| 2007-12-11 17:06:29 | **** DENIED 2ND REVIEW **** |
| | |
| | ** AS STATED ON PREVIOUS REVIEW, PLEASE SEE PERMIT # |
| | 07010426 IS STILL ACTIVE. |
| | |
| | 1) NOTE: PLEASE SEE THE NEW LOAD SHOWN ON SHEET A-1 IS |
| | SHOWN AS 1.86 AMPS, HOWEVER THE NEW LOAD SHOWN ON SHEET |
| | A-2 IS 7.5AMPS. |
| | PLEASE ADJUST LOAD CALCULATIONS TO SHOW NEW LOADS BEING |
| | ADDED TO EXISTING PER 220.87 |
| | |
| | 2) NOTE: PLEASE SEE THE *EQUIPMENT GROUNDING CONDUCTOR* |
| | SHOWN FROM EXISTING PANEL TO NEW MAIN AT DETACHED |
| | BUILDING AND FROM DISCONNECT TO PANEL IS SHOWN WITH A |
| | CONDUCTOR SIZE WHICH IS NOT STANDARD PER AWG (AMERICAN |
| | WIRE GAUGE) OR 310.16. |
| | PLEASE KNOW THE MINIMUM SIZE NEEDS TO BE #10 PER |
| | 250.122, 310.16. |
| | PLEASE KNOW THIS IS AN ITEM WHICH COULD BE *REDLINED* |
| | ON PLANS. |
| | PLEASE ADDRESS COMMENT #1 ABOVE. |
| | |
| | ** PLEASE CALL IF ALL OTHER COMMENTS AND ALL OTHER |
| | TRADES PASS REVIEWS. A *PROVISO* MAY BE SET IN PLACE |
| | FOR PERMIT ISSUANCE. THIS IS ONLY IF ALL OTHER TRADES |
| | PASS THEIR REVIEWS. IF THERE ARE COMMENTS FOR ANY OTHER |
| | TRADES AND PLANS ARE GOING BACK FOR CORRECTIONS, PLEASE |
| | ADDRESS COMMENT #1 AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |