| Date |
Text |
| 2007-08-25 18:56:30 | 2007-08-25 18:56:30 |
| | |
| | *** DENIED *** |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER |
| | 13. |
| | PLANS INDICATE SEPARATE SPACE CONTROL FOR MOST AREAS, |
| | HOWEVER PLEASE CLARIFY AREAS SUCH AS THE MANAGER'S |
| | OFFICES,A108 AND SOME OTHER SEPARATE SPACES. |
| | 13-415.1.ABC.1.2 |
| | PLEASE SUBMIT INFORMATION FOR MAXIMUM TIMES FOR THE |
| | OVER RIDE AND OCCUPANCY SENSOR TYPE DEVICES AS SHOWN ON |
| | PLANS. THESE COULD NOT BE LOCATED ON THE SYMBOL LEGEND |
| | AND INFORMATION THE TYPE OF THE DEVICES. PLEASE SEE THE |
| | BATHROOMS ARE INDICATING A OC DEVICE WHICH IS OK, |
| | HOWEVER PLEASE EXPAND ON THE TYPE OF DEVICE. WILL THIS |
| | BE A COMBINATION DEVICE WHICH PROVIDES COVERAGE FOR |
| | BLIND SPOTS , STALLS. (ULTRASONIC TYPE?) |
| | PLEASE SUBMIT THE TIMED SCHEDULING INFORMATION. THE |
| | PLANS INDICATE THE LIGHTING TO A TIME CLOCK HOWEVER NO |
| | INFORMATION OR DETAIL FOR THIS WAS SUBMITTED OR COULD |
| | BE LOCATED ON PLANS. |
| | PLEASE PROVIDE OVER RIDE DEVICES, LOCATIONS AND TIMES |
| | PER 13-415.1.ABC.1.1, .1.2. |
| | PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO |
| | ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA |
| | COORDINATES WITH THE PLANS. |
| | PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS |
| | PER 13-415.2. |
| | PLEASE SEE PLEASE KNOW AT THIS TIME NOT REVIEW FOR |
| | LIGHTING COMPLIANCE CAN BE DONE FOR INTERIOR AND |
| | EXTERIOR LIGHTING POWER ALLOWANCES. PLEASE SEE |
| | 13-415.2, 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, |
| | 13-415.2.ABC.1.1 |
| | |
| | 3) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF THE |
| | EMERGENCY/EXIT LIGHTS. THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. PLEASE SHOW AND ADJUST |
| | CIRCUITING. |
| | |
| | 4) NOTE: PLEASE IDENTIFY THE CIRCUITS ON THE PANEL |
| | SCHEDULE AS NEW OR EXISTING. SOME OF THESE ARE ALREADY |
| | DONE FOR THE NEW A/C EQUIPMENT. |
| | PLEASE SEE THESE CAN BE SIMPLY DONE BY AN *E* OR *N* ON |
| | THE BRANCH CIRCUITS ON PANEL SCHEDULE OR AN *ASTERISK* |
| | WITH A NOTE AT THE BOTTOM OF PANEL SCHEDULE OR BY ANY |
| | OTHER MEANS DECIDED BY THE DESIGN PROFESSIONAL. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |