| Plan Review Notes For Permit 07080045 |
| Permit Number |
07080045 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-12-12 14:50:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) 401.5.1 INTAKE OPENINGS. | | | MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS | | | SHALL BE LOCATED A MINIMUM OF 10 FEET FROM ANY | | | HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | | AND LOADING DOCKS, EXCEPT AS OTHERWISE SPECIFIED IN | | | THIS CODE. FRESH AIR INTAKES SHALL NOT BE LOCATED | | | CLOSER THAN 10 FEET (3048 MM) FROM ANY CHIMNEY OR VENT | | | OUTLET, OR SANITARY SEWER VENT OUTLET. | | | | | | 2) PLEASE SHOW OUTDOOR AIR CALCULATIONS, AND | | | INFORMATION REGARDING SUPPLY FAN, SEE 2004 FBC/M | | | 403.2. | | | | | | 3) THE NEW HANDICAPPED BATHROOM REQUIRES A EXHAUST FAN | | | ALSO, SEE 2004 FBC/M 402.3.1 AND NOTE #1 ABOVE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|