE WITH PLANS. PLEASE SEE THE SUMMARY SHEETS AND
 THE INPUT DATA REPORT DOES NOT CONTAIN ANY *EXTERIOR
 LIGHTING* ENTERED. HOW IS THIS POSSIBLE WHEN THE PLANS
 CONTAIN DOZENS OF EXTERIOR LIGHT FIXTURES?
 PLEASE SEE LANDSCAPE PLANS AND ELECTRICAL PLANS WHICH
 INDICATE LANDSCAPE LIGHTING FIXTURES.
 PLEASE ALSO SEE THE INFORMATION ON THE INPUT DATA
 REPORT FOR THE INTERIOR LIGHTING WHICH ALSO DOES NOT
 MATCH WITH PLANS. PLEASE SEE THERE ARE ONLY 1 OF EACH
 TYPE OF FIXTURE ENTERED WHICH IS NOT POSSIBLE. PLEASE
 COORDINATE ALL INFORMATION ON CALCULATIONS WITH PLANS.
 PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.3 ETC
  
 7) NOTE: PLEASE SEE THERE ARE A FEW AREAS ON PLANS
 WHICH SOME DEVICES FOR CONTROLS ON LIGHTING AS REQUIRED
 PER 13-415.1.ABC.1.1, .1.2 NEEDS ADDRESSING. PLEASE SEE
 METHODS OF CONTROLS FOR EXTERIOR LIGHTING. PLEASE SEE
 SOME ROOMS FOR EXAMPLE, CUSTODIAN CLOSET, WOMEN RR AND
 MEN RR ON E2.3.2 NEAR THE POOL DECK ACCESS DOORS.
 PLEASE KNOW AREA FOR RESTROOMS NEEDS TO PROVIDE DEVICES
 WHICH PROVIDE COVERAGE IN ALL AREAS FOR LIFE SAFETY AND
 EGRESS SAFETY.
  
 8) NOTE: PLEASE SEE SHEET A102, 101 ETC WHICH REFERENCE
 TO SEE A307 FOR DETAILS FOR FIRE PUMP ROOM HOWEVER THE
 307 SHEET DOES NOT PROVIDE ANY INFORMATION.
 PLEASE SEE THAT NO INFORMATION FOR THIS PUMP HOUSE
 ELECTRICAL FOR LIGHTING, SERVICE RECEPTACLES ETC COULD
 BE FOUND ON PLANS.
 PLEASE KNOW AS THIS IS A SEPARATE BUILDING PLEASE SEE
 225.31-225.39, 250.32.
 PLEASE SEE BATTERY BACK UP LIGHTING FIXTURES WILL BE
 REQUIRED IN THIS ROOM IN ADDITION TO NORMAL LIGHTING.
 PLEASE SEE 700.16, 700.12F ETC
 408.4, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE PROVIDE THE INFORMATION ON PLANS FOR
 THE *EQUAL-POTENTIAL POOL GROUNDING GRID* AS REQUIRED
 PER 680.26.
 PLEASE KNOW EVEN THOUGH THE POOL IT SELF WILL BE UNDER
 SEPARATE PERMIT THE MAIN STRUCTURAL CONTENTS OF THE
 POOL WILL BE PART OF THE BUILDING AND WILL REQUIRE THIS
 GROUNDING.
  
 10) NOTE: PLEASE KNOW THAT THE PLANS WILL BE REQUIRED
 TO STATE *NO DUSK TO DAWN SWIMMING*. PLEASE KNOW IF ANY
 AFTER DISK SWIMMING WILL TAKE PLACE THE REQUIRED
 MINIMUM SIGNED, DATED AND SEALED PHOTO-METRICS WILL BE
 REQUIRED TO BE SUBMITTED TO PALM BEACH COUNTY HEALTH
 DEPARTMENT FOR REVIEW AND STAMPING. THESE WOULD BE
 REQUIRED TO BE SUBMITTED WITH BOTH THE BASE BUILDING
 PLANS AND ALONG WITH THE POOL PERMIT.
 AS MUCH OF THE ELECTRICAL CONDUITS, LIGHTING CONDUITS
 AND GROUNDING OF SYSTEMS IS PART OF THE BASE BUILDING;
 THESE PLANS WILL BE REQUIRED TO CONTAIN MUCH OF THIS
 INFORMATION.
 FBC 106.1.2, NEC 680
  
 11) NOTE: PLEASE SEE SHEET A-352 AND BE SURE THIS AND
 ANY OTHER ELECTRICAL REFLECTED ON OTHER SHEETS
 COORDINATE WITH THE ELECTRICAL PLANS.
 FBC 106.3.5.1.2
  
 12) NOTE: PLEASE SEE THE FS SHEETS WHICH REFLECT THE
 INCORRECT NFPA-20.
 THE STATE IS CURRENTLY UNDER THE 2003 NFPA-20
  
 13) NOTE: PLEASE PROVIDE ALL INFORMATION ON THE FIRE
 PUMPS AND MINIMUM FUEL BEING PROVIDED PER NFPA-20
 11.4.3.
 ** PLEASE SEE ALL OF CHAPTER 11.
  
 14) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS
 FOR FIRE PUMP, FIRE PUMP CONTROLLER AND FUEL
 TANKS.110.3, 90.7, NFPA-20 CHAPTER 10, 11 ETC. PLEASE
 KNOW MUCH OF THIS WILL ALSO BE REVIEWED BY THE
 MECHANICAL, BUILDING AND FIRE MARSHAL.
 **PLEASE BE SURE TO SEE ANY COMMENTS FROM FIRE MARSHAL
 WITH RESPECT TO BOTH BUILDINGS BEING FED FROM ONE FIRE
 PUMP AND LOCATION.
  
 15) NOTE: PLEASE SEE PLANS ARE MISSING COMPLETED
 PHOTO-METRICS FOR ALL EGRESS PATHS UNDER NORMAL AND
 EMERGENCY. PLEASE KNOW AS THE GARAGE INDICATES THE
 LEVELS UNDER EMERGENCY THIS DOES NOT NEED TO SHOW THE
 NORMAL.
 PLEASE SEE STAIRS WHICH DO NOT INDICATE ANY LEVELS. FAC
 61G15-33.004
 NFPA-101 7.8.1.3, 7.9.2.2
  
 16) NOTE: PLEASE CLARIFY HOW PHOTO-METRIC LEVELS WERE
 SUBMITTED FOR POOL DECK AREA UNDER EMERGENCY WHEN THE
 FIXTURES ON PLANS DO NOT INDICATE BATTERY BACK UP?
 COULD NOT LOCATE THESE? PLEASE SEE E2.3.1
 LS 101 7.8 AND 7.9
  
 17) NOTE: PLEASE SEE THERE ARE FIXTURE DESIGNATIONS ON
 PLANS WHICH DO NOT CORRELATE WITH THE LIGHTING FIXTURE
 LEGEND. PLEASE SEE GARAGE FIXTURES FOR EXAMPLE ON
 PHOTO-METRICS SEEM TO INDICATE A *G* NEXT TO THE
 FIXTURES, BUT THE LEGEND INDICATES WALL SCONCE
 FIXTURES? THIS IS THE SAME FOR WHAT APPEARS TO BE EXIT
 LIGHTS IN STAIRS. PLEASE SEE E2.1.1. THESE SEEM TO BE
 SOME KIND OF MISPRINT.
 PLEASE SEE SAME SHEET E2.1.1 WHICH INDICATES A NOTE #8
 IN THE UPPER LEFT HAND CORNER STAIRS , YET THE NOT
 LEGEND DOES NOT CONTAIN AND NOTE #8.
 PLEASE BE SURE TO SEE THE LIGHTING PLANS AND COORDINATE
 THE FIXTURES ON LIGHTING PLANS WITH THAT OF THE
 FIXTURES ON THE PHOTO-METRIC SHEETS SUBMITTED. PLEASE
 COORDINATE. FBC106.1.2
  
 18) NOTE: PLEASE SEE SOME STAIRS ON LOWER LEVEL/FIRST
 FLOOR DO NOT INDICATE THE FIXTURE IDENTIFICATION AND
 SOME CIRCUITS. E2.1.1
  
 19) NOTE: PLEASE SEE PHOTO-METRICS FOR THIRD FLOOR EAST
 WHICH DOES NOT INDICATE TABLES FOR AVERAGE LEVELS. FBC
 106.3.5.1.2, 106.1.2
 SAME CODE SECTIONS AS NOTED ABOVE FOR LS.
  
 20) NOTE: PLEASE SEE STAIR AREAS ON E1.3.1 WHICH
 REQUIRES 10FT/CANDLES UNDER NORMAL AND 1FT CANDLE UNDER
 EMERGENCY.
 PLEASE PROVIDE LEVELS.
 FAC 61G15-33.004, LS 101 7.8.1.3, 7.9.2.2
  
 21) NOTE: PLEASE SEE NOTE #5 ON SHEET E2.1.1 WHICH
 CONTAINS A NOTE FOR RATING THE J-BOX AT 500LBS? PLEASE
 CLARIFY THIS? WHAT TYPE OF FIXTURE/EQUIPMENT WILL BE
 PLACED ON THIS?
 FBC 106.1.2
  
 22) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE
 OPERATION OF DEVICES FOR ACCESS GATES, DOORS, AND
 PERSONNEL GATES.
 PLEASE SEE LS 101 7.2.1.5, 7.2.1.5.4, 7.2.1.6.2 ETC **
 PLEASE SEE FIRE MARSHAL REVIEW COMMENTS.
  
 23) NOTE: PLEASE CLARIFY MINIMUM LIGHTING LEVELS IN
 ELEVATOR PITS PER 620.24.
 PLEASE SEE COMMENTARY PROVIDED IN THE NEC FOR STANDARDS
 FROM THE ELEVATOR SAFETY CODE.
 PLEASE BE SURE TO CONTACT OR SEE ANY STATE ELEVATOR
 CODES WHICH ACTUALLY MAY BE MORE RESTRICTIVE FOR
 LIGHTING LEVELS.
 ? ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.*
  
 24) NOTE: PLEASE PROVIDE INFORMATION FOR EMERGENCY SHUT
 OFF OF SPA PER 680.41.
 THE DEVICE AS SHOWN DOES NOT PROVIDE LOCATION AND EM
 SHUT OFF INFORMATION.
  
 25) NOTE: PLEASE KNOW AS THE TIMERS AS SHOWN IN MOST
 ELECTRICAL ROOMS DO NOT MEET 110.26D, PLEASE PROVIDE A
 DIFFERENT WAY FOR CONTROLLING LIGHTING.
 PLEASE SEE13-415.1.ABC.1.1 EXCEPT *C*.
  
 26) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS LOCATED
 IN THE ELEVATOR EQUIPMENT ROOM ABOVE THE ELEVATOR
 MOTORS. PLEASE KNOW AS PER INFORMATION FROM THE STATE
 ELEVATOR CODE, THIS AREA WILL REQUIRE ADDITIONAL
 LIGHTING. THIS IS NOT IN THE NEC OR LS CODE, HOWEVER IT
 MAY BE OF INTEREST TO PLACE ON PLANS AT THIS TIME.
 PLEASE VERIFY WITH THE STATE.
 FBC 106.3.5.1.2, 106.1.2
 NO CHANGES ARE REQUIRED TO PLANS AND THIS NOTE IS FOR
 INFORMATIONAL PURPOSE.
  
 27) NOTE: PLEASE PROVIDE DISCONNECT DETAILS FOR ROOF
 TOP EQUIPMENT FOR SELECTIVE MECHANICAL AND OTHER
 EQUIPMENT.
 PLEASE SEE MECHANICAL REVIEW COMMENTS FOR POSSIBLE
 LOCATIONS AND INFORMATION NEEDED.
 440.11, 422.30 ETC THIS CAN BE A TYPICAL DETAIL FOR ANY
 EQUIPMENT WHICH IS MULTIPLE OF THE SAME USE ETC. FBC
 106.1.2
  
 28) NOTE: PLEASE SEE NEC 210.12 AS ARC FAULT PROTECTION
 IS REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS. PLEASE
 SEE THE SMOKE ALARMS IN BEDROOMS WHICH INDICATE AFCI
 PROTECTION ARE CIRCUITED TO A CIRCUIT IN THE PANEL
 SCHEDULE WHICH DOES NOT CONTAIN AFCI BREAKER. (KITCHEN)
 ETC.
 THIS IS TYPICAL OF ALL UNITS. C1.11, C2.11, C3.11 ETC.
  
 29) NOTE: PLEASE SEE E4.1.1 UNIT C-3 FOR CIRCUIT #26
 WHICH ON PANEL SCHEDULE MENTIONS HALF BATH, BUT ON
 PLANS ALSO FEED MASTER BEDROOM LIGHTING CIRCUIT. PLEASE
 SEE NO AFCI PROTECTION.
 408.4, 210.12
  
 30) NOTE: PLEASE SEE UNIT C-S E4.1.1 WHICH SHOWS NOOK
 RECEPTACLE IN DOOR WAY.
  
 31) NOTE: PLEASE SEE 210.4B FOR BRANCH CIRCUITS FEEDING
 SAME DEVICE/YOKE WITH MORE THAN ONE CIRCUIT.(REQUIRES
 2-POLE BREAKER.
 THIS IS TYPICAL OF ALL UNITS AND PANEL SCHEDULES.
  
 32) NOTE: PLEASE SEE UNIT C-1 MASTER BEDROOM DOORWAY TO
 BATHROOM WHICH CONTAINS THE RECEPTACLE WHICH SHOULD BE
 ON WALL IN DOOR WAY.
 PLEASE RELOCATE AND ADJUST.
  
 33) NOTE: PLEASE SEE C-5 4.1.1 MISSING DINING ROOM WALL
 RECEPTACLE PER 210.52
 PLEASE BE SURE TO CIRCUIT PER 210.52B1, 210.11C1,
 220.53
  
 34) NOTE: PLEASE SEE C-5, 4.1.2 BEDROOM #1 WHICH IS
 MISSING RECEPTACLE PER 2FT OF WALL PER 210.52
  
 35) NOTE: PLEASE SEE TH2 FOR MISSING RECEPTACLE FOR 2FT
 OR MORE OF WALL IN KITCHEN. THIS IS THE SAME FOR TH1
 ALSO.
  
 36) NOTE: PLEASE SEE DINING AREA IN TH3 FOR CIRCUITING
 OF RECEPTACLE WHICH IS SHOWN ON LIVING ROOM CIRCUIT.
 210.52B1
  
 37) NOTE: PLEASE SEE TH2 FOR MISSING DINING AREA PER
 210.52B1, 210.11C1, 220.53.
  
 38) NOTE: PLEASE SEE TH3 FOR MISSING RECEPTACLE
 REQUIRED WITHIN 6FT OF OPENING ON WALL SPACE. (DEN).
  
 39) NOTE: PLEASE SEE NFPA-72FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES.
 PLANS INDICATE ALL DEVICES IN UNITS AS *SMOKE
 DETECTORS* AND NOT * SMOKE ALARMS*.
 PLEASE KNOW IF THESE ARE DEVICES WHICH DETECT AND SOUND
 AN ALARM.
 PLEASE ADJUST PLANS.
 PLEASE ALSO BE SURE ALL SMOKE ALARMS ARE MOUNTED ON
 WALL LEADING TO THE FLOOR ABOVE. A NOTE IS LOCATED FOR
 THIS HOWEVER THE NOTE COULD ALSO BE READ TO MOUNT THIS
 UNIT ON WALL ON THE UPPER LEVEL.
 PLEASE ADJUST NOTE.
 NFPA-7211.5.1.1, 11.8.3
  
 40) NOTE: PLEASE SUBMIT WORST CASE VOLTAGE DROP
 CALCULATIONS FOR FEEDER(S) AND BRANCH CIRCUIT(S) PER
 13-413.1ABC.1
  
 41) NOTE: PLEASE SEE THE PANEL SCHEDULES FOR UNITS
 WHICH CONTAINS (??) ON SCHEDULE BEFORE LINE FOR
 *LARGEST A/C LOAD*.
 FBC 106.1.2
  
 42) NOTE: PLEASE BE SURE THE ARCHITECT AND STRUCTURAL
 ENGINEER OBTAINS THE BUS-WAY/DUCT CURBING DETAIL AND
 PLACES ON THEIR RESPECTIVE SHEETS.
 THIS AHJ HAS HAD SEVERAL NOT INSTALLED AND CONSTRUCTED
 CORRECTLY AS THE DETAIL WAS NOT ON THE A AND S SHEETS
 FOR THE BUILDING CONTRACTOR.
 THIS IS NOT AN ITEM TO CONSTRUCT AFTER INSTALLATION OF
 BUS-WAY.
 106.1.2
  
 43) NOTE: PLEASE SEE MSB-9 WHICH INDICATES A 200AMP
 BREAKER FEEDING PANEL L1HC WHICH IS ONLY A 125AMP
 PANEL.
 PLEASE ADJUST. 240, 408 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 44) NOTE: PLEASE CLARIFY WHERE ALL CONTINUOUS LOADS ARE
 SHOWN AT 125%.
 215.3, 230.42 ETC
 FBC 106.1.2
  
 45) NOTE: PLEASE PROVIDE INFORMATION ON MAINS FOR MSB,
 SBA AND MC1A. PLEASE VERIFY MANUAL MEANS OF DISCONNECT
 RATED FOR THE LOAD SERVED PER 230.76, 230.79
  
 46) NOTE: PLEASE SEE RISER INDICATING ALL UNITS ONLY
 SEEMS TO INDICATE 114 UNITS YET PLANS INCLUDING OTHER
 TRADES MENTIONS 120 UNITS?
 PLEASE CORRELATE AND ADJUST ALL PLANS AS NEED.
 FBC 106.3.5.1.2
  
 47) NOTE: PLEASE SEE MC 1,3,4,5,6 AND 7 WHICH ALL
 CONTAIN A NOTE #1 IN A CIRCLE AT THE LOWER LEFT HAND
 SIDE OF SCHEDULE, HOWEVER NO NOTE #1 COULD BE LOCATED
 ON THIS SHEET.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY CERTAINLY AFFECT THE ELECTRICAL
 PLANS AND/OR DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-14 07:01:352007-09-14 07:01:35
  
 REVIEW IN PROGRESS
2007-09-13 19:35:482007-09-13 20:01:33
  
 REVIEW STOPPED, TO CONTIUE ON 9/14
2007-09-13 14:41:482007-09-13 14:41:48
  
 IN ELEC FOR REVIEW, 1-SET ONLY OF EACH ARCHITECTURAL
 AND MEP.