Plan Review Notes
Plan Review Notes For Permit 07080065
Permit Number 07080065
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-11 17:06:29**** DENIED 2ND REVIEW ****
  
 ** AS STATED ON PREVIOUS REVIEW, PLEASE SEE PERMIT #
 07010426 IS STILL ACTIVE.
  
 1) NOTE: PLEASE SEE THE NEW LOAD SHOWN ON SHEET A-1 IS
 SHOWN AS 1.86 AMPS, HOWEVER THE NEW LOAD SHOWN ON SHEET
 A-2 IS 7.5AMPS.
 PLEASE ADJUST LOAD CALCULATIONS TO SHOW NEW LOADS BEING
 ADDED TO EXISTING PER 220.87
  
 2) NOTE: PLEASE SEE THE *EQUIPMENT GROUNDING CONDUCTOR*
 SHOWN FROM EXISTING PANEL TO NEW MAIN AT DETACHED
 BUILDING AND FROM DISCONNECT TO PANEL IS SHOWN WITH A
 CONDUCTOR SIZE WHICH IS NOT STANDARD PER AWG (AMERICAN
 WIRE GAUGE) OR 310.16.
 PLEASE KNOW THE MINIMUM SIZE NEEDS TO BE #10 PER
 250.122, 310.16.
 PLEASE KNOW THIS IS AN ITEM WHICH COULD BE *REDLINED*
 ON PLANS.
 PLEASE ADDRESS COMMENT #1 ABOVE.
  
 ** PLEASE CALL IF ALL OTHER COMMENTS AND ALL OTHER
 TRADES PASS REVIEWS. A *PROVISO* MAY BE SET IN PLACE
 FOR PERMIT ISSUANCE. THIS IS ONLY IF ALL OTHER TRADES
 PASS THEIR REVIEWS. IF THERE ARE COMMENTS FOR ANY OTHER
 TRADES AND PLANS ARE GOING BACK FOR CORRECTIONS, PLEASE
 ADDRESS COMMENT #1 AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]