Plan Review Notes
Plan Review Notes For Permit 07080045
Permit Number 07080045
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-28 12:33:03 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONE COMPLIANT WITH THE FOLLOWING:
  
 1} THE SCOPE OF WORK IS UNCLEAR. SUBMIT PLANS PER
 106.3.5.1.2 FBC. PANEL SCHEDULES, FLOOR PLANS, LOAD
 CALCS, CIRCUIT NUMBERS PANEL DESIGNATIONS, EXIT AND
 EMERGENCY LIGHTING, ETC.
  
 2} AN ELECTRICALPERMIT FOR THIS BUILDING WAS RECENTLY
 ISSUED, # 07070451, TO REPAIROR REPLACE FIXTURES. THE
 STATED USE AT THAT TIME WAS WAREHOUSE.THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 3} DECLARE THE TYPE OF OCCUPANY AND USE PER SECTION
 306
 CHANGE OF OCCUPANCY
 306.1SCOPE.
 CHANGE OF OCCUPANCY PROVISIONS APPLY WHERE THE ACTIVITY
 IS CLASSIFIED AS A CHANGE OF OCCUPANCY AS DEFINED IN
 CHAPTER 2.
 306.2APPLICATION.
 CHANGES OF OCCUPANCY SHALL COMPLY WITH THE PROVISIONS
 OF CHAPTER 8.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]