Plan Review Notes
Plan Review Notes For Permit 07080045
Permit Number 07080045
Review Stop P
Sequence Number 3
Notes
Date Text
2007-12-05 13:57:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 07 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 3RD TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE RESUBMITTED PLAN FOR PLUMBING PLAN REVIEW TO MEET
 CODE COMPLIANCE.
  
 1. FULL-OPEN VALVES SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS. PER *106.1, LOCATION OF FULL-OPEN
 VALVES.
  
 A} ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE
 ENTRANCE INTO THE STRUCTURE.
  
 B} ON THE WATER SUPPLY PIPE TO EVERY WATER HEATER.
  
 2. WATER HAMMER ARRESTORS SHALL BE INSTALLED WHERE
 QUICK CLOSING VALVES ARE UTILIZED. PLEASE PROVIDE WATER
 HAMMER ARRESTORS FOR THE COLD AND HOT WATER ON THE
 WASHING MACHINE. PER *604.9, WATER HAMMER.
  
 3. CLEARLY IDENTIFY THE BACKFLOW PREVENTER AND WATER
 METER ON THE RESUBMITAL. PER *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. THE WATER HEATER REQUIRES A PAN. PER *504.7, PAN
 REQUIRED: PAN DRAIN FOR WATER HEATER MINIMUM DIAMETER
 IS 3/4". PER 504.7.1, PAN SIZE AND DRAIN: PAN DRAIN
 SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND
 TERMINATE NOT LESS THAN 6" AND NOT MORE THAN 24" ABOVE
 ADJACENT GROUND SURFACE. PER *504.7.2, PAN DRAIN
 TERMINATION.
  
 5. RELIEF VALVE REQUIRED FOR THE WATER HEATER. PER
 *504.4, RELIEF VALVE: THE RELIEF VALVE SHALL DISCHARGE
 FULL SIZE TO A SAFE PLACE OF DISPOSAL SUCH AS THE
 HEATER PAN OR OUTSIDE THE BUILDING. PER *504.6.1,
 DISCHARGE.
  
 6. THERMAL EXPANSION CONTROL IS REQUIRED FOR THE WATER
 HEATER. PER *607.3, THERMAL EXPANSION CONTROL AND
 *607.3.2, BACKFLOW PREVENTION DEVICE OR CHECK VALVE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  