| Date |
Text |
| 2007-09-17 08:58:28 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 EXISTING BUILDING CODE |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. INDICATED THE LEVEL OF ALTERATION PER SECTIONS 303, |
| | 304 OR 305. |
| | |
| | 2. SHT SP-1 OCCUPANCY LOAD. MINIMUM FACILITIES AS SHOWN |
| | ARE NOT CORRECT. THREE W/C'S AND 3 LAVS REQUIRED. |
| | PLEASE CORRECT MINIMUM FACILITIES SHOWN. |
| | |
| | 3. MORE INFORMATION REQUIRED. PLEASE PROVIDE AN |
| | EXISTING FLOOR PLAN PRIOR TO ALTERATIONS TO DETERMINE |
| | THE EXTENT OF THE CHANGES TO THE FLOOR PLAN. SECTION |
| | 106.1.2. |
| | |
| | 4. PER SECTION 606.1 EXIST. BLDG. CODE, A BUILDING, |
| | FACILITY OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH |
| | CHAPTER 11 OF THE FLORIDA BUILDING CODE. THE STALLS IN |
| | ROOMS A117 & A118 SHALL MEET THE REQUIREMENTS OF |
| | 11-4.17.3 EXCEPTION NEW CONTRUCTION (1) & (2). A LAV IS |
| | REQUIRED IN THE STALL, AND THE W/C SHALL BE LOCATED IN |
| | THE CORNER DIAGONAL TO THE DOOR. PLEASE SHOW |
| | COMPLIANCE. |
| | |
| | 5. SUBMIT A DETAIL & ELEVATION FOR THE TECH LUNCH ROOM |
| | SINK. SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL |
| | SUBSECTIONS FOR THE SINK. FORWARD APPROACH IS REQUIRED |
| | AND THE CABINET DOORS ARE NOT ALLOWED IN THE CLEAR |
| | FLOOR SPACE. |
| | |
| | 6. SHT P-100 ALL DEMO'D PIPING BEING CAPPED. IN THE |
| | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS |
| | SHALL BE PROHIBITED. SECTION 704.5. INDICATED HOW THE |
| | CAPPING OF THE PIPING WILL COMPLY. |
| | |
| | 7. SHT P-100 SANITARY RISER DIAGRAM. ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE |
| | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | SECTION 909.1. THE SINK IN THE TECH LUNCH ROOM SHALL |
| | CONNECT DOWNSTREAM OF THE TOILET ROOM FIXTURES. |
| | |
| | 8. A WATER RISER DIAGRAM FOR ALL NEW WORK IS REQUIRED |
| | PER SECTION 106.3.5.1.3(3)(10)(13). PLEASE SUBMIT A |
| | WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES AND |
| | WATER HAMMER ARRESTORS, (IF REQUIRED BY SECTION |
| | 604.9). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |