Plan Review Notes
Plan Review Notes For Permit 07080065
Permit Number 07080065
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-02 11:34:35*****DENIED*****
  
  
 1.THE PERMIT NUMBER REGISTERS THE ADDRESS LOCATION AS
 4619 GEORGIA AVENUE AND NOT AS 604 BRADLEY STREET AS
 INDICATED ON THE APPLICATION OR ON THE SUBMITTED PLAN
 SHEETS.
  
 2.IF THE PROJECTED WORK SITE IS ADDRESSED ON BRADLEY
 STREET,THE NUMERICAL ADDRESS SHALL BE AN ODD NUMBER
 SINCE IT IT IS ON THE NORTH SIDE OF THE STREET.
  
 3.ON SHEET A-1,INCLUDE EAST, WEST, NORTH, AND SOUTH
 TO THE APPROPIATE EXTERIOR ELEVATIONS IN ADDITION TO
 WHAT IS LISTED.
  
 4.ON SHEET A-1 UNDER THE FLOOR PLAN LAYOUT, INSERT
 "NFPA 101," IN FRONT OF LIFE SAFETY CODE TO PREVENT
 CONFUSION WITH NFPA-70 (NEC).
  
 5.ON SHEET A-1 IN THE ELECTRICAL NOTES, REFERENCES
 ARE MADE TO SMOKE DETECTORS, BEDROOMS, AND SLEEPING
 AREAS.ARE THESE REFERENCES RELEVANT TO THIS SCOPE OF
 WORK?
  
 6.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THIS STRUCTURE IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722