 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET E-P, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PER 700.12(F)(4) THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. INDICATE SAME ON PLANS ,
 WITH CIRCUITS NUMBERED.
  
 2} RECEPTACLE SPACING MUST COMPLY WITH 210.60 AND
 LIGHTING PER 210.70(B), LOCATE SAME ON PLANS.
  
 3} THE LOAD CALCULATION MUST BE PER 220.44.
  
 4} INDICATE CONDUCTOR AND CONDUIT SIZES AND TYPE FOR
 THE FEEDER TO THE SUB PANEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  