| 2007-09-07 17:56:54 | |
| | BUILDING PLAN REVIEW |
| | PERMIT07080065 |
| | ADD: 604 BRADLEY ST. |
| | CONT: STONE IMAGE INC. |
| | TEL: (561)547-1177 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 3RD |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | NOTE:THIS PROJECT WAS SUBMITTED PREVIOUSLY UNDER |
| | APPLICATION #07010426 WITH THE ADDRESS AS 4619 GEORGIA |
| | AVE. THE SAME PROJECT IS NOW SUBMITTED WITH A NEW |
| | DIFFERENT APPLICATION #07080065 AND 604 BRADLEY ST AS |
| | THE ADDRESS. PLEASE RECTIFY THIS SITUATION WITH THE |
| | FRONT COUNTER WHEN RESUBMITTING. |
| | |
| | 2)OK |
| | |
| | 3) OK |
| | |
| | 4) OK. |
| | |
| | 5)FBC. 1203.4.2.1 ROOMS CONTAINING BATHTUBS, SHOWERS, |
| | SPAS AND SIMILAR BATHING FIXTURES SHALL BE MECHANICALLY |
| | VENTILATED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, MECHANICAL. |
| | **NEW** |
| | INDICATE ON THE DRAWINGS THE INTERIOR FINISHES OF THE |
| | NEW STRUCTURE. TOILET AND BATHING ROOM FLOORS SHALL |
| | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS |
| | UPWARD ON TO THE WALLS AT LEAST 6 INCHES.WALL WITHIN |
| | 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE THE SAME |
| | TYPE OF SURFACES MENTION ABOVE. FBC1210. NOTE: DRYWALL |
| | WITH PAINT IS NOT CONSIDERED A HARD SURFACE. INDICATE |
| | THE TYPE OF FINISH IN THE BATHROOM FROM THE FINISH |
| | FLOOR TO AT LEAST 4 FEET ABOVE. |
| | |
| | 6)OK |
| | |
| | **NEW** |
| | A)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASE ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY.INTERIOR WALL AND |
| | CEILING FINISH SHALL HAVE A FLAME SPREAD INDEX NOT |
| | GREATER THAN THAT SPECIFIED IN TABLE 803.5. |
| | B)ON SHEET A-2 DETAIL #1 SHOW THE PLYWOOD FASTENERS |
| | AS 8D RING SHANK NAILS, HOWEVER IN THE TABLE WITH THE |
| | SIZE, SPACING AND TYPE OF NAILS HAS 8D PLANE SHANK |
| | NAILS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE |
| | FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS. |
| | CLARIFY. |
| | |
| | C)SHOW THE ACCESSIBLE ROUTE TO THE NEW BUILDING. |
| | 11-4.1.3(1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING |
| | WITH 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND |
| | ELEMENTS WITHIN THE BUILDING OR FACILITY. |
| | |
| | D)11-4.1.3(3) GROUND & FLOOR SURFACES ALONG |
| | ACCESSIBLE ROUTES & IN ACCESSIBLE ROOMS & SPACES SHALL |
| | COMPLY WITH 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) A |
| | STATIC COEFFICIENT OF FRICTION OF 0.6 IS RECOMMENDED |
| | FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS. |
| | |
| | E)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | _XX___1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| | THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| | |
| | _XX__2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: |
| | MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF |
| | EACH ROOF TYPE |
| | |
| | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| | |
| | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | ____6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| | METHOD OF ATTACHMENT YOU ARE USING. |
| | |
| | _XX_7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |