| 2008-06-03 12:12:15 | ** DENIED REVIEW FOR REVISIONS ** |
| | |
| | |
| | ** PLEASE REVISE AND COORDINATE REVISIONS MADE TO |
| | PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THERE ARE ITEMS NOW OFF AND MISSING |
| | FROM THE PLANS WHICH WERE LOCATED ON PREVIOUS PLANS |
| | WHICH ARE JUST NO LONGER ON PLANS. |
| | FOR EXAMPLE: |
| | PLEASE SEE DRIVE SIGNS WHICH USED TO BE CIRCUIT L-30. |
| | PLEASE SEE SOFFIT NEON WHICH USED TO BE ON PLANS ON |
| | EAST SIDE OF BUILDING ALSO. |
| | THESE ARE A COUPLE OF EXAMPLES WHICH COORDINATION IS |
| | NEEDED. THIS MAY NOT BE AN EXHAUSTED LIST. |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND |
| | ADDITIONAL INFORMATION. |
| | NEC 408.4 |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS HAVE HAD SEVERAL REVISED |
| | CIRCUITS FOR LIGHTING ETC YET THE SCHEDULE ON E-300 HAS |
| | NOT BEEN REVISED. |
| | FBC 106.1.2, NEC 408.4 |
| | 13-415.1.ABC.1.1, 13-413.1.ABC.2.1, .2.2. |
| | |
| | 3) NOTE: PLEASE KNOW THE LOCK-OFF DEVICE WHICH IS SHOWN |
| | FOR CIRCUIT L12 FOR EMERGENCY LIGHTS/EXIT LIGHTS SHALL |
| | BE AN INTEGRAL PART OF THE BREAKER. MAY NOT BE OF A |
| | SNAP ON/CLIP ON TYPE. THIS WILL BE FIELD VERIFIED. THIS |
| | IS BEING SHOWN AS AN EXCEPTION TO 700.12E WHICH |
| | REQUIRES ALL EMERGENCY LIGHTS AND EXIT LIGHTS TO BE |
| | CIRCUITED TO LOCAL BRANCH CIRCUIT. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |