Plan Review Notes
Plan Review Notes For Permit 07080045
Permit Number 07080045
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-10-12 23:14:34*****DENIED*****
  
  
 01.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET (INCLUDING
 CONSTRUCTION DOCUMENTS).
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER ACCESS TO OR EGRESS FROM THE SAID PROPERTY.ALL
 EXIT COMPONENTS ARE TO BE MAINTAINED.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 06.THE DOOR TO THE TEMPORARY STRUCTURE IS TO REMAIN
 LOCKED DURING NON VIEWING TIMES.
  
 07.SPECIFY THE HAZARD OF CONTENTS OF THE STRUCTURE AS
 CLASSIFIED AS LOW, ORDINARY, OR HIGH.
  
 08.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERRMS OF CLASS A, CLASS B, OR CLASS C.
  
 09.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF
 CLASS I OR CLASS II.
  
 10.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.NFPA 13 - 2002 EDITION SHALL
 BE REFERENCED.PLEASE BE ADVISED THAT SUB-PERMITS
 SHALL NOT BE REVIEWED AND APPROVED BY THIS OFFICE UNTIL
 SUCH TIME THAT THE MASTER PERMIT HAS BEEN ISSUED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW