| 2007-09-14 20:07:46 | 2007-09-14 20:07:46 |
| | |
| | ** DENIED ** |
| | |
| | LAKES AT PALM BEACH FORMERLY MIZNER LAKES. BUILDING |
| | #4. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2003 NFPA-20 |
| | ** SOME OF THE ABOVE ARE REFERENCED ON PLANS HOWEVER |
| | SOME REFERENCED ARE NO LONGER IN EFFECT. |
| | PLEASE SEE THAT ALL SHEETS CONTAIN THE RELEVANT CODES |
| | FOR DESIGN. |
| | FBC 106.1.2, 106.1.3, 110.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THE DATE ON THE PLANS IN WHICH THE |
| | ENGINEERED SIGNED PLANS IS DATED BEFORE THEY WERE |
| | ISSUED. HOW IS THIS POSSIBLE? |
| | PLEASE SEE FLORIDA STATUTES471.025 AS THIS REQUIRES |
| | THE DESIGN PROFESSIONAL TO SIGN AND DATE EACH SHEET |
| | WHEN SIGNING, DATING AND SEALING SAID PLANS. |
| | |
| | 3) NOTE: PLEASE SEE THE LANDSCAPE PLANS IN WHICH THE |
| | TITLE BLOCKS ARE MISSING REQUIRED LICENSE INFORMATION |
| | PER FLORIDA ADMINISTRATIVE CODE 61G1-16.004, AND FS |
| | 481.219. |
| | ** PLEASE VERIFY WITH THE STATE BOARD OF LANDSCAPE |
| | ARCHITECTS WITH ANY CHANGES IN THE SEAL REQUIREMENTS TO |
| | THE NEW 2INCH SEAL. |
| | 61G1-16.002, 61G10-11.010 |
| | ** THIS IS REQUIRED FOR ALL LANDSCAPE SHEETS AND PLANS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES/REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE BE SURE THE LIGHTING SHOWN ON THE |
| | LANDSCAPE SHEETS CORRELATE WITH THE LIGHTING ON THE |
| | ELECTRICAL PLANS. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 5) NOTE: PLEASE SEE THE ADDRESS ON THE PERMIT |
| | APPLICATION INDICATES 715 HANK AARON DR, HOWEVER THE |
| | ASSIGNED ADDRESS FOR THIS BUILDING #4 IS 1596 VANDAN |
| | DR. |
| | **PLEASE KNOW THERE ARE STILL SEVERAL SHEETS IN PLANS |
| | SETS WHICH REFLECT THE PREVIOUS PROJECT NAME OF MIZNER |
| | LAKES AND SHEETS WHICH NOW REFLECT LAKES AT PALM |
| | BEACH. |
| | ** PLEASE BE SURE TO COORDINATE SHEETS. (NOT A KAMM |
| | CONSULTING COMMENT) |
| | |
| | 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED ARE IN NEED OF CORRECTIONS. |
| | PLEASE SEE THE ADDRESS AND BUILDING INFORMATION NEEDS |
| | TO MATCH WITH PLANS AND PROJECT. COVER SHEET CALLS FOR |
| | AN ADDRESS LOCATED IN MIAMI, CALLS FOR MIZNER LAKES, |
| | ETC. |
| | PLEASE SEE THE INFORMATION ON LIGHTING NEEDS TO |
| | CORRELATE WITH PLANS. PLEASE SEE THE SUMMARY SHEETS AND |
| | THE INPUT DATA REPORT DOES NOT CONTAIN ANY *EXTERIOR |
| | LIGHTING* ENTERED. HOW IS THIS POSSIBLE WHEN THE PLANS |
| | CONTAIN DOZENS OF EXTERIOR LIGHT FIXTURES? |
| | PLEASE SEE LANDSCAPE PLANS AND ELECTRICAL PLANS WHICH |
| | INDICATE LANDSCAPE LIGHTING FIXTURES. |
| | PLEASE ALSO SEE THE INFORMATION ON THE INPUT DATA |
| | REPORT FOR THE INTERIOR LIGHTING WHICH ALSO DOES NOT |
| | MATCH WITH PLANS. PLEASE SEE THERE ARE ONLY 1 OF EACH |
| | TYPE OF FIXTURE ENTERED WHICH IS NOT POSSIBLE. PLEASE |
| | COORDINATE ALL INFORMATION ON CALCULATIONS WITH PLANS. |
| | PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.3 ETC |
| | |
| | 7) NOTE: PLEASE SEE THERE ARE A FEW AREAS ON PLANS |
| | WHICH SOME DEVICES FOR CONTROLS ON LIGHTING AS REQUIRED |
| | PER 13-415.1.ABC.1.1, .1.2 NEEDS ADDRESSING. PLEASE SEE |
| | METHODS OF CONTROLS FOR EXTERIOR LIGHTING. PLEASE SEE |
| | SOME ROOMS FOR EXAMPLE, CUSTODIAN CLOSET, WOMEN RR AND |
| | MEN RR ON E2.3.2 NEAR THE POOL DECK ACCESS DOORS. |
| | PLEASE KNOW AREA FOR RESTROOMS NEEDS TO PROVIDE DEVICES |
| | WHICH PROVIDE COVERAGE IN ALL AREAS FOR LIFE SAFETY AND |
| | EGRESS SAFETY. |
| | |
| | 8) NOTE: PLEASE SEE SHEET A102, 101 ETC WHICH REFERENCE |
| | TO SEE A307 FOR DETAILS FOR FIRE PUMP ROOM HOWEVER THE |
| | 307 SHEET DOES NOT PROVIDE ANY INFORMATION. |
| | PLEASE SEE THAT NO INFORMATION FOR THIS PUMP HOUSE |
| | ELECTRICAL FOR LIGHTING, SERVICE RECEPTACLES ETC COULD |
| | BE FOUND ON PLANS. |
| | PLEASE KNOW AS THIS IS A SEPARATE BUILDING PLEASE SEE |
| | 225.31-225.39, 250.32. |
| | PLEASE SEE BATTERY BACK UP LIGHTING FIXTURES WILL BE |
| | REQUIRED IN THIS ROOM IN ADDITION TO NORMAL LIGHTING. |
| | PLEASE SEE 700.16, 700.12F ETC |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE PROVIDE THE INFORMATION ON PLANS FOR |
| | THE *EQUAL-POTENTIAL POOL GROUNDING GRID* AS REQUIRED |
| | PER 680.26. |
| | PLEASE KNOW EVEN THOUGH THE POOL IT SELF WILL BE UNDER |
| | SEPARATE PERMIT THE MAIN STRUCTURAL CONTENTS OF THE |
| | POOL WILL BE PART OF THE BUILDING AND WILL REQUIRE THIS |
| | GROUNDING. |
| | |
| | 10) NOTE: PLEASE KNOW THAT THE PLANS WILL BE REQUIRED |
| | TO STATE *NO DUSK TO DAWN SWIMMING*. PLEASE KNOW IF ANY |
| | AFTER DISK SWIMMING WILL TAKE PLACE THE REQUIRED |
| | MINIMUM SIGNED, DATED AND SEALED PHOTO-METRICS WILL BE |
| | REQUIRED TO BE SUBMITTED TO PALM BEACH COUNTY HEALTH |
| | DEPARTMENT FOR REVIEW AND STAMPING. THESE WOULD BE |
| | REQUIRED TO BE SUBMITTED WITH BOTH THE BASE BUILDING |
| | PLANS AND ALONG WITH THE POOL PERMIT. |
| | AS MUCH OF THE ELECTRICAL CONDUITS, LIGHTING CONDUITS |
| | AND GROUNDING OF SYSTEMS IS PART OF THE BASE BUILDING; |
| | THESE PLANS WILL BE REQUIRED TO CONTAIN MUCH OF THIS |
| | INFORMATION. |
| | FBC 106.1.2, NEC 680 |
| | |
| | 11) NOTE: PLEASE SEE SHEET A-352 AND BE SURE THIS AND |
| | ANY OTHER ELECTRICAL REFLECTED ON OTHER SHEETS |
| | COORDINATE WITH THE ELECTRICAL PLANS. |
| | FBC 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE SEE THE FS SHEETS WHICH REFLECT THE |
| | INCORRECT NFPA-20. |
| | THE STATE IS CURRENTLY UNDER THE 2003 NFPA-20 |
| | |
| | 13) NOTE: PLEASE PROVIDE ALL INFORMATION ON THE FIRE |
| | PUMPS AND MINIMUM FUEL BEING PROVIDED PER NFPA-20 |
| | 11.4.3. |
| | ** PLEASE SEE ALL OF CHAPTER 11. |
| | |
| | 14) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS |
| | FOR FIRE PUMP, FIRE PUMP CONTROLLER AND FUEL |
| | TANKS.110.3, 90.7, NFPA-20 CHAPTER 10, 11 ETC. PLEASE |
| | KNOW MUCH OF THIS WILL ALSO BE REVIEWED BY THE |
| | MECHANICAL, BUILDING AND FIRE MARSHAL. |
| | **PLEASE BE SURE TO SEE ANY COMMENTS FROM FIRE MARSHAL |
| | WITH RESPECT TO BOTH BUILDINGS BEING FED FROM ONE FIRE |
| | PUMP AND LOCATION. |
| | |
| | 15) NOTE: PLEASE SEE PLANS ARE MISSING COMPLETED |
| | PHOTO-METRICS FOR ALL EGRESS PATHS UNDER NORMAL AND |
| | EMERGENCY. PLEASE KNOW AS THE GARAGE INDICATES THE |
| | LEVELS UNDER EMERGENCY THIS DOES NOT NEED TO SHOW THE |
| | NORMAL. |
| | PLEASE SEE STAIRS WHICH DO NOT INDICATE ANY LEVELS. FAC |
| | 61G15-33.004 |
| | NFPA-101 7.8.1.3, 7.9.2.2 |
| | |
| | 16) NOTE: PLEASE CLARIFY HOW PHOTO-METRIC LEVELS WERE |
| | SUBMITTED FOR POOL DECK AREA UNDER EMERGENCY WHEN THE |
| | FIXTURES ON PLANS DO NOT INDICATE BATTERY BACK UP? |
| | COULD NOT LOCATE THESE? PLEASE SEE E2.3.1 |
| | LS 101 7.8 AND 7.9 |
| | |
| | 17) NOTE: PLEASE SEE THERE ARE FIXTURE DESIGNATIONS ON |
| | PLANS WHICH DO NOT CORRELATE WITH THE LIGHTING FIXTURE |
| | LEGEND. PLEASE SEE GARAGE FIXTURES FOR EXAMPLE ON |
| | PHOTO-METRICS SEEM TO INDICATE A *G* NEXT TO THE |
| | FIXTURES, BUT THE LEGEND INDICATES WALL SCONCE |
| | FIXTURES? THIS IS THE SAME FOR WHAT APPEARS TO BE EXIT |
| | LIGHTS IN STAIRS. PLEASE SEE E2.1.1. THESE SEEM TO BE |
| | SOME KIND OF MISPRINT. |
| | PLEASE SEE SAME SHEET E2.1.1 WHICH INDICATES A NOTE #8 |
| | IN THE UPPER LEFT HAND CORNER STAIRS , YET THE NOT |
| | LEGEND DOES NOT CONTAIN AND NOTE #8. |
| | PLEASE BE SURE TO SEE THE LIGHTING PLANS AND COORDINATE |
| | THE FIXTURES ON LIGHTING PLANS WITH THAT OF THE |
| | FIXTURES ON THE PHOTO-METRIC SHEETS SUBMITTED. PLEASE |
| | COORDINATE. FBC106.1.2 |
| | |
| | 18) NOTE: PLEASE SEE SOME STAIRS ON LOWER LEVEL/FIRST |
| | FLOOR DO NOT INDICATE THE FIXTURE IDENTIFICATION AND |
| | SOME CIRCUITS. E2.1.1 |
| | |
| | 19) NOTE: PLEASE SEE PHOTO-METRICS FOR THIRD FLOOR EAST |
| | WHICH DOES NOT INDICATE TABLES FOR AVERAGE LEVELS. FBC |
| | 106.3.5.1.2, 106.1.2 |
| | SAME CODE SECTIONS AS NOTED ABOVE FOR LS. |
| | |
| | 20) NOTE: PLEASE SEE STAIR AREAS ON E1.3.1 WHICH |
| | REQUIRES 10FT/CANDLES UNDER NORMAL AND 1FT CANDLE UNDER |
| | EMERGENCY. |
| | PLEASE PROVIDE LEVELS. |
| | FAC 61G15-33.004, LS 101 7.8.1.3, 7.9.2.2 |
| | |
| | 21) NOTE: PLEASE SEE NOTE #5 ON SHEET E2.1.1 WHICH |
| | CONTAINS A NOTE FOR RATING THE J-BOX AT 500LBS? PLEASE |
| | CLARIFY THIS? WHAT TYPE OF FIXTURE/EQUIPMENT WILL BE |
| | PLACED ON THIS? |
| | FBC 106.1.2 |
| | |
| | 22) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE |
| | OPERATION OF DEVICES FOR ACCESS GATES, DOORS, AND |
| | PERSONNEL GATES. |
| | PLEASE SEE LS 101 7.2.1.5, 7.2.1.5.4, 7.2.1.6.2 ETC ** |
| | PLEASE SEE FIRE MARSHAL REVIEW COMMENTS. |
| | |
| | 23) NOTE: PLEASE CLARIFY MINIMUM LIGHTING LEVELS IN |
| | ELEVATOR PITS PER 620.24. |
| | PLEASE SEE COMMENTARY PROVIDED IN THE NEC FOR STANDARDS |
| | FROM THE ELEVATOR SAFETY CODE. |
| | PLEASE BE SURE TO CONTACT OR SEE ANY STATE ELEVATOR |
| | CODES WHICH ACTUALLY MAY BE MORE RESTRICTIVE FOR |
| | LIGHTING LEVELS. |
| | ? ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) |
| | AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE |
| | EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.* |
| | |
| | 24) NOTE: PLEASE PROVIDE INFORMATION FOR EMERGENCY SHUT |
| | OFF OF SPA PER 680.41. |
| | THE DEVICE AS SHOWN DOES NOT PROVIDE LOCATION AND EM |
| | SHUT OFF INFORMATION. |
| | |
| | 25) NOTE: PLEASE KNOW AS THE TIMERS AS SHOWN IN MOST |
| | ELECTRICAL ROOMS DO NOT MEET 110.26D, PLEASE PROVIDE A |
| | DIFFERENT WAY FOR CONTROLLING LIGHTING. |
| | PLEASE SEE13-415.1.ABC.1.1 EXCEPT *C*. |
| | |
| | 26) NOTE: PLEASE CLARIFY WHERE THE LIGHTING IS LOCATED |
| | IN THE ELEVATOR EQUIPMENT ROOM ABOVE THE ELEVATOR |
| | MOTORS. PLEASE KNOW AS PER INFORMATION FROM THE STATE |
| | ELEVATOR CODE, THIS AREA WILL REQUIRE ADDITIONAL |
| | LIGHTING. THIS IS NOT IN THE NEC OR LS CODE, HOWEVER IT |
| | MAY BE OF INTEREST TO PLACE ON PLANS AT THIS TIME. |
| | PLEASE VERIFY WITH THE STATE. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NO CHANGES ARE REQUIRED TO PLANS AND THIS NOTE IS FOR |
| | INFORMATIONAL PURPOSE. |
| | |
| | 27) NOTE: PLEASE PROVIDE DISCONNECT DETAILS FOR ROOF |
| | TOP EQUIPMENT FOR SELECTIVE MECHANICAL AND OTHER |
| | EQUIPMENT. |
| | PLEASE SEE MECHANICAL REVIEW COMMENTS FOR POSSIBLE |
| | LOCATIONS AND INFORMATION NEEDED. |
| | 440.11, 422.30 ETC THIS CAN BE A TYPICAL DETAIL FOR ANY |
| | EQUIPMENT WHICH IS MULTIPLE OF THE SAME USE ETC. FBC |
| | 106.1.2 |
| | |
| | 28) NOTE: PLEASE SEE NEC 210.12 AS ARC FAULT PROTECTION |
| | IS REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS. PLEASE |
| | SEE THE SMOKE ALARMS IN BEDROOMS WHICH INDICATE AFCI |
| | PROTECTION ARE CIRCUITED TO A CIRCUIT IN THE PANEL |
| | SCHEDULE WHICH DOES NOT CONTAIN AFCI BREAKER. (KITCHEN) |
| | ETC. |
| | THIS IS TYPICAL OF ALL UNITS. C1.11, C2.11, C3.11 ETC. |
| | |
| | 29) NOTE: PLEASE SEE E4.1.1 UNIT C-3 FOR CIRCUIT #26 |
| | WHICH ON PANEL SCHEDULE MENTIONS HALF BATH, BUT ON |
| | PLANS ALSO FEED MASTER BEDROOM LIGHTING CIRCUIT. PLEASE |
| | SEE NO AFCI PROTECTION. |
| | 408.4, 210.12 |
| | |
| | 30) NOTE: PLEASE SEE UNIT C-S E4.1.1 WHICH SHOWS NOOK |
| | RECEPTACLE IN DOOR WAY. |
| | |
| | 31) NOTE: PLEASE SEE 210.4B FOR BRANCH CIRCUITS FEEDING |
| | SAME DEVICE/YOKE WITH MORE THAN ONE CIRCUIT.(REQUIRES |
| | 2-POLE BREAKER. |
| | THIS IS TYPICAL OF ALL UNITS AND PANEL SCHEDULES. |
| | |
| | 32) NOTE: PLEASE SEE UNIT C-1 MASTER BEDROOM DOORWAY TO |
| | BATHROOM WHICH CONTAINS THE RECEPTACLE WHICH SHOULD BE |
| | ON WALL IN DOOR WAY. |
| | PLEASE RELOCATE AND ADJUST. |
| | |
| | 33) NOTE: PLEASE SEE C-5 4.1.1 MISSING DINING ROOM WALL |
| | RECEPTACLE PER 210.52 |
| | PLEASE BE SURE TO CIRCUIT PER 210.52B1, 210.11C1, |
| | 220.53 |
| | |
| | 34) NOTE: PLEASE SEE C-5, 4.1.2 BEDROOM #1 WHICH IS |
| | MISSING RECEPTACLE PER 2FT OF WALL PER 210.52 |
| | |
| | 35) NOTE: PLEASE SEE TH2 FOR MISSING RECEPTACLE FOR 2FT |
| | OR MORE OF WALL IN KITCHEN. THIS IS THE SAME FOR TH1 |
| | ALSO. |
| | |
| | 36) NOTE: PLEASE SEE DINING AREA IN TH3 FOR CIRCUITING |
| | OF RECEPTACLE WHICH IS SHOWN ON LIVING ROOM CIRCUIT. |
| | 210.52B1 |
| | |
| | 37) NOTE: PLEASE SEE TH2 FOR MISSING DINING AREA PER |
| | 210.52B1, 210.11C1, 220.53. |
| | |
| | 38) NOTE: PLEASE SEE TH3 FOR MISSING RECEPTACLE |
| | REQUIRED WITHIN 6FT OF OPENING ON WALL SPACE. (DEN). |
| | |
| | 39) NOTE: PLEASE SEE NFPA-72FOR DEFINITIONS OF SMOKE |
| | DETECTION DEVICES. |
| | PLANS INDICATE ALL DEVICES IN UNITS AS *SMOKE |
| | DETECTORS* AND NOT * SMOKE ALARMS*. |
| | PLEASE KNOW IF THESE ARE DEVICES WHICH DETECT AND SOUND |
| | AN ALARM. |
| | PLEASE ADJUST PLANS. |
| | PLEASE ALSO BE SURE ALL SMOKE ALARMS ARE MOUNTED ON |
| | WALL LEADING TO THE FLOOR ABOVE. A NOTE IS LOCATED FOR |
| | THIS HOWEVER THE NOTE COULD ALSO BE READ TO MOUNT THIS |
| | UNIT ON WALL ON THE UPPER LEVEL. |
| | PLEASE ADJUST NOTE. |
| | NFPA-7211.5.1.1, 11.8.3 |
| | |
| | 40) NOTE: PLEASE SUBMIT WORST CASE VOLTAGE DROP |
| | CALCULATIONS FOR FEEDER(S) AND BRANCH CIRCUIT(S) PER |
| | 13-413.1ABC.1 |
| | |
| | 41) NOTE: PLEASE SEE THE PANEL SCHEDULES FOR UNITS |
| | WHICH CONTAINS (??) ON SCHEDULE BEFORE LINE FOR |
| | *LARGEST A/C LOAD*. |
| | FBC 106.1.2 |
| | |
| | 42) NOTE: PLEASE BE SURE THE ARCHITECT AND STRUCTURAL |
| | ENGINEER OBTAINS THE BUS-WAY/DUCT CURBING DETAIL AND |
| | PLACES ON THEIR RESPECTIVE SHEETS. |
| | THIS AHJ HAS HAD SEVERAL NOT INSTALLED AND CONSTRUCTED |
| | CORRECTLY AS THE DETAIL WAS NOT ON THE A AND S SHEETS |
| | FOR THE BUILDING CONTRACTOR. |
| | THIS IS NOT AN ITEM TO CONSTRUCT AFTER INSTALLATION OF |
| | BUS-WAY. |
| | 106.1.2 |
| | |
| | 43) NOTE: PLEASE SEE MSB-9 WHICH INDICATES A 200AMP |
| | BREAKER FEEDING PANEL L1HC WHICH IS ONLY A 125AMP |
| | PANEL. |
| | PLEASE ADJUST. 240, 408 ETC |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 44) NOTE: PLEASE CLARIFY WHERE ALL CONTINUOUS LOADS ARE |
| | SHOWN AT 125%. |
| | 215.3, 230.42 ETC |
| | FBC 106.1.2 |
| | |
| | 45) NOTE: PLEASE PROVIDE INFORMATION ON MAINS FOR MSB, |
| | SBA AND MC1A. PLEASE VERIFY MANUAL MEANS OF DISCONNECT |
| | RATED FOR THE LOAD SERVED PER 230.76, 230.79 |
| | |
| | 46) NOTE: PLEASE SEE RISER INDICATING ALL UNITS ONLY |
| | SEEMS TO INDICATE 114 UNITS YET PLANS INCLUDING OTHER |
| | TRADES MENTIONS 120 UNITS? |
| | PLEASE CORRELATE AND ADJUST ALL PLANS AS NEED. |
| | FBC 106.3.5.1.2 |
| | |
| | 47) NOTE: PLEASE SEE MC 1,3,4,5,6 AND 7 WHICH ALL |
| | CONTAIN A NOTE #1 IN A CIRCLE AT THE LOWER LEFT HAND |
| | SIDE OF SCHEDULE, HOWEVER NO NOTE #1 COULD BE LOCATED |
| | ON THIS SHEET. |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY CERTAINLY AFFECT THE ELECTRICAL |
| | PLANS AND/OR DESIGN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-14 07:01:35 | 2007-09-14 07:01:35 |
| | |
| | REVIEW IN PROGRESS |
| 2007-09-13 19:35:48 | 2007-09-13 20:01:33 |
| | |
| | REVIEW STOPPED, TO CONTIUE ON 9/14 |
| 2007-09-13 14:41:48 | 2007-09-13 14:41:48 |
| | |
| | IN ELEC FOR REVIEW, 1-SET ONLY OF EACH ARCHITECTURAL |
| | AND MEP. |