| 2007-10-12 23:14:34 | *****DENIED***** |
| | |
| | |
| | 01.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE |
| | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET (INCLUDING |
| | CONSTRUCTION DOCUMENTS). |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR |
| | HINDER ACCESS TO OR EGRESS FROM THE SAID PROPERTY.ALL |
| | EXIT COMPONENTS ARE TO BE MAINTAINED. |
| | |
| | 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 05. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 06.THE DOOR TO THE TEMPORARY STRUCTURE IS TO REMAIN |
| | LOCKED DURING NON VIEWING TIMES. |
| | |
| | 07.SPECIFY THE HAZARD OF CONTENTS OF THE STRUCTURE AS |
| | CLASSIFIED AS LOW, ORDINARY, OR HIGH. |
| | |
| | 08.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN |
| | TERRMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 09.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF |
| | CLASS I OR CLASS II. |
| | |
| | 10.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE SPRINKLER REMODEL.NFPA 13 - 2002 EDITION SHALL |
| | BE REFERENCED.PLEASE BE ADVISED THAT SUB-PERMITS |
| | SHALL NOT BE REVIEWED AND APPROVED BY THIS OFFICE UNTIL |
| | SUCH TIME THAT THE MASTER PERMIT HAS BEEN ISSUED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS |
| | ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |