| 2007-11-09 12:54:51 | ** DENIED ** | | | | | | | | | 1) NOTE:PLEASE SEE THE LIGHTING POWER CALCULATIONS | | | FOR DESIGN AND ALLOWANCES ARE DIFFERENT ON ELECTRICAL | | | PLANS ON SHEET E-300 THAN ON THE METHOD *C* AS | | | SUBMITTED ALONG WITH SUBMITTALS. | | | PLEASE SEE 13-415.2 AND COORDINATE PLANS/CALCULATIONS. | | | FOR EXAMPLE: MAXIMUM LIGHTING POWER ALLOWANCE AS LISTED | | | ON SHEET METHOD *C* IS SHOWN AS 7,983, YET TABLE | | | CALCULATIONS ON SHEET E-300 SHOWS DESIGN AT 11,397. | | | THIS EXCEEDS THE MAXIMUM AS STATED ON FORM 400C-04. | | | | | | THE LPD ON THE TABLES DOE HOWEVER SHOW A DESIGN LESS | | | THAN THE ALLOWANCE ON THIS SAME SHEET. | | | PLEASE EXPLAIN AND COORDINATE THESE DIFFERENCES. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTIONS SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 |
|