Plan Review Notes For Permit 07080046
Permit Number 07080046
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-20 09:01:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT
 WITH THE FOLLOWING:
  
 1} THE PANEL SHOWN IN THE NEW LAUNDRY ROOM IS LABLED
 50 AMPS. THE RISER SHOWS A NEW 60 AMP PANEL IN THE
 GARAGE. PROVIDE A SITE PLAN INDICATING THE LOCATION OF
 ALL SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE
 230 CAN BE REVIEWED.
  
 2} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE
 SEPARATE STRUCTURE PER 250.32, SIZED PER 250.66.
 INSTALL ON THE RISER, SEE 250.52(A)(3) FOR FOOTER
 STEEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.