Plan Review Notes
Plan Review Notes For Permit 07080065
Permit Number 07080065
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-19 16:04:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. THE ADDRESS ON THE APPLICATION AND PLANS, (604
 BRADLEY ST.), DOES NOT REFLECT THE ADDRESS FOR THE PCN
 NUMBER AND ADDRESS ON OUR SYSTEM. PLEASE CLARIFY.
 SECTION 105.3. (SEE ADDRESSING STOP DATED 01-17-2007 ON
 PERMIT NUMBER 07010426). INDICATE THE CORRECT ADDRESS
 ON THE APPLICATION AND ON THE PLANS.
 ****NO RESPONSE. THE ADDRESS WAS CORRECTED ON THE
 APPLICATION, BUT NOT ON THE PLANS.
  
 2. OK PERMIT NUMBER 07010426 VOIDED.
  
 3. OK
  
 4. THE SURVEY SHEET REQUIRES THE SIGNED SEAL TO BE
 DATED WHEN THE SEAL AND SIGNATURE ARE AFFIXED TO THE
 DOCUMENT. FS 472.025. ALSO SEE ELECTRICAL REVIEW
 COMMENT #7CONCERNING STAMPED SIGNATURES WHICH ARE NOT
 APPROVED.
 ****NO RESPONSE NOT ADDRESSED
  
 5. SUBMIT A MINIMUM OF 2 SETS OF PLANS. LOOSE LANDSCAPE
 AND SURVEY PLANS ARE NOT APPROVED. COMPLETE BOUND SETS
 OF PLANS REQUIRED. SECTIONS 106.1 & 106.1.3. ****NO
 RESPONSE, NOT ADDRESSED.
  
 6. OK
 7. OK
 8. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  