| Date |
Text |
| 2007-08-21 12:41:57 | BUILDING PLAN REVIEW |
| | PERMIT: 07080045 |
| | ADD: 1604 CLARE AVE |
| | CONT: BENITZ BUILDING LLC |
| | TEL: (561)659-4024 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)IF THERE IS A SPRINKLER SYSTEM IN THE BUILDING, THE |
| | MODEL ROOMS SHALL BE PROTECTED WITH SPRINLERS. SHOW THE |
| | SPRINKLER-HEADS SHALL BE INDICATED ON THE CEILING |
| | PLAN. |
| | |
| | 3)BEFORE THE MOCK-UP ROOMS CAN BE APPROVED, MORE |
| | INFORMATION SHALL BE SUBMITTED. |
| | |
| | 4)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT |
| | . ------------------------------------- |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | ) NUMBER OF BEDROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | |
| | 5)INDICATE IF THE MOCK-UP ROOMS WILL BE CONSTRUCTED |
| | IN A NEW BUILDING OR A RENOVATED BUILDING. WILL THIS |
| | PROJECT INVOLVED A CHANGE OF OCCUPANCY? IF SO SEE FBC |
| | EXISTING CH.8. |
| | |
| | 6)IF THIS IS A TEMPORARY STURCTURE, IT SHALL CONFORM |
| | TO FBC. SEC 107. WHIC HAS A TIME LIMIT OF 180 DAYS. |
| | |
| | 7)A LEGEND WITH THE WALL DETAILS SHALL ALSO BE |
| | SUBMITTED, ALONG WITH THE WALL FINISHES COMPLYING WITH |
| | FBC SEC. 803/ 804 AND 805. |
| | |
| | 8)ADDITIONAL STRUCTURAL DETAIL ON THE FLOOR AND |
| | CEILING STUDS WILL ALSO BE REQUIRED, ALSO THE |
| | VENTILATION PER 1203 AND 1210 OF THE FBC. THE TYPE OF |
| | GLASS AT THE BATHROOM SHOWER FBC.2406/ |
| | |
| | 9) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | THERE MAY BE OTHER COMMENTS FOR ACCESSIBILITY AND FAIR |
| | HOUSING DEPENDING ON THE USE AND OCCUPANCY OF THE |
| | BUILDING. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |