Plan Review Notes
Plan Review Notes For Permit 07080045
Permit Number 07080045
Review Stop B
Sequence Number 4
Notes
Date Text
2007-12-15 16:07:39BUILDING PLAN REVIEW
 PERMIT: 07080045
 ADD: 1604 CLARE AVE
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 4TH
 ACTION: DENIED
 12/15/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE
 INFORMATION SHALL BE SUBMITTED.
 **NOTED**SHEETS WERE REMOVED FROM PACKAGE.
 4)OK
 5)OK
 6) NOTE: IF THIS IS A TEMPORARY STURCTURE, IT SHALL
 CONFORM TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180
 DAYS.
 **THE RESPONSE SHEET STATES THAT THE WORK ?TEMPORARY?
 WILL BE REMOVED FROM THE APPLICATION. DOES THIS MEAN
 THAT THE STRUCTURE WILL NOW BE ?PERMANENT??**
  
  
  
  
 7)OK
  
 **NO RRESPONSE NOT ADDRESSED**
 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND
 CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE
 VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF
 GLASS AT THE BATHROOM SHOWER FBC.2406/
 **NEW**
 SHOW THE ATTACHMENT DETAIL OF THE FLOOR JOIST TO THE
 EXISTING FLOOR INDICATING THE MATERIALS. THE HEADER AND
 SILL FRAMING DETAIL SHALL BE SHOWN ON THE DRAWINGS. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS AND OTHER DATA NECESSARY TO DESCRIBE
 THE CONSTRUCTION OR INSTALLATION OF THE PROJECT. WPB
 AMENDMENTS 106.1.2
 **(A)PROVIDE A NORTH, SOUTH, EAST AND WEST FRAMING
 ELEVATION OF THE STRUCTURE SHOWING EACH OPENING WITH
 THE FRAMING DETAILS.
  
 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR
 HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE
 BUILDING.
  
 **NEW**
 10)OK.
  
 **NO RRESPONSE NOT ADDRESSED**
 11)SHOW THE ACCESSIBLE ROUTE TO THE UNIT MEET THE
 REQUIREMENTS OF SECTION 11-4.3.1
 **NEW** FBC 11-4.5.2 CHANGES IN LEVEL GREATER THAN ?
 INCH SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT
 COMPLIES WITH SECTION 11-4.7 OR 11-4.8. SHOW
 COMPLIANCE. THIS IS REQUIRED DUE TO THE FACT THAT THERE
 ARE STEPS LEADING TO THE ENTRANCE OF THE ROOM. ALL
 RAMPS SHALL BE STABLE, FIRM, SLIP RESISTANT, AND SHALL
 COMPLY WITH SECTION 11-4.5.LANDINGS AT RAMPS SHALL
 MEET THE REQUIREMENTS OF 11-4.8.4 AND 11-4.13.6 SHOW IN
 DETAIL DRAWINGS HOW THESE REQUIREMENTS WILL BE
 ACCOMPLISHED.
 **(A) ALL LANDINGS ON RAMPS SHALL BE NOT LESS THAN 60
 INCHES CLEAR, AND THE BOTTOM OF EACH RAMP SHALL HAVE
 NOT LESS THAN 72 INCHES OF STRAIGHT AND LEVEL
 CLEARANCE. 11-4.8.4(2)
 **(B) IF A RAMP RUN HAS A RISE GREATER THAN 6 INCHES,
 THEN IT SHALL HAVE HANDRAILS ON BOTH SIDES. THE
 INFORMATION ABOVE SHALL BE CLEARLY INDICATED ON THE
 DRAWINGS. THE DRAWINGS SUBMITTED DO NOT SHOW ALL THE
 REQUIREMENTS FOR THE RAMP CLEARLY. SUBMIT ELEVATION
 DRAWINGS SHOWING THE SLOPE AND RISE, CLEAR WIDTH,
 LANDINGS AND HANDRAILS WITH ALL REQUIRED DIMENSIONS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS O THIS CODE. 106.1.1**
  
 **NO RRESPONSE NOT ADDRESSED**
 12)SHOW ON THE ON THE DRAWINGS THE EXISTING BATHROOM
 FACILITIES. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. FBC 106.1.1.
 **(A) BATHROOMS, BATHING FACILITIES, OR SHOWER ROOMS
 REQUIRED TO BE ACCESSIBLE SHALL COMPLY WITH SECTION
 11-4.23 AND SHALL BE ON AN ACCESSIBLE ROUTE. THE CLEAR
 FLOOR SPACE AND TURNING SPACE SHALL BE INDICATED ON THE
 PLANS.
 **(B) SHOWER STALL SIZE AND CLEAR FLOOR SPACE SHALL
 COMPLY WITH FIGURE 35(A) OR FIGURE 35(B). A SEAT SHALL
 BE PROVIDED IN SHOWER STALLS 36 INCHES BY 36 INCHES AND
 SHALL BE AS SHOWN IN FIGURE 36.11-4.21.3
  
 **NO RRESPONSE NOT ADDRESSED**
 13)A DETAIL LETTER INDICATING THE USE/ OCCUPANCY AND
 PURPOSE OF THE STRUCTURE CAN ALSO SUBMITTED BY THE
 OWNER. THE LETTER SHALL BE CLEAR AND PRECISE STATING
 THAT THE SPACE IS ONLY USED AS A SHOW ROOM.
  
 **NEW**
 14)OK
  
 15)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  