2007-12-18 06:51:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 4TH TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE PREVIOUS PLAN REVIEW COMMENTS WERE ADDRESSED
 HOWEVER WITH THE ADDITION OF THE NEW HANDICAP BATHROOM
 THE FOLLOWING IS REQUIRED.
 NOTE: THE REQUIRED FIXTURE CLEAR FLOOR SPACE AND
 WHEELCHAIR TURNING SPACE SHALL ALSO BE INDICATED ON THE
 FLOOR PLAN.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
 .
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37) 11-4.21.5
 CONTROLS. REQUIRED (SEE FIGURE 37) 11-4.21.7 CURBS. 36"
 X 36" MAXIMUM 1/2" CURB (NO CURB REQUIRED IN MINIMUM
 30" X 60" STALLS)
  
 **11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 END OF COMMENTS:
  