2007-12-12 14:50:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) 401.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS, EXCEPT AS OTHERWISE SPECIFIED IN
 THIS CODE. FRESH AIR INTAKES SHALL NOT BE LOCATED
 CLOSER THAN 10 FEET (3048 MM) FROM ANY CHIMNEY OR VENT
 OUTLET, OR SANITARY SEWER VENT OUTLET.
  
 2) PLEASE SHOW OUTDOOR AIR CALCULATIONS, AND
 INFORMATION REGARDING SUPPLY FAN, SEE 2004 FBC/M
 403.2.
  
 3) THE NEW HANDICAPPED BATHROOM REQUIRES A EXHAUST FAN
 ALSO, SEE 2004 FBC/M 402.3.1 AND NOTE #1 ABOVE.
  
 MECHANICAL PLAN REVIEW BY;