| Plan Review Notes For Permit 07080045 |
| Permit Number |
07080045 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-10-03 16:29:02 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET E-P, UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | 1} PER 700.12(F)(4) THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT | | | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | | AHEAD OF ANY LOCAL SWITCHES. INDICATE SAME ON PLANS , | | | WITH CIRCUITS NUMBERED. | | | | | | 2} RECEPTACLE SPACING MUST COMPLY WITH 210.60 AND | | | LIGHTING PER 210.70(B), LOCATE SAME ON PLANS. | | | | | | 3} THE LOAD CALCULATION MUST BE PER 220.44. | | | | | | 4} INDICATE CONDUCTOR AND CONDUIT SIZES AND TYPE FOR | | | THE FEEDER TO THE SUB PANEL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|