| 2007-12-05 13:57:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 3RD TIME: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | THE RESUBMITTED PLAN FOR PLUMBING PLAN REVIEW TO MEET |
| | CODE COMPLIANCE. |
| | |
| | 1. FULL-OPEN VALVES SHALL BE INSTALLED IN THE |
| | FOLLOWING LOCATIONS. PER *106.1, LOCATION OF FULL-OPEN |
| | VALVES. |
| | |
| | A} ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE |
| | ENTRANCE INTO THE STRUCTURE. |
| | |
| | B} ON THE WATER SUPPLY PIPE TO EVERY WATER HEATER. |
| | |
| | 2. WATER HAMMER ARRESTORS SHALL BE INSTALLED WHERE |
| | QUICK CLOSING VALVES ARE UTILIZED. PLEASE PROVIDE WATER |
| | HAMMER ARRESTORS FOR THE COLD AND HOT WATER ON THE |
| | WASHING MACHINE. PER *604.9, WATER HAMMER. |
| | |
| | 3. CLEARLY IDENTIFY THE BACKFLOW PREVENTER AND WATER |
| | METER ON THE RESUBMITAL. PER *106.1.1, INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 4. THE WATER HEATER REQUIRES A PAN. PER *504.7, PAN |
| | REQUIRED: PAN DRAIN FOR WATER HEATER MINIMUM DIAMETER |
| | IS 3/4". PER 504.7.1, PAN SIZE AND DRAIN: PAN DRAIN |
| | SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND |
| | TERMINATE NOT LESS THAN 6" AND NOT MORE THAN 24" ABOVE |
| | ADJACENT GROUND SURFACE. PER *504.7.2, PAN DRAIN |
| | TERMINATION. |
| | |
| | 5. RELIEF VALVE REQUIRED FOR THE WATER HEATER. PER |
| | *504.4, RELIEF VALVE: THE RELIEF VALVE SHALL DISCHARGE |
| | FULL SIZE TO A SAFE PLACE OF DISPOSAL SUCH AS THE |
| | HEATER PAN OR OUTSIDE THE BUILDING. PER *504.6.1, |
| | DISCHARGE. |
| | |
| | 6. THERMAL EXPANSION CONTROL IS REQUIRED FOR THE WATER |
| | HEATER. PER *607.3, THERMAL EXPANSION CONTROL AND |
| | *607.3.2, BACKFLOW PREVENTION DEVICE OR CHECK VALVE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |