| Date |
Text |
| 2007-09-17 11:03:26 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. THE ADDRESS ON THE APPLICATION AND PLANS, (604 |
| | BRADLEY ST.), DOES NOT REFLECT THE ADDRESS FOR THE PCN |
| | NUMBER AND ADDRESS ON OUR SYSTEM. PLEASE CLARIFY. |
| | SECTION 105.3. (SEE ADDRESSING STOP DATED 01-17-2007 ON |
| | PERMIT NUMBER 07010426). INDICATE THE CORRECT ADDRESS |
| | ON THE APPLICATION AND ON THE PLANS. |
| | |
| | 2. PLEASE EXPLAIN WHY THERE ARE TWO PERMITS APPLIED FOR |
| | THE SAME PROJECT. PLEASE SUBMIT A LETTER INDICATING |
| | THAT THE PREVIOUS APPLICATION BE VOIDED OR CLOSED TO |
| | AVOID CONFUSION IN THE FUTURE. (SEE PERMIT NUMBER |
| | 07010426). |
| | |
| | 3. THE LANDSCAPE PLANS SEAL IS NOT APPROVED. SEE FAC |
| | 61G1-16.002 & FS 481.2055. SEAL TO BE APPROX. 2" IN |
| | DIAMETER. |
| | |
| | 4. THE SURVEY SHEET REQUIRES THE SIGNED SEAL TO BE |
| | DATED WHEN THE SEAL AND SIGNATURE ARE AFFIXED TO THE |
| | DOCUMENT. FS 472.025. ALSO SEE ELECTRICAL REVIEW |
| | COMMENT #7CONCERNING STAMPED SIGNATURES WHICH ARE NOT |
| | APPROVED. |
| | |
| | 5. SUBMIT A MINIMUM OF 2 SETS OF PLANS. LOOSE LANDSCAPE |
| | AND SURVEY PLANS ARE NOT APPROVED. COMPLETE BOUND SETS |
| | OF PLANS REQUIRED. SECTIONS 106.1 & 106.1.3. |
| | |
| | 6. SHT A-1 SANITARY PLUMBING RISER DIAGRAM. THE |
| | DRINKING FOUNTAIN IS NOT SHOWN ON THE RISER DIAGRAM. |
| | SECTION 301.3.--ONLY THE FIXTURES WITHIN THE TOILET |
| | ROOM SHALL CONNECT TO THE WET- VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE |
| | DOWNSTREAM OF THE WET VENT. THE MOP SINK AND DRINKING |
| | FOUNTAIN SHALL CONNECT DOWNSTREAM OF THE TOILET ROOM |
| | FIXTURES. SECTION 909.1 (SEE RED LINE EXAMPLE ON ONE |
| | SET OF PLAN TO CORRECT VIOLATION).--SHOW ALL PIPE |
| | SIZES ON SANT. RISER DIAGRAM. TABLES 709.1, 710.1(1) & |
| | 710.1(2). |
| | |
| | 7.SHT A-1 SHOW COMPLIANCE WITH THE FOLLOWING: ___FOR |
| | W/C |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | ___FOR LAV |
| | A. 11-4.19.2 CLEARANCES - 29" REQD. - 28" INDICATED |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | |
| | 8. SHT A-1 DETAIL SHOWS THE W/C 1'6" "MIN" OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE. THE 1'6" MEASUREMENT |
| | IS AN ABSOLUTE MEASURMENT. PLEASE DELETE THE REFERENCE |
| | TO "MINIMUM" . SECTION 11-3.1.--W/C AND LAV ARE TO |
| | BE A MINIMUM OF 30" CENTERLINE OF FIXTURE TO CENTERLINE |
| | OF FIXTURE, NOT 18" AS SHOWN ON THE DETAIL PLEASE |
| | CORRECT DETAIL. SECTION 405.3.1 & FIGURE 504.3.1.-- |
| | ACCESSIBLE LAVS SHALL BE A MINIMUM OF 15" OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE TO BE CENTERED IN THE |
| | 30" OF THE 30"X48" CLEAR FLOOR SPACE. PLEASE INDICATE |
| | ON DETAIL. SECTION 11-4.19.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |