Plan Review Notes
Plan Review Notes For Permit 07080045
Permit Number 07080045
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-21 12:41:57BUILDING PLAN REVIEW
 PERMIT: 07080045
 ADD: 1604 CLARE AVE
 CONT: BENITZ BUILDING LLC
 TEL: (561)659-4024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)IF THERE IS A SPRINKLER SYSTEM IN THE BUILDING, THE
 MODEL ROOMS SHALL BE PROTECTED WITH SPRINLERS. SHOW THE
 SPRINKLER-HEADS SHALL BE INDICATED ON THE CEILING
 PLAN.
  
 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE
 INFORMATION SHALL BE SUBMITTED.
  
 4)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 5)INDICATE IF THE MOCK-UP ROOMS WILL BE CONSTRUCTED
 IN A NEW BUILDING OR A RENOVATED BUILDING. WILL THIS
 PROJECT INVOLVED A CHANGE OF OCCUPANCY? IF SO SEE FBC
 EXISTING CH.8.
  
 6)IF THIS IS A TEMPORARY STURCTURE, IT SHALL CONFORM
 TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 DAYS.
  
 7)A LEGEND WITH THE WALL DETAILS SHALL ALSO BE
 SUBMITTED, ALONG WITH THE WALL FINISHES COMPLYING WITH
 FBC SEC. 803/ 804 AND 805.
  
 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND
 CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE
 VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF
 GLASS AT THE BATHROOM SHOWER FBC.2406/
  
 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR
 HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE
 BUILDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved